40
airflow;
HIGH
means 250% of maximum assessed airflow; and
NO LIMIT
means
the equipment does not stage down.
CFM associated for each limit is shown on the screen. Compare this value with the
equipment’s low stage CFM value to ensure that equipment will run for each zone.
Assessed airflow is determined as described in
DUCT ASSESSMENT
.
After the selections are made, touch
SAVE
.
S
Touch the zone name that you wish to change
S
Select the zone to adjust airflow:
Low, Med--Low, Medium, Med--High, High,
or No Limit
d
Default = High
6.3.6.4.
Duct Assessment Time
This option allows the installer to select the time in which the duct assessment will
be performed. After the selection is made, touch
SAVE
.
S
Duct Assessment Time:
Selectable between 12 AM and 11PM
d
Default = 1 PM
6.3.7.
Accessories
First touch
SETUP
, then touch
ACCESSORIES
to set up the parameters for the
accessories installed with the system.