T-359
4–28
Cd37
Defrost
Termination
Temperature
Setting
(Bulb Mode)
This code, as with function code Cd36, is used in conjunction with bulb mode and de-
humidification. If bulb mode is active, this code allows the user to change the tem-
perature above which defrost will terminate. It allows the user to change the setting
within a range of 4
C to 25.6
C in 0.1
C (0.2
F) increments. This value is changed
using the UP/DOWN ARROW keys, followed by the ENTER key when the desired
value is displayed. If bulb mode is deactivated, the DTS setting re turns to the default.
Cd38
Secondary Supply
Temperature
Sensor
Code Cd38 will display the current supply recorder sensor (SRS) reading for units
configured for four probes. If the unit is configured with a DataCORDER, Cd38 will
display “-----.” If the DataCORDER suffers a failure, (AL55) Cd38 will display the sup-
ply recorder sensor reading.
Cd39
Secondary Return
Temperature
Sensor
Code Cd39 will display the current return recorder sensor (RRS) reading for units
configured for four probes. If the unit is configured with a DataCORDER, Cd39 will
display “-----.” If the DataCORDER suffers a failure, (AL55) Cd39 will display the re-
turn recorder sensor reading.
Cd40
Container
Identification
Number
Code Cd40 is configured at commissioning to read a valid container identification
number. The reading will not display alpha characters; only the numeric portion of the
number will display.
Cd41
Valve Override
SERVICE FUNCTION:
This code is used for troubleshooting, and allows manual po-
sitioning of the economizer solenoid valve, electronic expansion valve, and digital un-
loader valve. Provides readings such as: Percent Capacity, EEV, Capacity Mode,
LIV, and DUV.
Refer to
Cd43
eAutoFresh Mode
Code Cd43 is used to select the mode of operation for the eAutoFresh slides. Asso-
ciated parameters can also be selected from submenus: OFF, USER, DELAY, TEST
and gASLM. If the unit is not configured for eAutoFresh, Cd43 will
display “-----.”
Cd44
eAutoFresh
Values
Code Cd44 displays the eAutoFresh CO
2
and O
2
values (CO2
and O2) and CO
2
and
O
2
limits (CO2LIM
and O2LIM), respectively.
If the unit is not configured for eAutoF-
resh, Cd44 will display “-----.”
Cd45
Fresh Air Vent
Position Sensor
Unless AL50 is active or CnF47 is OFF, the fresh air flow (CMH/CFM) is displayed.
This function code will automatically activate for 30 seconds and display when a vent
position change occurs.
Cd46
Airflow Display
Units
This code displays the airflow units to be displayed for Cd 45. Options are CF, CM,
or bOth (dependent on the setting of Cd28 or pressing of the C/F key).
Cd47
Variable Economy
Temperature
Setting
Code Cd47 is used with optional economy mode. Values are 0.5
C-4.0
C, default is
3.0°C. If unit is not configured for economy mode, “----” will be displayed.
Cd48
Dehumidification
Parameter
Selection
Code Cd48 is used both when dehumidification set point is set above 65% RH and
below 64% RH. When dehumidification set point is set above 65% RH, select goes
to LO if it had been set to hi. When dehumidification set point is set below 64% RH,
select goes to Alt if it had been set to LO.
Cd49
Days Since Last
Successful Pre-
trip
Code Cd49 will display the time period (days) since the last successful pre-trip com-
pletion. Press ENTER repeatedly to display last pre-trip completion in Auto, Auto 1,
and Auto 2 modes.
Table 4–5 Controller Function Codes (Continued)
CODE #
TITLE
DESCRIPTION
Содержание 69NT40-561-019
Страница 2: ......
Страница 4: ......
Страница 74: ......
Страница 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Страница 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Страница 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Страница 130: ......
Страница 134: ......
Страница 135: ......