Table 31 — 2-Step Demand Limit Configuration
NOTE:
Bold
values indicate sub-mode level.
MODE
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
DISP
UNIT
SERV
OPTN
RSET
Reset Cool and Heat Tmp
CRST
HRST
DMDC
Demand Limit Select
0
None
0
None
Flashing to indicate Edit mode. May require Password
/
1
Switch
Use up or down arrows to change value to 1.
1
Accepts the change.
DMDC
At mode level
SETPOINTS
/
Change to Setpoints Mode
COOL
Cooling Setpoints
HEAT
MISC
Miscellaneous Setpoints
DLS1
Switch Limit Setpoint 1
0
None
Current value for DLS1.
0
None
Flashing to indicate Edit mode. May require Password
60
Switch
Use arrows to change value to 60 from the example.
60
Accepts the change.
DLS1
DLS2
Switch Limit Setpoint 2
0
Current value of DLS2
0
Flashing to indicate Edit mode
40
Use arrows to change the value for DLS2 to 40 from the
example.
40
Accepts the change.
DLS2
x 2
DGRC
SETPOINTS
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ESCAPE