background image

7

Use only original replacement parts for any repair or compo-
nent replacement. Consult the list of replacement parts that 
corresponds to the specification of the original equipment.
Do not drain water circuits containing industrial brines, 
without informing the technical service department at the 
installation site or a competent body first.

Close the entering and leaving water shutoff valves and 
purge the unit water circuit, before working on the compo-
nents installed on the circuit (screen filter, pump, water 
flow switch, etc.).

Periodically inspect all valves, fittings and pipes of the 
refrigerant and hydronic circuits to ensure that they do 
not show any corrosion or any signs of leaks.

It is recommended to wear ear defenders, when working 
near the unit and the unit is in operation.

2 - PRElIMINARy CHECkS

2.1 - Check equipment received

• 

Inspect the unit for damage or missing parts. If damage 
is detected, or if shipment is incomplete, immediately 
file a claim with the shipping company.

• 

Compare the name plate data with the order. The name 
plate is attached in two places to the unit:

 

-  on one of the unit sides on the outside,

 

-  on the control box door on the inside.

• 

The unit name plate must include the following 
information:

 

Version number

 

Model number

 

CE marking

 

Serial number 

 

Year of manufacture and test date

 

Refrigerant used and refrigerant class

 

Refrigerant charge per circuit

 

Containment fluid to be used

 

PS: Min./max. allowable pressure (high and low 
pressure side)

 

TS: Min./max. allowable temperature (high and 
low pressure side)

 

Pressure switch cut-out pressure

 

Unit leak test pressure

 

Voltage, frequency, number of phases

 

Maximum current drawn

 

Maximum power input

 

Unit net weight

• 

Confirm that all accessories ordered for on-site installa-
tion have been supplied, are complete and undamaged.

• 

Do not keep the 30RW/30RWA units outside where they 
are exposed to the weather, as the sensitive control 
mechanism and the electronic modules may be damaged.

The unit must be checked periodically during its whole 
operating life to ensure that no shocks (handling accessories, 
tools etc.) have damaged it. If necessary, the damaged parts 
must be repaired or replaced. See chapter “Maintenance”.

The machine must be installed in a place that is not 
accessible to the public or protected against access by 
non-authorised persons.

2.2 - Moving and siting the unit

2.2.1 - moving
See chapter 1.1 - “Installation safety considerations”.

2.2.2 - siting the unit

Always refer to the chapter “Dimensions and clearances” 
to confirm that there is adequate space for all connections 
and service operations. For the centre of gravity coordinates, 
the position of the unit mounting holes, and the weight 
distribution points, refer to the certified dimensional 
drawing supplied with the unit.

Typical applications of these units are in refrigeration 
systems, and they do not require earthquake resistance. 
Earthquake resistance has not been verified.

In case of extra-high units the machine environment must 
permit easy access for maintenance operations.

CAUTION: Only use slings at the designated lifting 
points which are marked on the unit.

Before siting the unit check that:
• 

the permitted loading at the site is adequate or that 
appropriate strenghtening measures have been taken.

• 

the unit is installed level on an even surface (maximum 
tolerance is 1.5 mm in both axes).

• 

there is adequate space above the unit for air flow and 
to ensure access to the components.

• 

the number of support points is adequate and that 
they are in the right places.

• 

the location is not subject to flooding. 

CAUTION: Before lifting the unit, check that all casing 
panels are securely fixed in place. Lift and set down the 
unit  with great care. Tilting and jarring can damage the 
unit and impair unit operation.

If 30RW/RWA units are hoisted with rigging, it is neces-
sary to protect the unit frame (side and rear panels and 
front doors) against accidental crushing while a unit is 
being moved. Use struts or lifting beams to spread the 
slings above the unit. Do not tilt a unit more than 15°. 
Always follow the instructions on the handling notice 
attached to the unit.

If a unit includes a hydronic module (options 116B, 116C, 
270B, 270C), the hydronic module and pump piping must 
be installed in a way that does not submit it to any strain. 
The hydronic module pipes must be fitted so that the pump 
does not support the weight of the pipes.

Never push or lever on any of the enclosure panels (panels, 
uprights, front access doors) of the unit. Only the base of 
the unit frame is designed to withstand such stresses.

Checks before system start-up
Before the start-up of the refrigeration system, the complete 
installation, including the refrigeration system must be 
verified against the installation drawings, dimensional 
drawings, system piping and instrumentation diagrams and 
the wiring diagrams.

Содержание Aquasnap 30RW

Страница 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Страница 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Страница 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Страница 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Страница 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Страница 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Страница 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Страница 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Страница 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Страница 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Страница 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Страница 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Страница 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Страница 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Страница 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Страница 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Страница 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Страница 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Страница 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Страница 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Страница 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Страница 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Страница 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Страница 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Страница 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Страница 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Страница 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Страница 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Страница 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Страница 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Страница 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Страница 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Страница 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Страница 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Страница 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Страница 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Страница 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Страница 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Страница 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Страница 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Страница 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Страница 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Страница 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Страница 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Отзывы: