120
ELECTRIC HEATING CAPACITIES — 50HJQ004-014 (CONT)
UNIT
50HJQ
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00 or --B00
ACCESSORY SINGLE
POINT BOX PART NO.
CRSINGLE---A00
7.8/ 9.6/10.4
117
007
208/230/240
12.0/14.7/16.0
110
007
208/230/240
(3 phase)
18.6/22.8/24.8
111
009
(3 phase)
24.0/29.4/32.0
112
009
008
31.8/39.0/42.4*
112,117
013
008
(7
1
/
2
Tons)
12.8/13.9
116
006
(7 /
2
Tons)
460/480
15.2/16.5
113
006
460/480
(3 phase)
25.6/27.8
114
008
(3 phase)
30.4/33.0
115
008
38.4/41.7*
114,116
—
7.8/ 9.6/10.4
117
012
208/230/240
12.0/14.7/16.0
110
012
208/230/240
(3 phase)
18.6/22.8/24.8
111
015
(3 phase)
24.0/29.4/32.0
112
015
009
31.8/39.0/42.4*
112,117
017
009
(8
1
/
2
Tons)
12.8/13.9
116
011
(8 /
2
Tons)
460/480
15.2/16.5
113
011
460/480
(3 phase)
25.6/27.8
114
014
(3 phase)
30.4/33.0
115
014
38.4/41.7*
114,116
016
7.8/ 9.6/10.4
117
012
208/230/240
12.0/14.7/16.0
110
012
208/230/240
(3 phase)
24.0/29.4/32.0
112
015
(3 phase)
31.8/39.0/42.4*
112,117
017
012
37.6/46.2/50.0*
112,110
017
012
(10 Tons)
15.2/16.5
113
011
(10 Tons)
460/480
25.6/27.8
114
014
460/480
(3 phase)
30.4/33.0
115
014
(3 phase)
38.4/41.7*
114,116
016
46.0/50.0*
115,113
016
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW
new = Heater kW rated x (unit power distribution voltage/rated heater voltage)2
3. Single point boxes contain a junction box, wiring and sub---fusing assembly as necessary to meet National Electric Cod and UL requirements. Single
point boxes CRSINGLE001A00, 006A00 and 011A00 are junction boxes only.
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW
new = 16 kW (215/240)2
kW
new = 12.8 kW (rating at 215 v)
ELECTRIC HEATING CAPACITIES — 50HJQ014,016
HEATER kW
HEATER
% HEAT
MAXIMUM
HEATER kW
HEATER
% HEAT
MAXIMUM
UNIT 50HJQ
Unit Voltages
HEATER
% HEAT
MAXIMUM
UNIT 50HJQ
Unit Voltages
STAGES
PER STAGE
STAGES*
UNIT 50HJQ
208
230
460
575
STAGES
PER STAGE
STAGES*
14
19
15
—
1
100
1
014
26
34
32
—
2
50/50
2
014
42
56
55
37
2
33/67
3
26
34
32
—
2
50/50
2
016
42
56
55
—
2
33/67
3
016
—
—
—
50
2
50/50
4
*Maximum number of stages using accessory outdoor-air thermostats.
NOTE: Heaters are rated at 208 v, 240 v, 480 v, and 600 v. See multiplication factors table.
50H
JQ
Содержание APOLLO CONTROL 50HJQ004-016
Страница 5: ...5 50HEQ003 006 ...
Страница 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...
Страница 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...
Страница 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...
Страница 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...
Страница 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...
Страница 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...