Aquazone™

 

water source heat pump products are available

in a flexible, efficient array of models, which can be used in
all types of water loop, ground water, and ground loop
type systems. Use Aquazone products to provide optimal
energy efficient solutions and adapt to the most challeng-
ing design requirements.

AQUAZONE PRODUCT GUIDE

Water loop system

Water loop (or boiler/tower) system applications typically
include a number of units plumbed to a common piping
system. For optimal performance, design this system be-
tween 2.25 and 3 gpm per ton of cooling capacity. The
system is comprised of highly efficient packaged reverse
cycle heat pump units interconnected by a water loop. The
water circuit serves as both a sink and source for heat ab-
sorption and rejection and is designed for entering water
temperatures between 60

 

F and 90 F. Within this temper-

ature range, units can heat or cool from the same water
source. Transferring heat from warm to cold spaces in the
building, whenever they coexist, conserves energy rather
than creating new heat.

Refer to the

 Carrier

 

Water Source Heat Pump Sys-

tem Design Guide 

for assistance designing water loop

systems. The guide includes a practical approach for the
latest and most current design recommendations including:
• Horizontal, vertical, console, rooftop and water-to-

water product applications.

• Ventilation methods and system design including energy

recovery.

• Acoustical considerations for different product types.
• Addressing IAQ issues such as condensate removal,

humidity control.

• Air distribution design including diffuser selection/

layout and ductwork design.

• Hydronic system design including pipe sizing/layout

and boiler/tower sizing.

• Control configurations such as stand alone, DDC, DCV,

and VVT®.

• WSHP efficiency/operational cost comparison chart.
• System variations such as a system without a boiler,

variable pumping, and VAV for interior use.

Ground water systems

To use Aquazone units in ground water applications, you
should specify extended range. This will provide factory-
installed coaxial coil insulation to prevent condensate from
dripping when entering water temperatures are below
60 F. In addition, the copper coaxial coil installed on the
Aquazone units may not be suitable for all water condi-
tions. Refer to the Water Conditioning section for proper
coaxial coil material selection.

Surface water system — 

This system is typically located

near a lake or pond. In this application, the loop can be
submerged in a series of coils beneath the water surface.
The number of coils required depends on system load and
design. This application requires minimum piping and
excavation.

Open loop system — 

Use this system where ground

water is plentiful. In this application, ground water is
pumped through supply piping from the well to the build-
ing. The water is then pumped back into the ground
through a discharge well as it leaves the building. An addi-
tional heat exchanger is usually installed between the build-
ing water piping system and the ground water piping sys-
tem. This design limits piping and excavation.

Aquazone units include a standard TXV and are rated to

extremely low temperatures to self-adjust the refrigeration
circuit. Therefore, open loop systems do not require water
regulating valves. We recommend a slow opening/closing
solenoid valve to conserve water.

Ground loop systems

There are many commonly specified designs for ground
loop applications. Typical designs include vertical loops
and horizontal loops. In some applications, water is piped
from the ground or lake directly to the water source heat
pump. This system only requires piping to get the water
from the source to the unit.
NOTE: When utilizing Aquazone water source heat pumps
in ground loop systems, refer to the design considerations
in the ground water system section.

Horizontal ground loop —

 Use this system when ade-

quate space is available and trenching can be easily accom-
plished. A series of parallel pipes are laid out in trenches 3
to 6 feet below the ground surface, and then back-filled.
Often, multiple pipes are used to maximize each trench’s
heat transfer capability. Ground conditions, heating and
cooling requirements, and system design determine piping
requirements and ground loop field size.

50 SERIES

TYPE

SIZE (tons)

APPLICATION

50RHC,RVC

Horizontal/Vertical

Standard

Efficiency

1

/

2

-5

Efficient, compact, low cost 
alternative for retrofit or new 
boiler/tower systems.

50RHR,RVR

Horizontal/Vertical

High 

Efficiency

1

/

2

-5

Efficient, adaptable unit for 
new boiler/tower, ground 
water, or ground loop systems.

50RHS,RVS

Horizontal/Vertical

Premium 

Efficiency

1

1

/

4

-6

Premium, ultra efficient unit for 
new boiler/tower, ground 
water, or ground loop systems

50HQ,VQ

Horizontal/Vertical

Large Capacity

6

1

/

2

-25

Designed to handle large 
zoned areas for all 
applications.

50KQ

Console

1

/

2

-1

1

/

2

Attractive design for finished 
interior, under-window 
installations.

50RTG

Rooftop

3-20

Economical solution for IAQ 
problems and tempering 
ventilation air.

50RWS

Water-to-Water

3-30

Used to pre-heat or cool 
air and can be used as a 
stand-alone or supplemental 
boiler/chiller in most hydronic 
heating applications. Also 
conditions process fluids, 
lubricants and refrigerants.

Application data

Содержание 50KQA

Страница 1: ...tors and control valves for easy installation Flexible and reliable controls accommodate all systems Features Benefits Carrier s Aquazone console water source heat pumps are a flexible attractive alternative for all finished interior space under window style installations Operating efficiency Carrier Aquazone water source heat pumps WSHP are designed for quali ty and performance excellence over th...

Страница 2: ...ate line Compact cabinet design dimen sions are 10 in deep 48 in wide and 24 in tall with 3 in subbase For flexibility the controls can be mounted on the top right or left side Additionally the sloped top design discourages the use of the unit as a shelf or coffee holder preventing air blockage and any spills from damaging the unit No fuss maintenance and serviceability Regular maintenance or serv...

Страница 3: ...es of emergency electric heat Service test mode with diagnostic LED light emitting diode Test mode allows service personnel to check the operation of the WSHP and control system efficiently Upon enter ing test mode time delays speed up and the Status LED flashes a code indicating the last fault This mode provides easy fault diagnosis based on the fault code the status LED flashes Carrier provided ...

Страница 4: ...ch 15A Fuse F Disconnect Switch Non Fused H 20A Plug Cord Receptacle Disconnect Switch 15A Fuse K 20A Plug Cord Receptacle Disconnect Switch No Fuse Revision Code 0 Current Revision Water Circuit Options Controls A Manual Changeover with Complete C Microprocessor Board B Manual Changeover with Deluxe D Microprocessor Board C Automatic Changeover with Complete C Microprocessor Board D Automatic Cha...

Страница 5: ...2 x 1 8 7 x 291 2 x 1 8 7 x 291 2 x 1 8 7 x 291 2 x 1 8 UNIT WEIGHT lb Shipping Operating 158 151 162 154 172 164 178 168 183 174 REF TO AIR HEAT EXCHANGER Face Area sq ft No of Rows Deep Copper Tube Size O D in No of Fins in 1 44 2 3 8 13 1 44 2 3 8 13 1 44 3 3 8 13 1 81 3 3 8 13 1 81 3 3 8 13 REFRIG CHARGE R 22 CKT oz No of Circuits 16 1 16 1 21 1 23 1 22 1 UNIT CABINET W STAND SUBBASE W x H x D...

Страница 6: ...th dual stage units units with 2 compressors and 2 D controls or in master slave applications Boilerless electric heat control system Allows automatic changeover to electric heat at low loop water temperature Intelligent reversing valve operation Minimizes reversing valve operation for extended life and quiet operation Thermostat type select Y O or Y W Provides ability to work and select heat pump...

Страница 7: ...o control 10 or 18 zones of WSHP units Panel can be ordered to control variable frequency cool ing tower fan operation System pumping operation can be configured for start stop lead lag or variable frequency pump operation Direct Digital Control compatible using the Carrier Comfort Network CCN and WSHP units utilizing PremierLink CCN controllers Fire rated hoses are 2 ft long and have a fixed MPT ...

