18
Table 16 — “Configuration” Mode and Submode Directory (cont)
SUBMODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
HEAT
Heating Configuration
HT.TY
X
Type of Heat Installed
Default: 0
0: No Heat
1: Gas
2: Electric
N.HTR
X
Number of Heat Stages
Default: 2
HT.LO
XX
Heating Lockout Temp
Default: 75 F
MRT.H
XXX
Heat Minimum On Time
Default: 120 sec
MOT.H
XXX
Heat Minimum Off Time
Default: 120 sec
HT.PD
X.X
SPT Heat Demand (+) Level
Default: 1.0
∆
F
HT.ND
X.X
SPT Heat Demand (–) Level
Default: –1.0
∆
F
H.LAG
X.X
Heat Thermal Lag Factor
Default: 1.0 min
H.INC
XXX
Heat Stage Increase Secs
Default: 450 sec
H.DEC
XXX
Heat Stage Decrease Secs
Default: 300 sec
ECON
Economizer Configuration
EC.EQ
YES/NO
Economizer Equipped Unit
Default: NO
MIN.P
XXX
Economizer Min Position
Default: 30 %
ECL.H
XX
Econ High Temp Lockout
Default: 65 F
ECL.L
XX
Econ Low Temp Lockout
Default: 0° F
FC.EN
YES/NO
Unoccupied Free Cooling
Default: Yes
EN.SW
X
Enthalpy Switch Input
Default: 0
0: No Switch
1: Normal Open
2: Normal Close
PE.EN
YES/NO
Power Exhaust Control
Default: NO
PE1.P
XXX
PE Stage1 Econo Position
Default: 25 %
PE2.P
XXX
PE Stage2 Econo Position
Default: 75 %
IAQ
IAQ Configuration
AQ.MP
XXX
Minimum IAQ Position
Default: 10 %
MIN.P
XXX
Economizer Min Position
Default: 30 %
AQD.L
XXX
AQ Differential Low
Default: 100 PPM
AQD.H
XXXX
AQ Differential High
Default: 700 PPM
I.4M
XXXX
IAQ Sensor Value at 4MA
Default: 0 PPM
I.20M
XXXX
IAQ Sensor Value at 20MA
Default: 2000 PPM
O.4M
XXXX
OAQ Sensor Value at 4MA
Default: 0 PPM
O.20M
XXXX
OAQ Sensor Value at 20MA
Default: 2000 PPM
OAQ.L
XXXX
OAQ Lockout Value
Default: 600 PPM
CCN
CCN Configuration
CCN.A
XXX
CCN Address
Default: 1
Range: 1 to 239
CCN.B
XXX
CCN Bus Number
Default: 0
Range: 1 to 239
BAUD
X
CCN Baud Rate
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
B.TIM
ON/OFF
CCN Time/Date Broadcast
Default: OFF
B.OAT
ON/OFF
CCN OAT Broadcast
Default: OFF
B.GS
ON/OFF
Global Schedule Broadcast
Default: OFF
B.ACK
ON/OFF
CCN Broadcast Ack’R
Default: OFF
ENTER
ENTER
ENTER
ENTER