(4.) AC/HP CFM ADJUST-Select NOM (Lo for 060).
(5.) ON/OFF DELAY-Select ENH profile.
(6.) CONTINUOUS FAN-Select desired fan speed when
thermostat is set to continuous fan.
(7.) DEHUMIDIFY MODE-Remove J1 jumper to activate.
(8.) LOW VOLTAGE CONNECTIONS-Make connec-
tions as shown in ELECTRICAL CONNECTIONS
section.
(9.) CONFIGURE THERMIDISTAT™ (or capable zoning
system)-Following its installation instructions for Su-
per Dehumidify and Super Comfort Heat operation.
This configuration provides the following comfort enhance-
ments:
(a.) A 30 sec blower on delay with 150 sec at 70
percent airflow to allow the indoor coil to warm
up or cool down before the blower is asked to
deliver 100 percent airflow reducing the cold blow
sensation at start up in heating and allowing the
indoor coil to more quickly reach wet coil oper-
ating conditions in cooling.
(b.) A no blower off delay eliminates cold blow which
may be associated with running the blower after
shut down of the compressor and avoids re-
evaporation
of
condensed
moisture
after
cooling/dehumidifying operation.
(c.) Lower airflow while the compressor is running to
reduce draft effects and increase heating air tem-
perature and improved humidity control during
cooling operation.
ACCESSORY INSTALLATION
a. ACCESSORY ELECTRIC HEATERS
Electric heaters may be installed with the 50XZ units per
instructions supplied with electric heater package. See unit
rating plate for factory-approved electric heater kits.
b. AUXILIARY TERMINALS
The AUX and HUM terminals on the Easy Select™ Board
are tied directly to the G terminal, and provide a 24-v.
signal whenever the G terminal is energized (See Fig. 20).
During Super dehumidify mode, the G signal is not present
and the auxiliary terminals are not energized. If the
installation includes the use of the operating mode, do not
use these terminals to control accessories. See Electronic
Air Cleaner and Humidifier sections for further informa-
tion.
c. ELECTRONIC AIR CLEANER CONNECTIONS
The AUX1 and AUX2 terminals are not always energized
during blower operations, as described above. When using
an electronic air cleaner with the unit, use Airflow Sensor
P/N KEAAC0101AAA. The airflow sensor turns on elec-
tronic air cleaner when the blower is operating.
d. HUMIDIFIER/HUMIDISTAT CONNECTIONS
Easy Select™ Board terminals HUM1 and HUM2 are
provided for direct connection to the low-voltage control of
a humidifier through a standard humidistat (See Fig.
20–22). These terminals are energized with 24-v. when G
thermostat signal is present. (See Fig. 20–22). Alternately,
the 24-v. signal may be sourced from the W and C circuit
board connections. When using a Thermidistat™ Control,
Zone Comfort Plus or Comfort Zone II, the 24-v. signal
may be sourced directly from the Thermidistat™ HUM
terminal.
e. DEHUMIDIFY CAPABILITY WITH STANDARD
HUMIDISTAT CONNECTION
Latent capacities for these units are better than average
systems. If increased latent capacity is an application
requirement, the circuit board provides connection termi-
nals for use of a standard humidistat. The unit will detect
the humidistat contacts opening on increasing humidity and
reduce its airflow to approximately 80 percent of nominal
cooling mode airflow. This reduction will increase the
system latent capacity until the humidity falls to a level
which causes the humidistat to close its contacts. When the
Fig. 19—Transformer Label
C99058
TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR
IT WILL NOT AUTOMATICALLY RESET
DISCONNECT POWER AND INSTALL
LOCKOUT TAG PRIOR TO SERVICING
THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING
Fig. 20—Detail of SPP Printed-Circuit Board
C01033
EASY SELECT
HEATER/MOTOR
AUX HEAT KW/CFM
0-30
1075
SEC1
SEC2
J1
AC/HP SIZE
036
030
024
018
AC
HP-COMFORT
HP-EFF
NOM
HI
ENH
LO
SYSTEM TYPE
AC/HP CFM ADJUST
ON/OFF DELAY
CONTINUOUS FAN
MED
HI
YEL
LO
AUX1
HUM1
AUX2
24VAC
GRY
HUM2
YEL
WHT
BLK
ORN
BLU
VIO
0-20
875
0-10
725
0
90
30
90
0
0
0-5
625
TM
J2
D
H
R
W
1
W
2
Y
1
Y/Y
2
G
O
C
9 PIN CONNECTOR
ICM PRINTED CIRCUIT BOARD
12 PIN CONNECTOR
A
B
C
D
E
F
Fig. 21—Humidifier Wiring for 50XZ
A95317
HUMIDISTAT
TO HUMIDIFIER
HUMIDIFIER WIRING
HUM 1
(C)
HUM 2
(G)
24-VAC
16