28
Carrier Yileng - Shanghai, China
6
– APPLICATION DATA
6.1
– Cooling operating range
6.2
– Heating operating range
Operating Range
Cooling mode
Evaporator
Min.temperature
Max.temperature
Entering water temperature (at start)
℃
-
45
Entering water temperature (during operation)
℃
6.8
21
Entering water temperature (during stop)
℃
3
55
Leaving water temperature (during operation)
℃
4
15
Condenser
Min.temperature
Max.temperature
Outdoor air temperature
-10
46
* A glycol/water solution must be used if the air temperature is below 0°C,
** Max 50°C during part load operation;
Lengend
Part load
Operating range, standard unit.
Below 0°C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must be
protected against frost by using a frost protection solution by the installer
Содержание AquaForce 30XQ0330