PERFORMANCE DATA—50TFQ (CONT)
INSTANTANEOUS AND INTEGRATED HEATING RATINGS (CONT)
50TFQ007
Return
Air
Cfm
(Standard
Air Temperature Entering Outdoor Coil (F)
Air
(F db)
(Standard
Air)
0
10
17
30
40
47
50
60
1800
Cap.
37.8
32.2
43.9
40.3
48.3
44.1
58.0
50.8
66.2
66.2
72.3
72.3
75.2
75.2
86.0
86.0
1800
kW
4.72
4.97
5.16
5.58
5.96
6.25
6.40
6.95
55
2400
Cap.
37.9
32.2
44.0
40.4
48.5
44.2
58.4
51.2
66.6
66.6
72.8
72.8
75.9
75.9
87.0
87.0
55
2400
kW
4.55
4.76
4.92
5.28
5.57
5.81
5.93
6.38
3000
Cap.
38.0
32.3
44.0
40.4
48.5
44.3
58.5
51.3
66.9
66.9
73.1
73.1
76.2
76.2
87.5
87.5
3000
kW
4.46
4.64
4.78
5.09
5.35
5.56
5.67
6.07
1800
Cap.
37.3
31.7
43.6
40.0
48.1
43.9
57.5
50.4
65.2
65.2
71.1
71.1
74.0
74.0
84.6
84.6
1800
kW
5.32
5.61
5.84
6.33
6.75
7.10
7.27
7.91
70
2400
Cap.
37.5
31.9
43.8
40.2
48.2
43.9
57.7
50.5
65.6
65.6
71.8
71.8
74.7
74.7
85.4
85.4
70
2400
kW
5.13
5.38
5.57
5.97
6.32
6.61
6.74
7.25
3000
Cap.
37.6
32.0
43.9
40.3
48.3
44.0
57.8
50.7
66.0
66.0
72.1
72.1
75.0
75.0
86.0
86.0
3000
kW
5.03
5.25
5.41
5.76
6.08
6.32
6.44
6.89
1800
Cap.
36.8
31.3
43.1
39.6
47.9
43.7
57.1
50.1
64.8
64.8
70.5
70.5
73.4
73.4
83.6
83.6
1800
kW
5.75
6.09
6.34
6.88
7.35
7.72
7.90
8.58
80
2400
Cap.
37.0
31.4
43.4
39.8
48.0
43.8
57.4
50.3
65.1
65.1
71.1
71.1
73.9
73.9
84.5
84.5
80
2400
kW
5.55
5.83
6.04
6.49
6.87
7.18
7.33
7.89
3000
Cap.
37.1
31.5
43.5
39.9
48.1
43.9
57.5
50.4
65.3
65.3
71.5
71.5
74.4
74.4
85.0
85.0
3000
kW
5.44
5.68
5.87
6.26
6.60
6.88
7.01
7.49
50TFQ008
Return
Air
Cfm
(Standard
Air Temperature Entering Outdoor Coil (F)
Air
(F db)
(Standard
Air)
0
10
17
30
40
47
50
60
2000
Cap.
36.6
31.2
44.0
40.4
49.8
45.4
61.4
53.8
70.4
70.4
77.4
77.4
80.6
80.6
91.8
91.8
2000
kW
5.24
5.64
5.94
6.58
7.08
7.50
7.68
8.32
55
2600
Cap.
37.6
32.0
45.2
41.4
51.2
46.6
63.0
55.2
72.4
72.4
79.6
79.6
83.0
83.0
92.4
92.4
55
2600
kW
5.18
5.56
5.82
6.40
6.84
7.20
7.36
7.78
3200
Cap.
38.2
32.4
45.8
42.0
51.8
47.2
63.8
55.8
73.6
73.6
81.0
81.0
83.8
83.8
91.2
91.2
3200
kW
5.16
5.50
5.74
6.28
6.70
7.02
7.12
7.40
2000
Cap.
32.4
27.6
40.4
37.2
46.0
41.8
57.8
50.6
66.8
66.8
73.6
73.6
76.6
76.6
87.8
87.8
2000
kW
5.42
5.90
6.22
6.92
7.48
7.94
8.16
8.90
70
2600
Cap.
33.4
28.4
41.8
38.2
47.4
43.2
59.6
52.2
68.8
68.8
75.8
75.8
79.0
79.0
90.4
90.4
70
2600
kW
5.38
5.82
6.12
6.76
7.28
7.68
7.86
8.48
3200
Cap.
34.2
29.0
42.2
38.6
48.4
44.0
60.6
53.0
70.0
70.0
77.2
77.2
80.6
80.6
91.0
91.0
3200
kW
5.36
5.76
6.06
6.66
7.14
7.50
7.68
8.16
2000
Cap.
29.2
24.8
37.4
34.4
43.4
39.6
54.8
48.0
64.0
64.0
70.8
70.8
73.8
73.8
84.8
84.8
2000
kW
5.52
6.02
6.40
7.12
7.72
8.22
8.44
9.24
80
2600
Cap.
30.2
25.8
38.8
35.6
44.6
40.6
56.8
49.8
66.2
66.2
73.2
73.2
76.4
76.4
87.8
87.8
80
2600
kW
5.48
5.96
6.30
6.98
7.54
7.98
8.18
8.88
3200
Cap.
31.0
26.4
39.6
36.4
45.4
41.4
58.0
50.8
67.4
67.4
74.6
74.6
78.0
78.0
89.0
89.0
3200
kW
5.46
5.92
6.24
6.90
7.42
7.82
8.00
8.58
LEGEND
Cap.
--- Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
db
--- dry bulb
kW --- Total Power Input (includes compressor motor power input,
outdoor---fan motor input, and indoor---fan motor input)
NOTES
:
1.
indicates integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.
50TFQ
Содержание APOLLO CONTROL 50HJQ004-016
Страница 5: ...5 50HEQ003 006 ...
Страница 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Страница 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Страница 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Страница 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Страница 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Страница 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...