4-1
SECTION 4
SERVICE
This section covers service for the generator set and some engine servicing only. Refer to the Deutz engine workshop
manual for other engine servicing (refer to section 1.1.).
WARNING
Beware of moving V-Belts and belt driven components.
4.1 MAINTENANCE SCHEDULE
Unit
Reference
ON/OFF
Operation
Section
4.1.1 Daily Maintenance
X
1. Pre-Trip Inspection --- before starting
2.2.a
X
2. Pre-Trip Inspection --- after starting
2.2.b
X
3. Check total time meter
Run 10 min.
4.1.2 First 400 Hour Maintenance
X
1. Pre-Trip Inspection --- before starting
2.2.a
X
X
2. Change lube oil and filter
4.3.2
X
3. Pre-Trip Inspection --- after starting
2.2.b
X
4. Check total time meter
Run 10 min.
4.1.3 Every 1000 Hour Maintenance
(Normal Operating Conditions)
X
X
1. Complete 400 Hour Maintenance
4.1.2
X
2. Tighten engine and generator mounting bolts
4.7
X
3. Tighten all electrical connections in control box and unit
Tighten
X
4. Clean air cleaner filter, check hose and connections
4.3.5
X
5. Check V-belt tension
4.4.2
X
6. Check battery charging alternator amperage output
4.8
X
7. Clean mechanical fuel lift pump filter (If equipped)
Engine Manual
X
8. Change engine lube oil
1.4.j
X
9. Change primary and secondary fuel filters
None
4.1.4 Every 3000 to 6000 Hour Maintenance
X
X
1. Complete a 400 and 1000 Hour Maintenance
4.1.2 & 4.1.3
X
2. Clean crankcase breather
4.3.7
X
3. Check starter condition
Engine Manual
X
X
4. Check engine compression
Engine Manual
X
5. Check and adjust injector nozzles
Engine Manual
X
6. Replace V-Belts
4.4
X
7. Change Fill-Max oil filter (Optional Item)
None