11.5 - 30RW units without evaporator and condenser 

pump, three-way valve configuration for low outside 

temperature application

30RW units can be supplied from the factory without evapo-
rator and condenser pump. If year-round low-temperature 
operation is planned, the chiller will be installed with a 
three-way valve that is not supplied with the chiller.

In this case Pro-Dialog Plus should be configured for 
three-way valve system control from an analogue 0-10 volt 
output on the NRCP type master board. An adequate 
condensing temperature will be maintained with constant 
condenser flow rate. This configuration permits year-round 
system operation down to -20°C outside temperature.

Control and changeover of the fan stages are described in 
the paragraph “Configuration of the number of fan stages 
and  automatic changeover of the fan stages” is identical in 
this case.

11.6 - Drycooler installation

For the drycooler installation follow professional guidelines.
• 

Water pipe sizing

• 

Maximum piping and shut-off valve pressure drops 
based on the available pressure of the 30RW pumps

• 

Maximum drycooler elevation in relation to the chiller 
(safety valve at 4 bar on the 30RW water circuit).

• 

Fan stage control (see “Fan stage control”).

• 

Good positioning of the outside air temperature and 
drycooler leaving water temperature sensors.

12 - 30RWA UNIT OPERATION WITH REMOTE AIR-

COOlED CONDENSER

12.1 - Operating principle

30RWA units are specially designed to optimise the opera-
tion of split installations using air-cooled condensers as the 
chiller heat rejection system. The installation of an operational 
system is limited to the connection of the air-cooled 
condenser entering and leaving piping to the 30RWA unit.

The Pro-Dialog Plus control system of the 30RWA units 
incorporates the logic to permit control of the different fan 
versions (single-circuit, dual-circuit, fixed and variable-
speed fan, separate ventilation or interlaced ventilation at 
the circuit level). 

12.2 - Master fan

The physical position of the air-cooled single- or dual-circuit 
air-cooled condenser with fixed or variable-speed fans 
depends on the position of the leaving liquid refrigerant 
manifold. In all cases there is always a so-called master fan. 
This is the fixed or variable-speed fan that is physically the 
closest to the leaving liquid refrigerant manifold.

This ensures optimum subcooling on the leaving condenser 
side, especially at part load. This is the first fan to start in 
each circuit and the last fan to stop. A fan configuration 
with fixed-speed fans permits year-round system operation 
down to 0°C outside temperature.

A fan configuration with a variable-speed master fan permits 
year-round operation down to -10°C outside temperature.

12.3 - Dual-circuit condenser with separate ventilation 

and interlaced ventilation

For dual-circuit air-cooled condensers the most frequent and 
recommended configuration is with an air-cooled conden-
ser with completely independant circuits at fan level. This 
configuration is called “separate ventilation” by circuit.

It is also possible to control ventilation of a dual-circuit 
air-cooled condenser where the fans are not independant 
by circuit. This is called “interlaced ventilation”.

The Pro-Dialog Plus service configuration of the fans 
per-mits setting up these two dual-circuit air-cooled 
condenser types.

12.4 - Auxiliary electronic analogue input and output 

and discrete output board (AUX1) for control of the 

air-cooled remote condenser

This is the same board as the one used in the drycoolers (see 
paragraph “Auxiliary electronic analogue input and output 
and discrete output board for control of the drycooler”).

Refer to the assignment od the discrete output of the board 
based on the air-cooled condenser type installed (single-
circuit, dual-circuit with separate ventilation, dual-circuit 
with interlaced ventilation).

See paragraph “Possible fan arrangements based on the 
air-cooled condenser type used in the installation”.

0-10 V dc analogue outputs connectors J4 and J5:
Used for master fan speed variation of circuits A and B of 
the air-cooled condensers for operation at low outside 
temperature.
• 

Connector J6: Analogue inputs CH 11 for outside 
temperature sensors

• 

Connector J9: Communication with the master basic 
board of the 30RW unit.

12.5 - Configuration of the number of fan stages and 

fan type based on the air-cooled condenser model 

used in the installation

Please refer to the instructions in the Pro-Dialog Plus IOM 
for the 30RW/30RWA units to carry out the parameter 
setting of the air-cooled condenser used in the installation:
• 

Single-circuit or dual-circuit condenser

• 

Use of speed variation on the master fan(s)

• 

Dual-circuit condenser with separate or interlaced 
ventilation

• 

Number of fixed-speed fans

Based on the parameter setting used, the arrangement of the 
discrete and corresponding analogue outputs controlling 
the fans will be activated by the control.

The minimum configuration of the number of fan stages is 
2 for correct operation (2 fixed-speed or 1 variable-speed + 
1 fixed-speed fan).

Содержание Aquasnap 30RW

Страница 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Страница 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Страница 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Страница 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Страница 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Страница 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Страница 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Страница 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Страница 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Страница 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Страница 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Страница 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Страница 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Страница 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Страница 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Страница 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Страница 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Страница 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Страница 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Страница 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Страница 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Страница 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Страница 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Страница 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Страница 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Страница 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Страница 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Страница 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Страница 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Страница 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Страница 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Страница 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Страница 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Страница 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Страница 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Страница 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Страница 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Страница 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Страница 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Страница 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Страница 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Страница 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Страница 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Страница 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Отзывы: