Some of the factors that affect conversion of sound

power to sound pressure and consequent NC level include:
• Acoustical ceiling type
• Use of metal or flex duct
• Absorption in the occupied space
• Location in the occupied space
• Open or closed layout plan
• Use of open or ducted returns
• Orientation of unit to occupant
• Use of lined or unlined duct

OCTAVE BAND SOUND PRESSURE LEVEL (Lp) 

ASSOCIATED WITH NC CURVES

WSHP sound control

Analyzing the projected sound level in the conditioned
space caused by a WSHP unit is quite involved. The key is
to have good sound power ratings (Lw) in dB on the equip-
ment to determine the ductwork, ceiling and room sound
attenuation effect. We provide suggestions for console unit
sound design around the WSHP units.

Console units

With console units, the fan and compressor are located
within the space, and only the casing design attenuates the
transmission of sound sources into the space. The designer
should carefully review the manufacturer’s acoustical data
when selecting console units and use lower fan speeds to
minimize space noise.

Operating limits

Environment

This equipment is designed for indoor installation ONLY.

Power supply

A voltage variation of ± 10% of nameplate utilization volt-
age is acceptable.

Starting conditions

50KQA units

The 50KQA units start and operate in an ambient temper-
ature of 40 F, with entering air temperature at 40 F, with
entering water temperature at 70 F, with both air and
water at the flow rate used in the ARI Standard 320-86
rating test, for initial start-up in winter.

50KQD units

The 50KQD unit will start and operate in an ambient tem-
perature of 40 F, with entering air temperature at 40 F,
with entering water temperature at 40 F, with both air and
water at the flow rates used in the ARI Standard 320-86
rating test, for initial start-up in winter.
NOTE: These are not normal or continuous operating
conditions. We assume that such a start-up is used to bring
the building space up to occupancy temperature.

AIR LIMITS

WATER LIMITS

    LEGEND

NOTES:

1. Minimum Air and Water conditions can only be used at ARI flow

rates.

2. Only one maximum or minimum value may be used with 50KQA

units, all other parameters must be at normal conditions. The
50KQA units may have up two values at maximum or minimum
with all other parameters at normal conditions.

Solenoid valves

In applications using variable flow pumping, solenoid
valves can be factory installed and operated from the con-
trol board in the Aquazone™ WSHP unit.

Freeze protection

Applications where systems are exposed to outdoor
temperatures below freezing (32 F) must be protected from
freezing. The most common method of protecting water
systems from freezing is adding glycol concentrations into
the water. Use design care when selecting both the type
and concentrations of glycol due to the following:
• Equipment and performance may suffer with high con-

centrations of glycol and other antifreeze solutions

• Loss of piping pressure may increase greatly, resulting

in higher pumping costs

• Higher mixture viscosity may cause excess corrosion

and wear on the entire system

• The water’s acidity may be greatly increased, promoting

corrosion

Glycol promotes galvanic corrosion in systems of dissimilar
metals. The result is corrosion of one metal by the other,
causing leaks.

NOISE

CRITERIA

CURVES

OCTAVE BAND SOUND PRESSURE LEVEL (Lp)

Frequency (Hz)

63

125

250

500

1000

2000

4000

8000

NC-15

49

36

26

17

17

14

12

11

NC-20

52

41

33

27

22

19

17

16

NC-25

54

45

38

31

27

24

22

21

NC-30

58

49

41

36

31

29

28

27

NC-35

61

53

45

40

36

34

33

32

NC-40

64

57

50

45

41

39

38

37

NC-45

67

61

54

49

46

44

43

42

NC-50

71

64

58

54

51

49

48

47

NC-55

74

68

63

58

56

54

53

52

NC-60

77

71

67

63

61

59

58

57

NC-65

80

75

71

68

66

64

63

62

50KQA

50KQD

Cooling

Heating

Cooling

Heating

Min. Ambient Air

50 F

50 F

40 F

40 F

Rated Ambient Air

80 F

70 F

80 F

70 F

Max. Ambient Air

100 F

85 F

100 F

85 F

Min. Entering Air

50 F

50 F

50 F

40 F

Rated Entering Air, db/wb

80/67 F

70 F

80/67 F

70 F

Max. Entering Air, db/wb

100/83 F

80 F

100/83 F

80 F

50KQA

50KQD

Cooling

Heating

Cooling

Heating

Min. Entering Water

60 F

60 F

40 F

40 F

Normal Entering Water

85 F

70 F

85 F

70 F

Max. Entering Water

95 F

90 F

110 F

90 F

db —

Dry Bulb

wb —

Wet Bulb

Application data (cont)

Содержание 50KQA

Страница 1: ...tors and control valves for easy installation Flexible and reliable controls accommodate all systems Features Benefits Carrier s Aquazone console water source heat pumps are a flexible attractive alternative for all finished interior space under window style installations Operating efficiency Carrier Aquazone water source heat pumps WSHP are designed for quali ty and performance excellence over th...

Страница 2: ...ate line Compact cabinet design dimen sions are 10 in deep 48 in wide and 24 in tall with 3 in subbase For flexibility the controls can be mounted on the top right or left side Additionally the sloped top design discourages the use of the unit as a shelf or coffee holder preventing air blockage and any spills from damaging the unit No fuss maintenance and serviceability Regular maintenance or serv...

Страница 3: ...es of emergency electric heat Service test mode with diagnostic LED light emitting diode Test mode allows service personnel to check the operation of the WSHP and control system efficiently Upon enter ing test mode time delays speed up and the Status LED flashes a code indicating the last fault This mode provides easy fault diagnosis based on the fault code the status LED flashes Carrier provided ...

Страница 4: ...ch 15A Fuse F Disconnect Switch Non Fused H 20A Plug Cord Receptacle Disconnect Switch 15A Fuse K 20A Plug Cord Receptacle Disconnect Switch No Fuse Revision Code 0 Current Revision Water Circuit Options Controls A Manual Changeover with Complete C Microprocessor Board B Manual Changeover with Deluxe D Microprocessor Board C Automatic Changeover with Complete C Microprocessor Board D Automatic Cha...

Страница 5: ...2 x 1 8 7 x 291 2 x 1 8 7 x 291 2 x 1 8 7 x 291 2 x 1 8 UNIT WEIGHT lb Shipping Operating 158 151 162 154 172 164 178 168 183 174 REF TO AIR HEAT EXCHANGER Face Area sq ft No of Rows Deep Copper Tube Size O D in No of Fins in 1 44 2 3 8 13 1 44 2 3 8 13 1 44 3 3 8 13 1 81 3 3 8 13 1 81 3 3 8 13 REFRIG CHARGE R 22 CKT oz No of Circuits 16 1 16 1 21 1 23 1 22 1 UNIT CABINET W STAND SUBBASE W x H x D...

Страница 6: ...th dual stage units units with 2 compressors and 2 D controls or in master slave applications Boilerless electric heat control system Allows automatic changeover to electric heat at low loop water temperature Intelligent reversing valve operation Minimizes reversing valve operation for extended life and quiet operation Thermostat type select Y O or Y W Provides ability to work and select heat pump...

Страница 7: ...o control 10 or 18 zones of WSHP units Panel can be ordered to control variable frequency cool ing tower fan operation System pumping operation can be configured for start stop lead lag or variable frequency pump operation Direct Digital Control compatible using the Carrier Comfort Network CCN and WSHP units utilizing PremierLink CCN controllers Fire rated hoses are 2 ft long and have a fixed MPT ...

Страница 8: ...COMMUNICATING CONTROL COOL HEAT AUTO R 5 DAY PROGRAMMABLE NON PROGRAMMABLE AUTO Pm COOL HEAT Carrier CARRIER AQUAZONE THERMOSTATS FOR USE WITH REMOTE THERMOSTAT UNITS 7 DAY PROGRAMMABLE LIGHT ACTIVATED PROGRAMMABLE 7 DAY PROGRAMMABLE FLUSH MOUNT ...

Страница 9: ...610 16 406 FRONT VIEW DAMPER OPENING 48 1219 1 63 41 11 75 298 9 75 248 0 81 21 21 533 3 76 REAR VIEW Control Access Door AIR INLETAREA Air Inlet Discharge Air 1 5 38 3 5 89 0 75 19 R H Pipe Electric Area REAR ACCESS 1 25 1 25 4 5 114 20 508 10 254 8 203 48 1219 48 1219 9 5 241 Optional 5 in 127 sub base will increase damper opening to 3 63 in 92 high and increase overall unit height by 2 in 51 ...

Страница 10: ...ischarge Air 89 10 254 48 1219 48 1219 1 5 38 3 5 9 5 241 1 25 4 5 114 20 21 533 3 76 1 25 REAR ACCESS 508 L H Pipe Electric Area 8 203 0 75 19 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD BOTTOM RETURN CABINET DIMENSIONS LEFT HAND PIPING Optional 5 in 127 subbase will increase damper opening to 3 63 in 92 high and increase overall unit height by 2 in 51...

Страница 11: ...CTRIC AREA 0 75 19 3 5 89 30 10 254 1 5 38 Filter 48 1219 21 533 FRONT VIEW Control Access Door 5 127 16 406 Air Discharge Air Inlet 21 533 48 1219 REAR VIEW REAR ACCESS 1 25 4 5 114 1 25 20 508 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD FRONT RETURN CABINET DIMENSIONS RIGHT HAND PIPING ...

Страница 12: ...OFF PLATE ON BOTTOM OF CHASSIS 3 5 89 30 10 254 1 5 38 Filter 48 1219 21 533 FRONT VIEW Control Access Door 1 5 38 12 5 318 Air Inlet Air Discharge 21 533 48 1219 REAR VIEW 1 25 1 25 4 5 114 REAR ACCESS 20 508 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD FRONT RETURN CABINET DIMENSIONS LEFT HAND PIPING ...

Страница 13: ... LH 30 3 375 86 2 51 4 102 5 127 16 406 1 5 38 9 5 241 1 25 CONDENSATE RELIEF FRONT VIEW RH SIDE VIEW RH POWER SUPPLY IN 13 330 1 25 0 75 19 2 51 3 5 89 2 51 BLOWER DECK BLOWER ACCESS PANEL CONTROL BOX COMPRESSOR ACCESS PANEL 41 1041 20 5 521 WATER OUT WATER IN WATER IN WATER OUT 0 75 19 0 75 19 0 75 19 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD CHASSI...

Страница 14: ... bulb and wet bulb using the Corrections Factor tables found in this book Using the following formulas to determine the cor rection factors of dry bulb and wet bulb a Corrected Total Cooling tabulated total cooling x wet bulb correction x airflow correction b Corrected Sensible Cooling tabulated sensible cooling x wet dry bulb correction x airflow correction V Determine entering air and airflow co...

Страница 15: ... 412 Power Input in watts fan power correction in watts pump power correction in watts Watts Watts NOTE Do not divide ISO Heating Capacity by 3 412 to obtain Btuh Watts Refer to English to SI conversion table in this book b Identify the design conditions corrected for air and water conditions Airflow Cfm 325 Cfm Water Flow Based upon 12 F rise in temp 3 0 GPM External Static Pressure 0 0 in wg non...

Страница 16: ... 6 3 0 71 0 42 10 3 6 7 0 58 4 8 5 0 6 2 7 3 50 1 5 8 4 6 2 0 74 0 44 9 9 7 4 0 61 5 4 1 8 2 2 2 6 1 9 8 5 6 3 0 74 0 44 10 0 7 6 0 60 5 5 2 3 3 0 3 6 2 5 8 6 6 3 0 73 0 43 10 0 7 7 0 60 5 7 5 0 6 2 7 3 60 1 5 8 1 6 1 0 75 0 47 9 7 8 4 0 62 6 3 1 8 2 2 2 6 1 9 8 2 6 1 0 75 0 46 9 8 8 6 0 61 6 5 2 3 3 0 3 6 2 5 8 2 6 1 0 75 0 46 9 8 8 8 0 63 6 6 5 0 6 2 7 3 70 1 5 7 8 6 0 0 77 0 51 9 5 9 4 0 64 7 2...

Страница 17: ... 44 12 4 8 2 0 67 6 0 7 2 8 9 10 5 50 1 7 10 4 7 6 0 73 0 51 12 2 9 0 0 70 6 7 2 3 2 8 3 4 2 3 10 5 7 6 0 73 0 49 12 2 9 3 0 70 6 9 4 3 5 3 6 3 3 0 10 5 7 7 0 73 0 48 12 2 9 4 0 71 7 0 7 2 8 9 10 5 60 1 7 10 0 7 4 0 74 0 56 11 9 10 2 0 73 7 7 2 3 2 8 3 4 2 3 10 1 7 5 0 74 0 55 12 0 10 4 0 73 7 9 4 3 5 3 6 3 3 0 10 2 7 5 0 74 0 54 12 0 10 6 0 74 8 1 7 2 8 9 10 5 70 1 7 9 7 7 3 0 75 0 63 11 8 11 3 0...

Страница 18: ...0 2 3 13 3 7 4 0 55 0 74 15 9 10 7 0 89 7 6 5 5 6 5 7 5 3 0 13 5 7 4 0 55 0 72 15 9 10 9 0 89 7 9 9 7 11 4 13 0 4 0 13 6 7 5 0 55 0 70 16 0 11 1 0 90 8 0 16 6 19 6 22 5 60 2 3 12 9 7 4 0 58 0 82 15 7 12 1 0 93 8 9 5 5 6 5 7 5 3 0 13 0 7 5 0 57 0 79 15 7 12 3 0 95 9 1 9 7 11 4 13 0 4 0 13 1 7 5 0 57 0 78 15 8 12 5 0 97 9 2 16 6 19 6 22 5 70 2 3 12 4 7 4 0 60 0 89 15 5 13 5 0 99 10 1 5 5 6 5 7 5 3 0...

Страница 19: ...13 8 1 5 0 9 5 13 9 50 2 7 16 1 10 6 0 66 0 92 19 2 13 2 1 18 9 2 1 5 2 9 4 2 3 7 16 3 10 7 0 66 0 87 19 3 13 6 1 17 9 6 3 0 5 6 8 1 4 9 16 5 10 8 0 66 0 84 19 4 13 8 1 19 9 8 5 0 9 5 13 9 60 2 7 15 6 10 4 0 67 0 95 18 9 15 1 1 23 10 9 1 5 2 9 4 2 3 7 15 8 10 5 0 66 0 91 18 9 15 5 1 26 11 2 3 0 5 6 8 1 4 9 16 0 10 6 0 66 0 89 19 0 15 6 1 23 11 4 5 0 9 5 13 9 70 2 7 15 1 10 2 0 67 1 08 18 8 17 0 1 ...

Страница 20: ...3 5 18 9 11 7 0 62 1 09 22 6 17 0 1 46 12 0 2 6 4 9 7 1 4 5 19 0 11 8 0 62 1 05 22 6 17 4 1 50 12 3 4 2 8 0 11 7 6 0 19 2 11 9 0 62 1 03 22 7 17 7 1 53 12 5 8 3 15 1 21 6 60 3 5 18 3 11 4 0 63 1 19 22 3 19 1 1 56 13 8 2 6 4 9 7 1 4 5 18 4 11 5 0 62 1 16 22 4 19 6 1 59 14 1 4 2 8 0 11 7 6 0 18 6 11 6 0 62 1 13 22 5 20 0 1 63 14 4 8 3 15 1 21 6 70 3 5 17 6 11 2 0 64 1 30 22 1 21 3 1 65 15 7 2 6 4 9 ...

Страница 21: ...0 856 73 0 961 0 930 0 924 0 957 0 977 1 088 0 885 80 0 971 0 947 0 943 0 968 0 982 1 066 0 914 87 0 980 0 964 0 961 0 978 0 988 1 045 0 941 92 0 990 0 982 0 981 0 989 0 994 1 023 0 971 100 1 000 1 000 1 000 1 000 1 000 1 000 1 000 107 1 011 1 019 1 021 1 012 1 006 0 976 1 031 113 1 020 1 035 1 038 1 022 1 012 0 956 1 058 COOLING CORRECTIONS HEATING CORRECTIONS Entering Air Wet Bulb F Total Coolin...

Страница 22: ...rface The number of coils required depends on system load and design This application requires minimum piping and excavation Open loop system Use this system where ground water is plentiful In this application ground water is pumped through supply piping from the well to the build ing The water is then pumped back into the ground through a discharge well as it leaves the building An addi tional he...

Страница 23: ...water loop applications Aqua zone WSHP units use copper water to refrigerant heat exchanger Units can also be equipped with a Cupronickel heat exchanger for applications where water is outside the copper heat exchanger s standard contaminant limits WATER QUALITY GUIDELINES If the concentration of these corrosives exceeds the maximum allow able level then the potential for serious corrosion problem...

Страница 24: ...S 1 Minimum Air and Water conditions can only be used at ARI flow rates 2 Only one maximum or minimum value may be used with 50KQA units all other parameters must be at normal conditions The 50KQA units may have up two values at maximum or minimum with all other parameters at normal conditions Solenoid valves In applications using variable flow pumping solenoid valves can be factory installed and ...

Страница 25: ...0 1 60 197 254 3 8 20 0 0 33 4 8 6 0 15 265 1 60 239 292 3 3 18 6 0 35 3 7 4 5 15 012 115 1 60 104 126 9 7 54 0 1 28 11 5 14 0 20 208 230 1 60 197 254 4 8 26 3 0 52 5 4 6 6 15 265 1 60 239 292 4 2 28 0 0 43 4 8 5 9 15 015 208 230 1 60 197 254 6 4 38 0 0 52 7 5 9 3 15 265 1 60 239 292 5 4 32 0 0 43 5 9 7 3 15 019 208 230 1 60 197 254 7 6 45 0 1 10 9 4 11 5 15 265 1 60 239 292 6 3 32 0 0 83 7 2 8 8 ...

Страница 26: ...EAT X O O X X O O X X BLOWER MOTOR WIRING UNIT SIZE POLE A POLE B 007 5 3 009 5 3 012 5 4 015 4 3 019 4 3 AL Alarm Relay Contacts BM Blower Motor BR Blower Relay Cap Capacitor CO Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor Water Coil Freeze Protection FP2 Sensor Air Coil Freeze Protection HP High Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB...

Страница 27: ...Trace Optional Low Voltage Wiring Relay Contactor Coil Solenoid Coil Thermistor Ground Mate N Lock NOTES 1 Compressor and Blower Motor thermally protected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and in...

Страница 28: ...o tected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and insulate RED lead Transformer is energy limiting or may have circuit breaker 4 FP1 Thermistor provides freeze protection for WATER When using ANTI F...

Страница 29: ...5 3 009 5 3 012 5 4 015 4 3 019 4 3 PUSH BUTTON SWITCH ATTRIBUTES X CLOSED O OPEN TERMINALS 1 2 3 4 5 6 7 8 1A 1B 2A 3A 4A 5A 6A 7A 8A STOP X O O O O O O O O FAN ONLY X O O O O X O O O LOW FAN X O O X X O X O O HIGH FAN X O O X X O O X X Field Line Voltage Wiring Field Low Voltage Wiring Printed Circuit Trace Optional Low Voltage Wiring Relay Contactor Coil Solenoid Coil Thermistor Ground Mate N L...

Страница 30: ...mpressor and Blower Motor thermally pro tected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and insulate RED lead Transformer is energy limiting or may have circuit breaker 4 FP1 Thermistor provides freeze ...

Страница 31: ... RELAY FAULT STATUS R RV G TEST Y Microprocessor D NO COM NO 1 FP2 CO P7 12 RV 9 10 8 4 FP1 6 7 5 LOC HP 3 2 NC SPEED RELAY FAN RELAY JW4 NOTES 1 Compressor and Blower Motor thermally protected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 6...

Страница 32: ... bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing through the 41 2 in 114 wide opening in the rear cabinet 3 Be sure adequate room is given for any accessories like valves disconnect switches etc 4 All measurements in inches Measur...

Страница 33: ... 3 5 89 3 5 89 3 5 89 2 51 WITH MOTORIZED SHUT OFF VALVE Subbase available only on bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing through the 41 2 in 114 wide opening in the rear cabinet 3 All measurements in inches Measurements ...

Страница 34: ...330 13 330 13 330 5 5 140 2 51 1 5 38 9 5 241 3 76 7 178 7 5 191 21 533 4 25 108 Fuses Power Supply In 1 25 32 1 25 3 5 89 L E F T H A N D R I G H T H A N D Subbase available only on bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing...

Страница 35: ...The cabinet shall be powder painted C Fan and Motor Assembly The fan motors shall be multi speed permanently lubricated PSC permanent split capacitor type with thermal overload protection To facilitate field service all units shall have a slide out fan deck and quick electrical disconnect D Refrigerant Components 1 Units shall have a sealed refrigerant circuit includ ing a hermetic compressor a re...

Страница 36: ...Cool Hi Heat Lo Heat Unit mounted thermostats shall have a remote sensor for sensing the return air temperature 5 The optional Deluxe D electronic control shall have all the features of the Complete C control with the following additional features a 75 VA transformer b A removable thermostat connector c Random start on return from night setback d Minimized reversing value operation for extended li...

Страница 37: ...by the remote thermostat G Special Features 1 Aquazone Thermostat Controls for use with remote thermostat units a Programmable multi stage thermostat with 7 day clock holiday scheduling large backlit display and remote sensor capability b Programmable 7 Day Light Activated Ther mostat offers occupied comfort settings with lights on unoccupied energy savings with lights off c Programmable 7 Day Flu...

Страница 38: ......

Страница 39: ......

Страница 40: ...at any time specifications or designs without notice and without incurring obligations New Pg 40 Catalog No 525 00049 Printed in U S A PC 111 Form 50KQ 6PD Replaces 50KQ 5PD Book 1 4 Tab 5a 5a Carrier Corporation Syracuse New York 13221 5 03 Book 1 Tab 1IP4a ...

Отзывы: