Table 13 — Configuring the Master Chiller
NOTE:
Bold
values indicate sub-mode level.
MODE
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
DISP
UNIT
SERV
OPTN
CCNA
CCN Address
Confirm address of chiller. The master and slave chiller
must have different addresses.
1
Factory default address is 1.
CCNA
CCNB
CCN Bus Number
Confirm the bus number of the chiller. The master and slave
chiller must be on the same bus.
0
Factory default is 0.
CCNB
OPTN
RSET
Reset Cool and Heat Tmp
CRST
Cooling Reset Type
x 5
MSSL
Master/Slave Select
0
Disable
0
Disable
Flashing to indicate Edit mode. May require Password.
1
Master
Use up arrows to change value to 1.
1
Accepts the change.
MSSL
SLVA
Slave Address
1
1
Flashing to indicate Edit mode.
2
Use up arrows to change value to 2. This address must
match the address of the slave chiller.
2
Accepts the change.
SLVA
LLBL
Lead/Lag Balance Select
ENBL
Factory Default is ENBL
LLBL
LLBD
Lead/Lag Balance Delta
168
Factory Default is 168.
LLBD
LLDY
Lead/Lag Start Delay
10
Factory Default is 10.
LLDY
LAGP
Lag Unit Pump Select
0
Off if U Stp
Factory Default is 0, Off if unit is stopped. Master and slave
chiller must be configured to the same value.
LAGP
LPUL
Lead Pulldown Time
0
Factory Default is 0.
At mode level.
OPERATING
MODES
OPER
Operating Control Type
0
Switch Control
Master chiller should be configured for job requirements,
Switch Control, Time Schedule, or CCN.
At mode level.
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ESCAPE
Содержание AQUASNAP 30RBA315
Страница 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Страница 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Страница 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Страница 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Страница 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...