z. Return Air CO
2
Sensor (EconoMi$er IV):
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV. The IAQ
sensor shall be duct mounted. The set point shall have
adjustment capability.
aa. Ultra-Violet Germicidal Lamps:
Ultra-violet germicidal lamps are designed to eliminate
odor-causing mold and fungus that may develop in the
wet area of the indoor section of the unit. The high output,
low temperature germicidal lamps are field installed in
the indoor section of the unit, aimed at the indoor coil and
condensate pan. The short wave-length ultra-violet light
inhibits and kills mold, fungus and microbial growth. The
lamps have an output rating at 45 F in 400 fpm airflow
of 120 microwatts/cm
2
at 1 meter.
ab. Hinged Panel Option:
Hinged panel option provide hinged access panels for the
filter, compressor, evaporator fan, and control box areas.
Filter hinged panels permit tool-less entry for changing
filters. Each hinged panel is permanently attached to the
rooftop unit.
ac. Emergency Heat Control Package:
When mechanical heating is locked out, auxiliary heat
shall be activated when necessary.
50H
EQ
Содержание APOLLO CONTROL 50HJQ004-016
Страница 5: ...5 50HEQ003 006 ...
Страница 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Страница 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Страница 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Страница 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Страница 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Страница 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...