background image

28

Table 7 – Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan

will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, HP/AC control board,

or high--pressure, loss--of--charge or low--pressure

switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

User Interface setting too low/too high

Reset UI setting

DO NOT bypass this compressor time

delay–wait for 5 minutes until time--delay

relay is de--energized

Units have a 5--minute time delay

Compressor will not start but outdoor fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

Low input voltage

Determine cause and correct

Compressor cycles (other than normally satis-

fying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Damaged reversing valve

Determine cause and correct

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

UI temperature set too low/too high

Reset UI setting

Low refrigerant charge

Locate leak, repair, and recharge

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

(Heat) Indoor air restricted or recirculating

Determine cause and correct

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

(Cool) High Heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

(Cool) Dirty air filter

Replace filter

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

(Cool) Insufficient coil airflow

Increase air quantity

Check filter–replace if necessary

(Cool) Temperature too low in conditioned area

Reset UI setting

(Cool) Outdoor ambient below 55

°

F (13

_

C)

Verify low--ambient cooling enabled in UI

Filter drier restricted

Replace

IFM does not run

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly sealed

Connectors should snap easily; do not force

IFM operation is intermittent

Water dripping into motor

Verify proper drip loops in connector wires

Connectors not firmly sealed

Gently pull wires individually to be sure they are

crimped into the housing

IFM--Indoor Fan Motor

50X

T

--

A

Содержание Infinity 15 SEER 50XT-A

Страница 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Страница 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Страница 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Страница 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Страница 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Страница 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Страница 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Страница 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Страница 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Страница 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Страница 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Страница 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Страница 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Страница 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Страница 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Страница 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Страница 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Страница 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Страница 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Страница 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Страница 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Страница 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Страница 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Страница 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Страница 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Страница 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Страница 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Страница 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Страница 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Страница 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Отзывы: