LLS

Liquid Line Solenoid

UTILITY RELAY  

*

UTILITY SIGNAL

OPEN RELAY

*

 SUPPLIED BY UTILITY PROVIDER

A05247

Fig. 16 -- 2--Stage HP/AC Control Board

B. Control

Start--Up

and

System

Communications

Troubleshooting

On power up, green COMM LEDs will be turned off until
successful system communications are established (this should

happen within 10 seconds). Once communications with UI are
successful, both COMM LEDs will be lit and held on. At the same

time, amber STATUS LEDs will be lit and held continuously on
until a request for operating mode is received. The STATUS LED

will be on any time unit is in idle mode.
If, at any time, communications are not successful for a period
exceeding 2 minutes, the Infinity control will only allow

emergency heating or cooling operation using a common
thermostat and the terminal strip connections on the two control

boards (see Non--Communicating Emergency Cooling/Heating

Mode) and will display Status Code 16, System Communication
Fault, on amber STATUS LED. No further troubleshooting

information will be available at UI until communications are
re--established.
If either COMM LED does not light within proper time period and

status codes are not displayed;

1. Check system transformer high-- and low--voltage to be sure

the system is powered.

2. Check ABCD connection on both boards.
3. Check fuse on fan coil board to be sure it is not blown. If

fuse is open, check system wiring before replacing it to be
sure a short does not cause a failure of replacement fuse.

If COMM LED does not light within proper time period and status
code is displayed,

1. Check system wiring to be sure UI is powered and

connections are made A to A, B to B, etc. and wiring is not

shorted.

Mis--wiring

or

shorting

of

the

ABCD

communications wiring

will not allow successful

communications.

NOTE

: Shorting or mis--wiring low--voltage system wiring will

not cause damage to unit control or UI but may cause low voltage
fuse to open.

C. Indoor Fan Motor (IFM) Troubleshooting

The indoor fan is driven by an Electronic Computated Motor

(ECM) which consists of two parts: the control module and the
motor winding section. Do not assume motor or module is

defective if it will not start. Use the designed--in LED information

aids and follow troubleshooting steps described below before
replacing motor control module or entire motor. Motor control

module is available as a replacement part.
VERIFY MOTOR WINDING SECTION

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
After disconnecting power from the ECM motor, wait at

least 5 minutes before removing the control section. Internal

capacitors require time to discharge.

!

WARNING

Before proceeding to replace a motor control module:

1. Check motor winding section to be sure it is functional.
2. Remove motor control module section and unplug winding

plug. Motor shaft should turn freely, resistance between any
two motor leads should be similar and resistance between

any motor lead and unpainted motor end should exceed
100,000 ohms.

3. Failing any of these tests, entire ECM motor must be

replaced.

4. Passing all of the tests, motor control module alone can be

replaced.

50X

T

--

A

Содержание Infinity 15 SEER 50XT-A

Страница 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Страница 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Страница 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Страница 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Страница 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Страница 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Страница 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Страница 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Страница 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Страница 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Страница 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Страница 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Страница 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Страница 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Страница 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Страница 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Страница 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Страница 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Страница 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Страница 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Страница 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Страница 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Страница 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Страница 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Страница 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Страница 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Страница 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Страница 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Страница 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Страница 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Отзывы: