![Carrier 50XZ024 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/carrier/50xz024/50xz024_installation-start-up-and-service-instructions-manual_2563361022.webp)
again turn off for an additional 30 sec and the outdoor fan for 40
sec. When the Quiet Shift is in OFF position, only a brief 30 sec
cycle will be observed.
If it is desirable to observe a complete defrost in warmer weather,
the defrost thermostat must be closed as follows.
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control
board. (See Fig. 28) Tape to prevent grounding.
3. Restart unit in Heating mode, allowing frost to accumulate on
outdoor coil.
4. After a few minutes in Heating mode, liquid line temperature
should drop below closing point of defrost thermostat (ap-
proximately 30°F).
NOTE:
Unit will remain in defrost until defrost thermostat
reopens at approximately 80°F coil temperature at liquid line or
remainder of defrost cycle time.
5. Turn off power to outdoor and reconnect fan motor lead to
OF2 on control board after above forced defrost cycle.
MAINTENANCE
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should
be inspected at least once each year by a qualified service person.
To troubleshoot unit, refer to Table 7.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
The ability to properly perform maintenance on this equip-
ment requires certain expertise, mechanical skills, tools and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment, other than those
procedures recommended in the User’s Manual. FAILURE
TO HEED THIS WARNING COULD RESULT IN SERI-
OUS INJURY OR DEATH AND POSSIBLE DAMAGE TO
THIS EQUIPMENT.
Failure to follow these warnings could result in serious injury
or death:
1. Turn off electrical power to the unit before performing any
maintenance or service on this unit.
2. Use extreme caution when removing panels and parts. As
with any mechanical equipment, personal injury can result
from sharp edges.
3. Never place anything combustible either on, or in contact
with, the unit.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to disconnect-
ing when servicing.
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
Table 5—FILTER PRESSURE DROP TABLE (In. wg)
FILTER SIZE
CFM
500
600
700
800
900
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20 X 20 X 1
0.05 0.07 0.08 0.10 0.12
0.13
0.14
0.15
—
—
—
—
—
—
—
—
—
—
—
20 X 24 X 1
—
—
—
—
0.09
0.10
0.11
0.13
0.14
0.15
0.16
—
—
—
—
—
—
—
—
24 X 30 X 1
—
—
—
—
—
—
—
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.18
Table 6—ELECTRIC HEAT PRESSURE DROP TABLE
Small Cabinet: 024-036CFM
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
5 kw
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
7.5 kw
0.00
0.00
0.00
0.00
0.00
0.00
0.02
0.03
0.05
0.07
0.08
0.09
10 kw
0.00
0.00
0.00
0.00
0.00
0.02
0.04
0.06
0.07
0.09
0.10
0.11
15 kw
0.00
0.00
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
20 kw
0.00
0.00
0.02
0.04
0.06
0.08
0.09
0.11
0.13
0.15
0.17
0.19
ELECTRIC HEAT PRESSURE DROP TABLE
Large Cabinet: 042-060
CFM
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
5 kw
0.00
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
7.5 kw
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
10 kw
0.00
0.00
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
15 kw
0.00
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
20 kw
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.15
0.16
22