Table 9 — “Service Test” Mode and Submode Directory
Table 10 — “Temperatures” Mode and Submode Directory
SUBMODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
TEST
ON/OFF
Field Service Test Mode
Use to Enable/Disable Manual Mode
INDP
Test Independent Outputs
ECON
XXX
Economizer Position Test
%
E.PWR
ON/OFF
Economizer Power Test
E.CAL
ON/OFF
Calibrate Economizer
PE.1
ON/OFF
Power Exhaust 1 Test
PE.2
ON/OFF
Power Exhaust 2 Test
ALM
ON/OFF
Alarm Relay Test
FANS
Test Fans
IDF
ON/OFF
Indoor Fan Test
IDFP
ON/OFF
Indoor Fan Power Test
OFC.1
ON/OFF
Outdoor Fan Cntr 1 Test
OFC.2
ON/OFF
Outdoor Fan Cntr 2 Test
OFC.3
ON/OFF
Outdoor Fan Cntr 3 Test
COOL
Test Cooling
A1
ON/OFF
Compressor A1 Test
B1
ON/OFF
Compressor B1 Test
C1
ON/OFF
Compressor C1 Test
HEAT
Test Heating
HTR.1
ON/OFF
Heat Stage 1 Test
HTR.2
ON/OFF
Heat Stage 2 Test
SUBMODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
UNIT
Unit Temperatures
SAT
XXX.X
Supply Air Temperature
OAT
XXX.X
Outdoor Air Temperature
SPT
XXX.X
Space Temperature
SPTO
X.X
Space Temperature Offset
CIRC
Circuit Temperatures
SST.A
XXX.X
Saturated Suct Temp A
Temperature is calculated
SCT.A
XXX.X
Saturated Cond Temp A
SST.B
XXX.X
Saturated Suct Temp B
Temperature is calculated
SCT.B
XXX.X
Saturated Cond Temp B
SST.C
XXX.X
Saturated Suct Temp C
Temperature is calculated
SCT.C
XXX.X
Saturated Cond Temp C
CALB
Calibrate Temperatures
SPT.C
XXX.X
Space Sensor Calibration
Enter either temperature or
trim but not both
SPT.T
XXX.X
Space Temperature Trim
Enter either temperature or
trim but not both
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER