OPERATION MANUAL 

FOR DN-107NE DISPLAYS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

1227K27D 

Summary of Contents for DN-107NE

Page 1: ...OPERATION MANUAL FOR DN 107NE DISPLAYS 1227K27D ...

Page 2: ...PERATION 1 4 1 Initial start up 1 4 2 Parameter programming 1 4 2 1 Enter to modify parameters 2 4 2 2 Exit modify parameters 2 4 2 3 Function of each parameter 2 4 3 Protocols 5 4 3 1 TCP IP Protocol 5 4 3 2 UDP Protocol 5 4 3 3 Modbus TCP Protocol 6 4 3 4 Valid Characters 8 4 4 IP Address 10 4 5 Modifying the port settings 10 4 5 1 Configure to use the UDP IP protocol 11 4 6 Colour configuration...

Page 3: ...net network and can be configured for use with TCP IP UDP et Modbus TCP protocols The selection of the parameters and the communication protocol is done using two buttons with a system of easily programmable codes The digit height 57mm allows a reading distance up to 30m is one of the main characteristics ETHERNET 1 INTRODUCTION ETHERNET ...

Page 4: ...er memory Eeprom Communication Ethernet 10 100 RJ 45 connector Communication Protocols TCP IP UDP IP and Modbus TCP Environmental Conditions Operation Temperature 20 to 60ºC Storage temperature 30ºC to 70ºC Humidity 5 95 RH non condensing Maximum environmental illumination 1000 lux Sealing IP41 2 GENERAL CHARACTERISTICS 2 1 Electrical characteristics of the displays 2 1 1 Electrical characteristic...

Page 5: ...TICS CHAPTER 2 245 120 70 40 All the measurements are in millimeters 245 120 70 40 All the measurements are in millimeters 2 2 1 Dimensions of the displays DN 107 3 2 2 2 DN 119 weight and power consumption 2 2 Dimensions and fixing of the displays ...

Page 6: ...CHAPTER 2 GENERAL CHARACTERISTICS 2 3 DN 107NE display series 100 150 400 600 90 º 73 5 7 15 52 52 All the measurements are in millimeters 2 2 3 Fixing of the displays DN 107 M8 Fixing plate ...

Page 7: ...ith an illumination level in excess of 1000 lux Neither should the display be placed in direct sunlight as visibility would be lost In the electrical installation proximity to lines of high intensity circulation and high voltage lines must be avoided as well as proximity to High Frequency generators and U F converters for motors The power supply must be 88 to 264 VAC 47 to 63Hz or 19 to 36VDC The ...

Page 8: ...ink can be done in two ways Direct connection using a crossover cable or connection via a switch type concentrator or hub and a category 5 100Base T4 cable is recommended For direct connection between a computer and a display a crossover cable must be used ETHERNET To connect various displays a switch type concentrator or hub must be used with a port for each unit ETHERNET 3 2 Connecting to the Et...

Page 9: ...rk and displays it The display does not receive data and the time without data equals zero Continues to show the decimal points The display does not receive data and the time without data is not equal to zero After a time without data it displays a dash in each digit Displays DN 107NE can be adapted to the specifications of each client by the programming of parameters The parameters which can be c...

Page 10: ...ameter may be selected using the key The number if the parameter is The left one when the decimal dot is activated in 2 digit displays In 3 or more digits displays the third digit starting from the right In order to exit the sequence for modifying parameters parameter F must be selected then press 0 Protocols TCP IP and UDP IP 1 Protocol Modbus TCP Function 06h and Function 10h ASCII 2 Protocol Mo...

Page 11: ... end of block is the one selected in parameter 2 If value 1 has been selected the 06h code is sent followed by the block selected in parameter 2 If value 2 has been selected the ACK characters are sent followed by the block selected in parameter 2 The MAC code is a code which identifies each port which connects to an Ethernet network It is unique to each unit and is needed to configure the port Th...

Page 12: ... 99 must be input and the advance key pressed During the parameter loading time the three digits are displayed flashing When finished parameter 6 is displayed wished In order to exit parameter configuration press the key Before exit the parameters are saved If you wish continue modifying parameters press the key until arrive parameter 4 2 3 6 Parameter 6 Load the default configuration to the port ...

Page 13: ...end of block that is recognized by the display The end of block coding which the display expects to receive can be found in 4 2 3 2 Parameter 2 End of Block Only TCP IP and UDP IP protocols The last character sent is displayed on the right of the display Local Port 10001 must be used In order for the display to be able to accept a block it must end with an end of block that is recognized by the di...

Page 14: ... 06h 00h 02h F000h Response from the display The response from the display is the same block received It allows the user to send blocks with ASCII characters to the display Parameter 1 must have value 2 See 4 2 3 1 Parameter 1 Protocol In the block the following values must be codified Unit 01h Function 10h It allows to use integers with or without sign The address sent determines if the values ar...

Page 15: ...Dh 01h 10h 00h 06h In this example the visualized value is 123456 78 Response from the display The response from the display is the same block received from the identifier until the number of registers Identifier Protocol Number of bytes Unit Function Start Address Number of registers 01h 65h 00h 00h 00h 0Dh 01h 10h 00h 06h 00h 03h It the user to send blocks with ASCII characters to the display Pa...

Page 16: ... the visualized value is 4268 3 Numerical displays can only display numbers and some characters All valid characters and their representation in hexadecimal format are shown below Character 0 1 2 3 4 5 6 7 8 9 A B HEXA 30h 31h 32h 33h 34h 35h 36h 37h 38h 39h 41h 62h DEC 48d 49d 50d 51d 52d 53d 54d 55d 56d 57d 65d 98d Character C c d E F H h i J L n O HEXA 43h 63h 64h 45h 46h 48h 68h 69h 4Ah 4Ch 6E...

Page 17: ...ust be sent 49d 50d 08d 51d 52d 09d 53d 54d end of block In hexa code the following must be sent 31h 32h 08h 33h 34h 09h 35h 36h end of block Example Protocols Modbus TCP On a 6 digit display to display 123456 with digits 3 and 4 flashing In decimal code the following must be sent 49d 50d 08d 51d 52d 09d 53d 54d In hexa code the following must be sent 31h 32h 08h 33h 34h 09h 35h 36h ...

Page 18: ...om the factory with the same IP address Therefore to configure various units they must be connected to the Ethernet and the address must be assigned one by one To modify the port configuration the DeviceInstaller program from Lantronix must be used which can be downloaded free from their website www lantronix com Select Support Resources Get Support Firmware Select DeviceInstaller Once the program...

Page 19: ...n Connect Protocol Select Datagram Type 1 in Datagram Mode In Endpoint Configuration set Local Port 10001 Remote Host IP address of the computer to which it is connected Remote Port Port of the computer to which it is connected Click OK on the bottom of the page Click Apply Settings on the menu 4 5 1 Configure to use the UDP IP protocol ...

Page 20: ...igit allow setting up a negative value Parameter b Left Digit Control bit Right Digit Set Reset 0 ON if Value Parameter C 0 No delay No hysteresis 1 ON if Value Parameter C 1 Delay 1s 2 Always OFF 2 Delay 2s 3 Delay 4s 4 Delay 6s 5 Delay 10s 6 Hysteresis 2 7 Hysteresis 4 8 Hysteresis 8 9 Hysteresis 12 To set up the internal bit r2 parameters d and E are used Parameter d is used to set up the activ...

Page 21: ...ternal bit r2 is ON To change the colour press key Upon pressing the next parameter is shown Colour if internal bits r1 and r2 are ON To change the colour press key Upon pressing the next parameter is shown To work always with only one colour set up the following parameters Parameter Value b 20 C 0 d 20 E 0 nr colour r1 colour r2 colour r3 colour Parameters C and E may have any value Parameters nr...

Page 22: ...ph 4 5 1 Added paragraph 4 6 Revision F September 2013 Updated dimensions and weight of DN 109 3 Paragraphs 2 2 1 and 2 3 1 Revision G October 2013 Updated electrical characteristics of the 24VDC power Paragraphs 2 1 and 3 1 Updated section 4 2 3 2 Revision history ...

Page 23: ...declare under our sole responsibility that the aforementioned product complies with the following European directives Directive LVD 2006 95 CEE Low Voltage Directive Standard UNE EN61010 1 Security in electric equipment Directive EMC 2014 30 UE Electromagnetic Compatibility Standard UNE EN 61000 6 4 Generic Emission Standard Industrial environment Standard UNE EN 61000 6 2 Generic Immunity Standar...