![Carrier 69NT40-561-019 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/carrier/69nt40-561-019/69nt40-561-019_operation-and-service-manual_2563845059.webp)
4–33
T-359
AL17
Compressor
Pressure
Delta Fault
Compressor has at-
tempted to start in both
directions and fails to
generate sufficient
pressure differential
between SPT and
DPT.
N/A
Controller will attempt re-
start every 20 minutes
and deactivate the alarm
if successful.
Resume normal
operation.
Discharge Pres-
sure Transducer
(DPT)
Confirm accurate DPT
pressure readings, refer
to MANIFOLD GAUGE
SET
Replace DPT if
defective.
Suction Pressure
Transducer (SPT)
Confirm accurate SPT
pressure readings, refer
to MANIFOLD GAUGE
SET
.
Replace SPT if
defective.
Monitor unit
Alarm is display only the
alarm may clear itself
during operation.
If alarm remains active or
is repetitive replace com-
pressor at next available
opportunity.
AL18
Discharge
Pressure
High
Discharge pressure is
over the maximum for
10 minutes within the
last hour.
Restrictions in the
refrigeration
system.
Ensure Liquid Line Ser-
vice Valve is fully open.
Open Liquid Line Service
Valve as needed.
Filter Drier
Check the filter drier, if it
is iced up or very cold it
indicates that the filter
drier needs replacement.
Replace the filter drier if
needed, refer to FILTER
DRIER Service
.
Condenser Fan
Check Condenser Fan
for proper operation.
Correct as required.
Discharge
Pressure
Transducer (DPT)
Confirm accurate DPT
pressure readings, refer
to MANIFOLD GAUGE
SET
.
Replace DPT
if defective.
Non-condens-
ables in the
refrigeration
system.
With the unit off allow
system to stabilize to am-
bient temperature. Check
system pressure against
PT Chart for 134a, refer
to
Correct as required, refer
to Refrigerant Charge
.
Refrigerant
Check refrigerant level.
Correct as required, refer
to Refrigerant Charge
.
Table 4–6 Controller Alarm Indications
CODE #
CAUSE
COMPONENTS
TROUBLESHOOTING
CORRECTIVE ACTIONS
Содержание 69NT40-561-019
Страница 2: ......
Страница 4: ......
Страница 74: ......
Страница 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Страница 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Страница 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Страница 130: ......
Страница 134: ......
Страница 135: ......