Страница 8: ...COMMUNICATING CONTROL COOL HEAT AUTO R 5 DAY PROGRAMMABLE NON PROGRAMMABLE AUTO Pm COOL HEAT Carrier CARRIER AQUAZONE THERMOSTATS FOR USE WITH REMOTE THERMOSTAT UNITS 7 DAY PROGRAMMABLE LIGHT ACTIVATED PROGRAMMABLE 7 DAY PROGRAMMABLE FLUSH MOUNT ...

Страница 9: ...610 16 406 FRONT VIEW DAMPER OPENING 48 1219 1 63 41 11 75 298 9 75 248 0 81 21 21 533 3 76 REAR VIEW Control Access Door AIR INLETAREA Air Inlet Discharge Air 1 5 38 3 5 89 0 75 19 R H Pipe Electric Area REAR ACCESS 1 25 1 25 4 5 114 20 508 10 254 8 203 48 1219 48 1219 9 5 241 Optional 5 in 127 sub base will increase damper opening to 3 63 in 92 high and increase overall unit height by 2 in 51 ...

Страница 10: ...ischarge Air 89 10 254 48 1219 48 1219 1 5 38 3 5 9 5 241 1 25 4 5 114 20 21 533 3 76 1 25 REAR ACCESS 508 L H Pipe Electric Area 8 203 0 75 19 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD BOTTOM RETURN CABINET DIMENSIONS LEFT HAND PIPING Optional 5 in 127 subbase will increase damper opening to 3 63 in 92 high and increase overall unit height by 2 in 51...

Страница 11: ...CTRIC AREA 0 75 19 3 5 89 30 10 254 1 5 38 Filter 48 1219 21 533 FRONT VIEW Control Access Door 5 127 16 406 Air Discharge Air Inlet 21 533 48 1219 REAR VIEW REAR ACCESS 1 25 4 5 114 1 25 20 508 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD FRONT RETURN CABINET DIMENSIONS RIGHT HAND PIPING ...

Страница 12: ...OFF PLATE ON BOTTOM OF CHASSIS 3 5 89 30 10 254 1 5 38 Filter 48 1219 21 533 FRONT VIEW Control Access Door 1 5 38 12 5 318 Air Inlet Air Discharge 21 533 48 1219 REAR VIEW 1 25 1 25 4 5 114 REAR ACCESS 20 508 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD FRONT RETURN CABINET DIMENSIONS LEFT HAND PIPING ...

Страница 13: ... LH 30 3 375 86 2 51 4 102 5 127 16 406 1 5 38 9 5 241 1 25 CONDENSATE RELIEF FRONT VIEW RH SIDE VIEW RH POWER SUPPLY IN 13 330 1 25 0 75 19 2 51 3 5 89 2 51 BLOWER DECK BLOWER ACCESS PANEL CONTROL BOX COMPRESSOR ACCESS PANEL 41 1041 20 5 521 WATER OUT WATER IN WATER IN WATER OUT 0 75 19 0 75 19 0 75 19 NOTE All measurements in inches Measurements in parentheses are in millimeters 50KQA KQD CHASSI...

Страница 14: ... bulb and wet bulb using the Corrections Factor tables found in this book Using the following formulas to determine the cor rection factors of dry bulb and wet bulb a Corrected Total Cooling tabulated total cooling x wet bulb correction x airflow correction b Corrected Sensible Cooling tabulated sensible cooling x wet dry bulb correction x airflow correction V Determine entering air and airflow co...

Страница 15: ... 412 Power Input in watts fan power correction in watts pump power correction in watts Watts Watts NOTE Do not divide ISO Heating Capacity by 3 412 to obtain Btuh Watts Refer to English to SI conversion table in this book b Identify the design conditions corrected for air and water conditions Airflow Cfm 325 Cfm Water Flow Based upon 12 F rise in temp 3 0 GPM External Static Pressure 0 0 in wg non...

Страница 16: ... 6 3 0 71 0 42 10 3 6 7 0 58 4 8 5 0 6 2 7 3 50 1 5 8 4 6 2 0 74 0 44 9 9 7 4 0 61 5 4 1 8 2 2 2 6 1 9 8 5 6 3 0 74 0 44 10 0 7 6 0 60 5 5 2 3 3 0 3 6 2 5 8 6 6 3 0 73 0 43 10 0 7 7 0 60 5 7 5 0 6 2 7 3 60 1 5 8 1 6 1 0 75 0 47 9 7 8 4 0 62 6 3 1 8 2 2 2 6 1 9 8 2 6 1 0 75 0 46 9 8 8 6 0 61 6 5 2 3 3 0 3 6 2 5 8 2 6 1 0 75 0 46 9 8 8 8 0 63 6 6 5 0 6 2 7 3 70 1 5 7 8 6 0 0 77 0 51 9 5 9 4 0 64 7 2...

Страница 17: ... 44 12 4 8 2 0 67 6 0 7 2 8 9 10 5 50 1 7 10 4 7 6 0 73 0 51 12 2 9 0 0 70 6 7 2 3 2 8 3 4 2 3 10 5 7 6 0 73 0 49 12 2 9 3 0 70 6 9 4 3 5 3 6 3 3 0 10 5 7 7 0 73 0 48 12 2 9 4 0 71 7 0 7 2 8 9 10 5 60 1 7 10 0 7 4 0 74 0 56 11 9 10 2 0 73 7 7 2 3 2 8 3 4 2 3 10 1 7 5 0 74 0 55 12 0 10 4 0 73 7 9 4 3 5 3 6 3 3 0 10 2 7 5 0 74 0 54 12 0 10 6 0 74 8 1 7 2 8 9 10 5 70 1 7 9 7 7 3 0 75 0 63 11 8 11 3 0...

Страница 18: ...0 2 3 13 3 7 4 0 55 0 74 15 9 10 7 0 89 7 6 5 5 6 5 7 5 3 0 13 5 7 4 0 55 0 72 15 9 10 9 0 89 7 9 9 7 11 4 13 0 4 0 13 6 7 5 0 55 0 70 16 0 11 1 0 90 8 0 16 6 19 6 22 5 60 2 3 12 9 7 4 0 58 0 82 15 7 12 1 0 93 8 9 5 5 6 5 7 5 3 0 13 0 7 5 0 57 0 79 15 7 12 3 0 95 9 1 9 7 11 4 13 0 4 0 13 1 7 5 0 57 0 78 15 8 12 5 0 97 9 2 16 6 19 6 22 5 70 2 3 12 4 7 4 0 60 0 89 15 5 13 5 0 99 10 1 5 5 6 5 7 5 3 0...

Страница 19: ...13 8 1 5 0 9 5 13 9 50 2 7 16 1 10 6 0 66 0 92 19 2 13 2 1 18 9 2 1 5 2 9 4 2 3 7 16 3 10 7 0 66 0 87 19 3 13 6 1 17 9 6 3 0 5 6 8 1 4 9 16 5 10 8 0 66 0 84 19 4 13 8 1 19 9 8 5 0 9 5 13 9 60 2 7 15 6 10 4 0 67 0 95 18 9 15 1 1 23 10 9 1 5 2 9 4 2 3 7 15 8 10 5 0 66 0 91 18 9 15 5 1 26 11 2 3 0 5 6 8 1 4 9 16 0 10 6 0 66 0 89 19 0 15 6 1 23 11 4 5 0 9 5 13 9 70 2 7 15 1 10 2 0 67 1 08 18 8 17 0 1 ...

Страница 20: ...3 5 18 9 11 7 0 62 1 09 22 6 17 0 1 46 12 0 2 6 4 9 7 1 4 5 19 0 11 8 0 62 1 05 22 6 17 4 1 50 12 3 4 2 8 0 11 7 6 0 19 2 11 9 0 62 1 03 22 7 17 7 1 53 12 5 8 3 15 1 21 6 60 3 5 18 3 11 4 0 63 1 19 22 3 19 1 1 56 13 8 2 6 4 9 7 1 4 5 18 4 11 5 0 62 1 16 22 4 19 6 1 59 14 1 4 2 8 0 11 7 6 0 18 6 11 6 0 62 1 13 22 5 20 0 1 63 14 4 8 3 15 1 21 6 70 3 5 17 6 11 2 0 64 1 30 22 1 21 3 1 65 15 7 2 6 4 9 ...

Страница 21: ...0 856 73 0 961 0 930 0 924 0 957 0 977 1 088 0 885 80 0 971 0 947 0 943 0 968 0 982 1 066 0 914 87 0 980 0 964 0 961 0 978 0 988 1 045 0 941 92 0 990 0 982 0 981 0 989 0 994 1 023 0 971 100 1 000 1 000 1 000 1 000 1 000 1 000 1 000 107 1 011 1 019 1 021 1 012 1 006 0 976 1 031 113 1 020 1 035 1 038 1 022 1 012 0 956 1 058 COOLING CORRECTIONS HEATING CORRECTIONS Entering Air Wet Bulb F Total Coolin...

Страница 22: ...rface The number of coils required depends on system load and design This application requires minimum piping and excavation Open loop system Use this system where ground water is plentiful In this application ground water is pumped through supply piping from the well to the build ing The water is then pumped back into the ground through a discharge well as it leaves the building An addi tional he...

Страница 23: ...water loop applications Aqua zone WSHP units use copper water to refrigerant heat exchanger Units can also be equipped with a Cupronickel heat exchanger for applications where water is outside the copper heat exchanger s standard contaminant limits WATER QUALITY GUIDELINES If the concentration of these corrosives exceeds the maximum allow able level then the potential for serious corrosion problem...

Страница 24: ...S 1 Minimum Air and Water conditions can only be used at ARI flow rates 2 Only one maximum or minimum value may be used with 50KQA units all other parameters must be at normal conditions The 50KQA units may have up two values at maximum or minimum with all other parameters at normal conditions Solenoid valves In applications using variable flow pumping solenoid valves can be factory installed and ...

Страница 25: ...0 1 60 197 254 3 8 20 0 0 33 4 8 6 0 15 265 1 60 239 292 3 3 18 6 0 35 3 7 4 5 15 012 115 1 60 104 126 9 7 54 0 1 28 11 5 14 0 20 208 230 1 60 197 254 4 8 26 3 0 52 5 4 6 6 15 265 1 60 239 292 4 2 28 0 0 43 4 8 5 9 15 015 208 230 1 60 197 254 6 4 38 0 0 52 7 5 9 3 15 265 1 60 239 292 5 4 32 0 0 43 5 9 7 3 15 019 208 230 1 60 197 254 7 6 45 0 1 10 9 4 11 5 15 265 1 60 239 292 6 3 32 0 0 83 7 2 8 8 ...

Страница 26: ...EAT X O O X X O O X X BLOWER MOTOR WIRING UNIT SIZE POLE A POLE B 007 5 3 009 5 3 012 5 4 015 4 3 019 4 3 AL Alarm Relay Contacts BM Blower Motor BR Blower Relay Cap Capacitor CO Condensate Overflow CR Compressor Relay DM Damper Motor FP1 Sensor Water Coil Freeze Protection FP2 Sensor Air Coil Freeze Protection HP High Pressure Switch JW1 Jumper Wire for Alarm LOC Loss of Charge Pressure Switch PB...

Страница 27: ...Trace Optional Low Voltage Wiring Relay Contactor Coil Solenoid Coil Thermistor Ground Mate N Lock NOTES 1 Compressor and Blower Motor thermally protected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and in...

Страница 28: ...o tected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and insulate RED lead Transformer is energy limiting or may have circuit breaker 4 FP1 Thermistor provides freeze protection for WATER When using ANTI F...

Страница 29: ...5 3 009 5 3 012 5 4 015 4 3 019 4 3 PUSH BUTTON SWITCH ATTRIBUTES X CLOSED O OPEN TERMINALS 1 2 3 4 5 6 7 8 1A 1B 2A 3A 4A 5A 6A 7A 8A STOP X O O O O O O O O FAN ONLY X O O O O X O O O LOW FAN X O O X X O X O O HIGH FAN X O O X X O O X X Field Line Voltage Wiring Field Low Voltage Wiring Printed Circuit Trace Optional Low Voltage Wiring Relay Contactor Coil Solenoid Coil Thermistor Ground Mate N L...

Страница 30: ...mpressor and Blower Motor thermally pro tected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 60 switch RED and ORG Leads at L1 and insulate RED lead Transformer is energy limiting or may have circuit breaker 4 FP1 Thermistor provides freeze ...

Страница 31: ... RELAY FAULT STATUS R RV G TEST Y Microprocessor D NO COM NO 1 FP2 CO P7 12 RV 9 10 8 4 FP1 6 7 5 LOC HP 3 2 NC SPEED RELAY FAN RELAY JW4 NOTES 1 Compressor and Blower Motor thermally protected internally 2 All wiring to the unit must comply with NEC and local codes 3 Transformer is wired to 115V WHT lead for 115 1 60 units 265V BRN Lead for 265 1 60 units or 208V RED Lead for 208 1 60 For 230 1 6...

Страница 32: ... bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing through the 41 2 in 114 wide opening in the rear cabinet 3 Be sure adequate room is given for any accessories like valves disconnect switches etc 4 All measurements in inches Measur...

Страница 33: ... 3 5 89 3 5 89 3 5 89 2 51 WITH MOTORIZED SHUT OFF VALVE Subbase available only on bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing through the 41 2 in 114 wide opening in the rear cabinet 3 All measurements in inches Measurements ...

Страница 34: ...330 13 330 13 330 5 5 140 2 51 1 5 38 9 5 241 3 76 7 178 7 5 191 21 533 4 25 108 Fuses Power Supply In 1 25 32 1 25 3 5 89 L E F T H A N D R I G H T H A N D Subbase available only on bottom return units No condensate trap required Electrical wiring and water piping may enter the cabinet either 1 From below passing up through the 71 8 in 181 x 31 2 in 89 opening in the subbase 2 From behind passing...

Страница 35: ...The cabinet shall be powder painted C Fan and Motor Assembly The fan motors shall be multi speed permanently lubricated PSC permanent split capacitor type with thermal overload protection To facilitate field service all units shall have a slide out fan deck and quick electrical disconnect D Refrigerant Components 1 Units shall have a sealed refrigerant circuit includ ing a hermetic compressor a re...

Страница 36: ...Cool Hi Heat Lo Heat Unit mounted thermostats shall have a remote sensor for sensing the return air temperature 5 The optional Deluxe D electronic control shall have all the features of the Complete C control with the following additional features a 75 VA transformer b A removable thermostat connector c Random start on return from night setback d Minimized reversing value operation for extended li...

Страница 37: ...by the remote thermostat G Special Features 1 Aquazone Thermostat Controls for use with remote thermostat units a Programmable multi stage thermostat with 7 day clock holiday scheduling large backlit display and remote sensor capability b Programmable 7 Day Light Activated Ther mostat offers occupied comfort settings with lights on unoccupied energy savings with lights off c Programmable 7 Day Flu...

Страница 38: ......

Страница 39: ......

Страница 40: ...at any time specifications or designs without notice and without incurring obligations New Pg 40 Catalog No 525 00049 Printed in U S A PC 111 Form 50KQ 6PD Replaces 50KQ 5PD Book 1 4 Tab 5a 5a Carrier Corporation Syracuse New York 13221 5 03 Book 1 Tab 1IP4a ...

Отзывы: