background image

17

A05109

Fig. 16 -- Cooling Charging Chart

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE

: For cooling operation, the recommended airflow is 350 to

450 cfm for each 12,000 Btuh of rated cooling capacity.
Table 4 shows cooling airflows at various external static pressures.

Refer to this table to determine the airflow for the system being
installed.

NOTE

: Be sure that all supply-- and return--air grilles are open, free

from obstructions, and adjusted properly.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect electrical power to the unit and install lockout tag

before changing blower speed.

!

WARNING

Airflow can be changed by changing the lead connections of the

blower motor.
All 50SD units are factory wired for low speed, except sizes 030 and

048 which are wired for medium speed.
FOR 208/230v
For color coding on the 208/230v motor leads, see Table 5.

Table 5—

Color Coding for 208/230v Motor Leads

Black = High Speed

Blue = Medium Speed

Red = Low Speed

To change the speed of the indoor fan motor (IFM), remove the fan

motor speed leg lead from the time delay relay (TDR). This wire is
attached to terminal--3 of TDR for 3--phase units. To change the

speed, remove and replace with lead for desired blower motor speed.
Insulate the removed lead to avoid contact with chassis parts.
COOLING SEQUENCE OF OPERATION
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of

operation is as follows:
When the room temperature rises to a point that is slightly above the

cooling control setting of the thermostat, the thermostat completes

the circuit between thermostat terminal R to terminals Y and G.
These completed circuits through the thermostat connect contactor

coil (C) (through unit wire Y) and time delay relay (TDR) (through
unit wire G) across the 24--v secondary of transformer (TRAN).
The normally open contacts of energized contactor (C) close and
complete the circuit through compressor motor (COMP) to

condenser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally open contacts of energized relay TDR close and
complete the circuit through evaporator blower (indoor) fan motor

(IFM).

50SD

Содержание 50SD024

Страница 1: ...Rater Piston 19 TROUBLESHOOTING 19 START UP CHECKLIST 19 C99001 Fig 1 Unit 50SD SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical com...

Страница 2: ...re that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a n...

Страница 3: ...UNIT 2 00 50 8 SIDE OPPOSITE DUCTS 14 00 355 6 BOTTOM OF UNIT 0 50 12 7 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36...

Страница 4: ...m BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 1066 8 Refer...

Страница 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 50SD024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Страница 6: ...follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is engineered and designed to be ins...

Страница 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Страница 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Страница 9: ...res connected to the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor cont...

Страница 10: ...erminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component System contains oil and refrigerant under pressure 5 To rem...

Страница 11: ...83 3 80 90 208 230 3 60 187 253 11 7 88 0 0 9 4 1 19 6 19 6 25 25 3 8 5 0 10 4 12 0 19 6 20 2 25 25 7 2 10 0 20 8 24 1 31 2 35 2 35 40 11 3 15 0 31 3 36 1 44 2 50 2 15 0 20 0 41 7 48 1 57 2 65 3 60 7...

Страница 12: ...n time delay expires when FAN switch is placed in AUTO position 2 Place SYSTEM switch in COOL position and FAN switch in AUTO position Set cooling control below room temperature Observe that compresso...

Страница 13: ...604 1538 1457 1362 1271 High Watts 798 772 738 700 CFM 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 CFM 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 6...

Страница 14: ...14 A05112 Fig 13 Wiring Diagram 208 230 1 60 50SD...

Страница 15: ...15 A06307 Fig 14 Wiring Diagram 208 230 3 60 50SD...

Страница 16: ...16 A06485 Fig 15 Wiring Diagram 460 3 60 50SD...

Страница 17: ...o change the speed of the indoor fan motor IFM remove the fan motor speed leg lead from the time delay relay TDR This wire is attached to terminal 3 of TDR for 3 phase units To change the speed remove...

Страница 18: ...g season Clean when necessary 4 Check electrical connections for tightness and controls for proper operation each cooling season Service when necessary 5 Ensure electric wires are not in contact with...

Страница 19: ...e grille ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panel to locate all the electri...

Страница 20: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Страница 21: ...AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE ____...

Страница 22: ...t 2006 Carrier Corporation Printed in the U S A Edition Date 09 06 Catalog No 50SD 4SI Replaces 50SD 3SI Manufacturer reserves the right to change at any time specifications and design without notice...

Отзывы: