NOTE:
Where local codes require thermostat wiring be routed
through conduit or raceways, splices can be made inside the fan
coil unit. All wiring must be NEC Class l and must be separated
from incoming power leads.
A factory-authorized disconnect kit is available for installation of
0- through 10-kw applications. When electric heat packages with
circuit breakers are installed, the circuit breaker can be used as a
disconnect. Transformer is factory wired for 230-v operation. For
208-v applications, disconnect black wire from 230-v terminal on
transformer and connect it to 208-v terminal. (See Fig. 13.)
The secondary circuit of transformer is protected by a 5-amp fuse
mounted on printed-circuit board.
IMPORTANT:
Do not use outdoor thermostat with Intelligent
Heat Staging.
COMFORT OPTIONS-- SUPER COMFORT HEAT AND
SUPER DEHUMIDIFY
Super Comfort Heat and Super Dehumidify options are possible
when the 40FKA Fan Coil is installed with an outdoor temperature
sensor (Super Comfort Heat only) and the factory supplied
Thermidistat™ Control or Comfort Zone II.
Complete the system low-voltage wiring as shown in Fig. 9, 10,
11, or 12.
Fig. 9—40FKA Fan Coil Wiring with 1-Speed Air
Conditioner
A98232
O/W2
Y1/W2
W/W1
G
R
W2
Y1
INDOOR CONTROL
40FKA
FAN COIL
1-SPEED
AIR CONDITIONER
W1
G
C
Y
C
DHUM
HUM
B
S1
S2
Y/Y2
R
O
C
DH
HEAT STAGE 2
N/A
HEAT STAGE 1
COOL STAGE 1
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
N/A
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
REMOVE J2 JUMPER
FOR HEAT STAGING
REMOVE
J1 JUMPER
FOR
DEHUMIDIFY
MODES
Fig. 10—40FKA Fan Coil Wiring with 2-Speed Air
Conditioner
A98233
O/W2
W/W1
Y1/W2
G
R
W2
W1
INDOOR CONTROL
40FKA
FAN COIL
2-SPEED
AIR CONDITIONER
Y1
G
C
Y2
R
Y1
C
DHUM
HUM
B
S1
S2
Y/Y2
R
O
C
DH
HEAT STAGE 2
HEAT STAGE 1
COOL STAGE 1
COOL STAGE 2
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
N/A
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
REMOVE J2 JUMPER
FOR HEAT STAGING
REMOVE
J1 JUMPER FOR
DEHUMIDIFY
MODES
Fig. 11—40FKA Fan Coil Wiring with 1-Speed Heat
Pump
A98234
O/W2
W/W1
Y1/W2
G
R
O
W2
INDOOR CONTROL
40FKA
FAN COIL
1-SPEED
HEAT PUMP
W1
G
C
Y
R
W2
O
C
DHUM
HUM
B
S1
S2
Y/Y2
R
Y1
C
DH
HEAT STAGE 3
HEAT STAGE 2
HEAT/COOL
STAGE 1
RVS COOLING
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
RVS HEATING
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
REMOVE J2 JUMPER
FOR HEAT STAGING
REMOVE
J1 JUMPER FOR
DEHUMIDIFY
MODES
Fig. 12—40FKA Fan Coil Wiring with 2-Speed
Puron Heat Pump
A02005
O/W2
W/W1
Y1/W2
G
R
O
Y1
INDOOR CONTROL
FAN COIL
2-SPEED
HEAT PUMP
W1
G
W2
C
Y2
R
W1
Y1
O
C
DHUM
HUM
B
S1
S2
Y/Y2
R
C
DH
HEAT/COOL
STAGE 1
HEAT STAGE 3
HEAT/COOL
STAGE 2
RVS COOLING
FAN
24 VAC HOT
24 VAC COMM
DEHUMIDIFY
HUMIDIFY
RVS HEATING
OUTDOOR
SENSOR
CONNECTION
Y/Y2
HUMIDIFIER
(24 VAC)
OUTDOOR
SENSOR
REMOVE J2
JUMPER FOR
HEAT STAGING
REMOVE J1 FOR
DEHUMIDIFY
MODES
7