Carrier 40SMC N Series Скачать руководство пользователя страница 7

7

E N G L I S H

Operating test for 40SMC---N

• Perform the operating test after the units have been installed in

position and the gas leak test has been completed.

• Check all electrical connections  (instructions and wiring diagram).

• Insert the batteries into the remote control and leave it OFF.

• Energise the system, turning the power supply ON.

• Press the 

 and 

 buttons of the infrared remote control and

hold them pressed for more than 5 seconds. The display will be
cleared, the time segments will display the icon (Src = service test).

FOR SYSTEMS 1:1

The system emits an acoustic signal to reply to the message
sending.
The 3 LEDs of the kit start blinking every 2 seconds and the
indoor fan works according to the configuration set by the user.
If this configuration is set on the Auto mode, the fan works at a
high speed.
In case the unit is of the cool only type, the test will restart it in
the cool.
If the unit is of the heat pump type, the system starts in the cool
mode just for the first 3 minutes, then works in the heat mode
for the 2 following minutes or until the coil temperature is higher
than 40°C, and finally goes back to the cool mode until the test
has been completed.

FOR T-KIT or MULTISPLIT SYSTEMS

If just one single indoor unit has received  the test start request,
the test will be started  immediately while the other units are
switched off.
While one unit carries out the test, the second unit receives the
test start message; the test can be started only after the first
unit has completed its own test.

The green and red LEDs blink every 2 seconds while the yellow
LED blinks every 0.5 seconds (0.5 seconds ON and 0.5 seconds
OFF) according to the table below:

5

-

VRF System

4

-

T-KIT System

3

-

MULTI System

2

-

All other configurations

After switching on and off for a while, the yellow LED remains
OFF for 5 seconds before repeating the same sequence.
During the test, the unit works 3 minutes in the cool mode, then
2 minutes in the heat mode and  finally goes back to the cool
mode until the test has been completed.
If during the heat mode the coil temperature is higher than
40°C, the test will switch to the cool mode until it has been
completed.

During the test, the indoor fan works at high speed and the
outdoor fan changes its speed every 30 seconds from high to
low, while the electric heaters are off.

The test could stop for the following reasons:

• If the 

 ON/OFF button is pressed.

• If power supply is out. Once power supply has been

restored, the unit continues to work in the mode which was
active before the power supply interruption (but not in the
test mode).

• 30 minutes after receiving the last test start message.
• If the indoor coil temperature is higher than 60°C.

Once the test has been completed, the unit continues to work in
the mode set before the test start.

Note:
When 30 minutes have elapsed and no buttons have been
pressed, the remote control will automatically exit the test menu
and resume its normal operation.

Operating test for 40SQV

• Perform the operating test after the units have been installed in

position and the gas leak test has been completed.

• Check all electrical connections  (instructions and wiring diagram).

• Insert the batteries into the remote control and leave it OFF.

• Energise the system, turning the power supply ON.

• Press the 

 and 

 buttons of the infrared remote control and

hold them pressed for more than 5 seconds. The display will be
cleared, the time segments will display the icon (Src = service
test).

When test mode is selected, the unit  operates as described below:

• The green  LED and the yellow LED blink every 2 seconds.

• The indoor fan operates at low speed.

• The system works in Cool Mode at fixed compressor frequency

for 3 minutes.

• The system stops for 3 minutes.

• The system  works in Heat Mode with fixed compressor

frequency for 3 minutes or until the indoor coil temperature is
greater than 40°C.

During the cool mode and heat mode check the following
conditions:

1. Difference between indoor ambient temperature and indoor unit

air discharge temperature must be greater than 3°C.

2. Indoor fan must operate at low speed.

3. No fault code must be signalled by the system.

If one of the above conditions is not positive, please check the
correct installation of the system.

• After test has been completed, press button 

 on the remote

control to leave the test menu.

Note:
When 30 minutes have elapsed and no buttons have been
pressed, the remote control will automatically exit the test menu
and resume its normal operation.

My-comfort control

Operating test

Содержание 40SMC N Series

Страница 1: ...rnbedienung seite 15 17 ACONDICIONADORES DE AIRE Instrucciones SISTEMA SPLIT Satellite Mando a distancia de infrarrojos p g 18 20 SPLIT SYSTEMEN Instructies Afstandsbediening KLIMAATREGELAARS Satellit...

Страница 2: ...ponents fig page 1 Componenti del kit fig pag 1 Composants du kit fig page 1 Komponenten des Satzes Abb Seite 1 Componentes del kit fig p g 1 DESCRIPTION DESCRIZIONE DESCRIPTION BESCHREIBUNG DESCRIPCI...

Страница 3: ...3 5 40SMC N 40SQV 15 m 7 6 15 m max 30 m max 15 m max 15 m max...

Страница 4: ...4 9 40SMC N 40SQV 8 10 11...

Страница 5: ...5 40SMC N 40SQV 12...

Страница 6: ...e and buttons of the infrared remote control and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item CH remote addr...

Страница 7: ...completed During the test the indoor fan works at high speed and the outdoor fan changes its speed every 30 seconds from high to low while the electric heaters are off The test could stop for the foll...

Страница 8: ...ss unit zone not valid Yes 13 Not used Yes Fault code for 40SQV The inside unit can detect any system fault and stop it at once The failure is recoverable based on the table VI below When a diagnostic...

Страница 9: ...apparir senza icone il segmento della temperatura mostrer la prima voce di configurazione CH indirizzo remoto e il segmento dell orario mostrer il valore predefinito di questa configurazione Ab contr...

Страница 10: ...alta velocit il ventilatore esterno cambier la sua velocit ogni 30 secondi passando dall alta alla bassa e le resistenze elettriche saranno spente Ognuna delle successive azioni avr l effetto di term...

Страница 11: ...re il malfunzionamento del sistema arrestandolo immediatamente La causa del guasto pu essere individuata consultando la tabella VI riportata qui sotto Con la diagnostica attiva i led verde P e giallo...

Страница 12: ...ches et de la t l commande infrarouge et les maintenir enfonc es pendant plus de 5 secondes L affichage est remis z ro les segments de temp rature affichent le premier l ment de configuration CH adres...

Страница 13: ...marche haute vitesse le ventilateur ext rieur change sa vitesse toutes les 30 secondes en passant de la haute la basse vitesse et les r sistances lectriques restent teintes Chacune des op rations suiv...

Страница 14: ...utilis Oui Code de d faut pour 40SQV L unit int rieure d tecte le dysfonctionnement du syst me en l arr tant tout de suite La cause de la panne peut tre identifi e en consultant le tableau VI ci apr...

Страница 15: ...ese ausgeschaltet lassen Die Tasten und der Fernbedienung dr cken und 5 Sekunden lang gedr ckt halten Die Anzeige wird gel scht die Temperatursegmente zeigen den Vorgabewert dieses Konfigurationposten...

Страница 16: ...le 30 Sekunden von hoher zu niedriger Geschwindigkeit die elektrische Widerst nde sind ausgeschaltet In allen folgenden F lle wird der Test beendet Taste ON OFF wird gedr ckt Stromversorgung f llt aus...

Страница 17: ...sofort zu stoppen Die St rungsursache kann aus der hier unten angef hrten Tabelle VI gelesen werden Ist die Diagnostik aktiv blinken die gr ne Led P und die gelbe Led R alle 0 5 Sekunden und zeigen ei...

Страница 18: ...rrojos Se borrar la pantalla y los segmentos de tiempo mostrar n el primer elemento de la configuraci n CH direcci n remota y los segmentos de temperatura mostrar n el valor por defecto de este primer...

Страница 19: ...r interno girar a la alta velocidad el ventilador externocambiar su velocidad cada 30 segundos pasando de la alta a la baja y las resistencias el ctricas estar n apagadas Cada una de las siguientes ac...

Страница 20: ...to y Mantenimiento prestando especial atenci n a los principales modos de funcionamiento de la unidad como se citan a continuaci n Como encender y apagar la unidad Funciones del control remoto Dejar a...

Страница 21: ...atterijen in de afstandbediening maar laat hem UIT Houd de toetsen en van de afstandbediening gelijktijdig langer dan 5 seconden ingedrukt In de display wordt het eerste configuratie item afgebeeld CH...

Страница 22: ...ole draait de binnenventilator op hoge snelheid de buitenventilator wijzigt zijn snelheid iedere 30 seconden met overgang van de hoge naar de lage snelheid terwijl de elektrische weerstanden uitgescha...

Страница 23: ...RLANDS Foutcode voor 40SQV De binnen unit is in staat de storing van het systeem waar te nemen en het onmiddellijk af te zetten De oorzaak van het defect kan met behulp van de hieronder gegeven tabel...

Страница 24: ...AC II 30 12345 1 J rc HP AC HR CR 6 II 7 38 A A I A CH b B I B Ab J X tU C C 0 F Z C rc HPQ ACQ J HR 17 32 17 C 32 C C C 63 90 63 F 90 F C Z CR 17 32 17 C 32 C C C 63 90 63 F 90 F C Z CL 12 12 12 AM Q...

Страница 25: ...C N OFF 5 0 Src 1 1 3 2 J J Q Q 3 2 40 C Q MULTISPLIT J LED 2 0 5 0 5 5 Q VRF 4 Q CD 3 Q MULTI 2 5 3 2 J 40 C C 30 C ON OFF I J 30 0 60 C 30 6 40SQV OFF 5 0 Src P R 2 C 3 3 0 3 40 C Q 1 3 C 2 3 J Q 30...

Страница 26: ...40SMC N 6 8 6 2 J 3 J 4 J 5 I 6 J 7 G 8 9 G 4 10 l EEprom 11 I 12 I 13 I 6 40SQV VI P R 0 5 R P 2 Q 4 C 12 2 0 5 4 Q 10 R 6 VI 6 40SQV 6 2 X 3 X 4 X 10 X EEProm 12 X I X 14 J CDU 15 X 18 X G Tr 20 Q 2...

Страница 27: ...remoto por infravermelhos e mantenham nos pressionados durante mais 5 segundos O visor ficar limpo os segmentos do tempo apresentar o o primeiro item da configura o CH endere o remoto e os segmentos d...

Страница 28: ...o virar em alta velocidade o ventilador externo mudar a sua velocidade a cada 30 segundos passando de alta a baixa e as resist ncias el ctricas ser o desligadas Cada uma das ac es seguintes ter o efei...

Страница 29: ...amente A causa da avaria pode ser identificada consultando a tabela VI reproduzida abaixo Com o diagn stico ativo os leds verde P e amarelo R iniciam a lampejar em intervalos de 0 5 segundos indicando...

Страница 30: ...ngd OFF Tryck ned och knapparna p den infrar da fj rrkontrollen och h ll dem nedtryckta l ngre n 5 sekunder Displayen rensas i temperaturf lten visas den f rsta konfigurationsfunktionen CH extern adre...

Страница 31: ...en externa ventilatorn byter hastighet vart 30 sekund medan den byter fr n h gt till l gt l ge och de elektriska motst nden r avst ngda Var och en av f ljande g rningar avslutar testet Tryck av ON OFF...

Страница 32: ...Ja 13 Ej anv nd Ja Felkoder 40SQV Inomhusenheten r i st nd att k nna av felfunktion p systemet och stoppa systemet omedelbart Orsaken till felet kan fastst llas med hj lp av tabellen VI nedan Med akt...

Страница 33: ...t kaukos timeen ja j t se OFF tilaan Paina ja pid painettuna ja painikkeet infrapunakaukos timess yli 5 sekuntia N ytt on oltava tyhj l mp tilalohko n ytt ensimm isen ohjelmointiosan CH poista osoite...

Страница 34: ...en tuuletin toimii nopealla nopeudella ja ulkoinen tuuletin vaihtaa nopeuttaan joka 30 sekunti siirtyen nopeasta hitaaseen nopeuteen ja s hk vastukset sammutetaan Testi p ttyy seuraavien toimenpiteide...

Страница 35: ...k voi keskeytt j rjestelm n toimintah iri n pys ytt m ll j rjestelm n v litt m sti Vian syy voidaan selvitt alla olevan taulukon VI avulla Vianetsinn n ollessa aktiivinen vihre ledi P ja keltainen led...

Страница 36: ...uit peut n cessiter des modifications ou changements sans pr avis nderungen im Zuge der technischen Weiterentwicklung vorbehalten El fabricante se reserva el derecho de cambiar algunas especificacione...

Отзывы: