CL-1
CONTROL SET-UP CHECKLIST
Model Number: ____________________________________
Software Versions: ____________________________________
Serial Number: _____________________________________
MBB: CESR131278-00- __ __
Date: ____________________________________________
SCB/ECB: CESR131249-00- __ __
Technician: ________________________________________
MARQ: CESR131171-01- __ __
INDICATE UNIT SETTINGS BELOW
Control Type:
Thermostat / T55 Space Temp. / T56 Space Temp. / T58 Space Temp.
Set Points:
Cooling
Occupied:___________
Unoccupied:____________
Heating
Occupied:___________
Unoccupied:____________
Configurations
SETTING
Default
UNIT
U.CTL ________
Auto
Thermostat
Space
Sensor
T.CTL
________
Adaptive
1 Stage Y1
2 Stage Y1
OC.FN ________
Y
N
S.DLY ________
30
IDF.F
________
N
Y
FN.SW
________
No Switch
Normal Open
Normal Close
FL.SW
________
No Switch
Normal Open
Normal Close
FS.SW
________
No Switch
Normal Open
Normal Close
RM.SW
________
No Switch
Normal Open
Normal Close
ECB ________
Y
N
SAT.T ________
240
COOL
N.CMP
________
3 (016-024) or 2 (014,028)
MC.LO
________
0° F
MRT.C
________
180 sec
MOT.C
________
300 sec
CL.PD
________
1.0
∆
F
CL.ND
________
–1.0
∆
F
C.LAG
________
1.0 min
SA.PD
________
1.0
∆
F
SA.ND
________
–1.0
∆
F
C.INC
________
450 sec
C.DEC
________
300 sec
A.NOW
________
Y
N
INV.E ________
Y
N
A1.CS
________
Y
N
B1.CS
________
Y
N
C1.CS
________
Y
N
HEAT
HT.TY
________
No Heat
GAS
ELECTRIC
N.HTR
________
2
HT.LO
________
75 F
MRT.H
________
120 sec
MOT.H
________
120 sec
HT.PD
________
1.0
∆
F
HT.ND
________
–1.0
∆
F
H.LAG
________
1.0 min
H.INC
________
450 sec
H.DEC
________
300 sec
202
→
Содержание 48HG016
Страница 3: ...3 Fig 1 Low Voltage Control Schematic 48HG Units...
Страница 4: ...4 Fig 2 Low Voltage Control Schematic 50HG Units...
Страница 5: ...5 Fig 3 Typical Power Schematic...