BACview® system screens
BACview®
CARRIER CORPORATION ©2021
Installation and User Guide
All rights reserved
22
Screen
Description
BACnet
Time
Master
For: RTU Open and WSHP
Navigate to:
System Settings
>
TimeMstr
For: i-Vu® Open Router
Navigate to:
TimeMstr
The network should have only one BACnet Time Master that issues time broadcasts.
Set
Time Sync Mode
to:
•
No Broadcast
if this controller is not the BACnet Time Master.
•
Local Broadcast
to have the controller send time broadcasts only to controllers on his
locally connected MS/TP network.
•
Global Broadcast
to have the controller send time broadcasts to all controllers and all
MS/TP networks in the system.
Set
Time Sync Interval
to how often the time broadcast should be sent (1-9999 minutes).
Local
Schedule
For: RTU Open, WSHP, VVT Zone, and VVT Bypass controllers
Navigate to:
Config
>
Sched
See
Setting local schedules
(page 23).