4–21
T-354
Cd28
Temperature Units
(Degrees C or
Degrees F)
This code determines the temperature units (
C or
F) which will be used for all
temperature displays. The user selects
C or
F by selecting function code
Cd28 and pushing the ENTER key. The factory default value is Celsius units.
NOTE
This code will display "
-----"
if Configuration Variable CnF34 is set to
F.
Cd29 Failure Action (Mode)
If all of the control sensors are out of range (alarm code AL26) or there is a
probe circuit calibration failure (alarm code AL27), the unit will enter the shut-
down state defined by this setting. The user selects one of four possible actions
as follows:
A - Full Cooling (stepper motor SMV at maximum allowed opening)
B - Partial Cooling (stepper motor SMV 11% open)
C - Evaporator Fan Only
D - Full System Shutdown - Factory Default
Cd30 In-Range Tolerance
The in-range tolerance will determine the band of temperatures around the set
point which will be designated as in-range. If the control temperature is in-
range, the in-range light will be illuminated. There are four possible values:
1 = +/- 0.5
C (+/-0.9
F)
2 = +/- 1.0
C (+/-1.8
F)
3 = +/- 1.5
C (+/-2.7
F)
4 = +/- 2.0
C (+/-3.6
F) - Factory Default
Cd31
Stagger Start Offset
Time (Seconds)
The stagger start offset time is the amount of time that the unit will delay at start-
up, thus allowing multiple units to stagger their control initiation when all units
are powered up together. The eight possible offset values are:
0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds
Cd32 Current Limit (Amperes)
The current limit is the maximum current draw allowed on any phase at any
time. Limiting the unit's current reduces the load on the main power supply. This
is ac complished by reducing the SMV position until current draw is reduced to
the set point. When desirable, the limit can be lowered. Note, however, that ca-
pacity is also reduced. The five values for 460VAC operation are:
15, 17, 19, 21 (Factory Default), 23
Cd33
Perishable Mode
Dehumidification
/Humidification
Control (% RH)
Relative humidity set point is available only on units configured for dehumidifi-
cation. When the mode is activated, the control probe LED flashes on and off
every second to alert the user.
If not configured, the mode is permanently deactivated and "
-----
" will dis play. The
value can be set to "OFF." "TEST," or a range of 65 to 95% relative humidity in
increments of 1%. [If bulb mode is active (code Cd35) and "Lo" speed evaporator
motors are selected (code Cd36) then set point ranges from 60 to 95%].
When "TEST" is selected or test set point is entered, the heat LED should illumi-
nate, indicating that dehumidification mode is activated. After a period of five min-
utes in the "TEST" mode has elapsed, the previously selected mode is reinstated.
NOTE
If humidification (CnF35) is enabled, then humidification will be enabled and
dehumidification locked out at set points of 75% and above. At set points be
low 75%, dehumidification will be enabled and humidification locked out.
Cd34
Economy Mode
(On-Off)
Economy mode is a user selectable mode of operation provided for power sav-
ing purposes.
Table 4–5 Controller Function Codes (Continued)
CODE
TITLE
DESCRIPTION
Содержание 69NT40-541-306
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 78: ...T 354 5 8 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode ...
Страница 142: ...T 354 8 2 Figure 8 2 Schematic Diagram Standard Unit Configuration BASED ON 62 66686 00 ...
Страница 143: ...8 3 T 354 Figure 8 3 Unit Wiring Diagram Standard Unit Configuration 1 of 2 BASED ON 62 66686 00 ...
Страница 144: ...T 354 8 4 Figure 8 4 Unit Wiring Diagram Standard Unit Configuration 2 of 2 BASED ON 62 66686 00 ...
Страница 148: ...T 354 8 8 ...
Страница 152: ......
Страница 153: ......