background image

20

6.2 - Power supply

The power supply must conform to the specification on the 
chiller nameplate. The supply voltage must be within the 
range specified in the electrical data table. For connections 
refer to the wiring diagrams.

WARNINg: Operation of the chiller with an improper 
supply voltage or excessive phase imbalance constitutes 
abuse which will invalidate the Carrier warranty. If the 
phase imbalance exceeds 2% for voltage, or 10% for 
current, contact your local electricity supply at once and 
ensure that the chiller is not switched on until corrective 
measures have been taken.

6.3 - Voltage phase imbalance (%)

100 x max. deviation from average voltage 

Average voltage

example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase 
voltages were measured to be:

AB = 406 V ; BC = 399; AC = 394 V

Average voltage = (406 + 399 + 394)/3 = 1199/3
 

 

= 399.7 say 400 V

Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6

The maximum deviation from the average is 6 V. The 
greatest percentage deviation is: 100 x 6/400 = 1.5 %

This is less than the permissible 2% and is therefore 
acceptable.

6.4 - Recommended wire sections

Wire sizing is the responsibility of the installer, and depends 
on the characteristics and regulations applicable to each 
installation site. The following is only to be used as a guide-
line, and does not make Carrier in any way liable. After wire 
sizing has been completed, using the certified dimensional 
drawing, the installer must ensure easy connection and 
define any modifications necessary on site.

The connections provided as standard for the field-supplied 
power entry cables to the general disconnect/isolator switch 
are designed for the number and type of wires, listed in the 
table below.

The calculations are based on the maximum machine current 
(see electrical data tables). For the design the following 
standardised installation methods are used, in accordance  
with IEC 60364, table 52C:
• 

For units installed inside the building:

 

No.13: perforated horizontal cable conduit, and No. 
41: closed conduit.

The calculation is based on PVC or XLPE insulated cables 
with copper or aluminium core. A maximum ambient 
temperature of 40°C has been taken into account. The 
given wire length limits the voltage drop to <  5%.

IMPORTANT: Before connection of  the main power cables 
(L1 - L2 - L3) on the terminal block, it is imperative to 
check the correct order of the 3 phases before proceeding 
to the connection on then terminal block or the main 
disconnect/isolator switch.

6.4.1 - selection table of minimum and maximum wire sections for connection to 30Rw/Rwa units

400 V-3 ph-50 hz

30RW/30RWA

Minimum wire

section (mm

2

)

Wire type 

l (m)

Maximum wire

section (mm

2

)

Wire type

l (m)

020

1x 6

XLPE Cu

85

1x16

PVC Al

160

025

1x 6

XLPE Cu

80

1x16

PVC Al

155

030

1x 6

XLPE Cu

80

1x16

PVC Al

150

040

1x 6

XLPE Cu

75

1x16

PVC Al

145

045

1x 6

XLPE Cu

75

1x16

PVC Al

145

060

1x 10

XLPE Cu

90

1x25

PVC Al

165

070

1x 10

XLPE Cu

90

1x35

PVC Al

185

080

1x 16

XLPE Cu

110

1x35

PVC Al

185

090

1x 16

XLPE Cu

108

1x50

PVC Al

215

110

1x 25

XLPE Cu

135

1x70

PVC Al

230

120

1x 25

XLPE Cu

130

1x70

PVC Al

230

135

1x 35

XLPE Cu

145

1x95

PVC Al

250

150

1x 35

XLPE Cu

145

1x95

PVC Al

250

160

1x 35

XLPE Cu

142

1x120

PVC Al

260

185

1x 50

XLPE Cu

162

1x120

XLPE Al

205

210

1x 70

XLPE Cu

175

1x120

XLPE Al

205

245

1x 70

XLPE Cu

170

1x150

XLPE Al

210

275

1x 70

XLPE Cu

168

1x150

XLPE Al

210

300

1x 95

XLPE Cu

180

1x185

XLPE Al

220

S  Power supply wire section (see diagram in chapter ‘Electrical connection’).

Motor

Содержание Aquasnap 30RW

Страница 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Страница 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Страница 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Страница 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Страница 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Страница 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Страница 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Страница 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Страница 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Страница 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Страница 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Страница 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Страница 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Страница 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Страница 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Страница 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Страница 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Страница 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Страница 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Страница 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Страница 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Страница 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Страница 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Страница 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Страница 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Страница 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Страница 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Страница 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Страница 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Страница 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Страница 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Страница 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Страница 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Страница 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Страница 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Страница 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Страница 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Страница 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Страница 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Страница 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Страница 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Страница 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Страница 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Страница 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Отзывы: