45
A13228
• System in Control: The system will decide which stage should be
running to satisfy the heating demand.
• High Heat: Temperature below which only the high stage of heating
will be energized.
• Only Low Heat: The system will only run in low stage heating.
6.3.4.2. Cooling Lockout
Outside temperature below which cooling will not be provided. After the
selection is made, touch
SAVE
.
•
Cooling Lockout Temp
: None, 45, 50 or 55 (°F). Default = None
NOTE:
When simultaneous heating and cooling demand feature is on,
the cooling lockout shall be ignored.
6.3.4.3. Defrost Interval
Time interval at which defrost cycles can occur on a heat pump.
AUTO
means the defrost interval is optimized by the outdoor control. After the
selection is made, touch
SAVE
.
•
Set Defrost Interval
: 30, 60, 90, 120 minutes or AUTO. Default =
AUTO
NOTE:
See Heat Pump Installation Instructions for Defrost Timing
Interval when using
AUTO
Defrost.