Carrier 40FKA Скачать руководство пользователя страница 13

3. SYSTEM TYPE - Select system type HP-COMFORT (for

heat pump system) or AC (for air conditioner system).

4. AC/HP CFM ADJUST - Select LO.

5. ON/OFF DELAY - Select ENH profile.

6. CONTINUOUS FAN - Select desired fan speed when ther-

mostat is set to continuous fan.

7. If the fan coil is installed with Intelligent Heat Staging capable

electric heaters, remove jumper J2. (See Fig. 17.)

NOTE:

If configuring to run warmer heating, do not remove

jumper J2 when using 5-, 8-, or 10-kw heaters.

8. Remove jumper J1 to activate dehumidify modes.

9. Wire low voltage connections as shown in Fig. 9, 10, 11, or

12.

10. Configure Thermidistat (or other Super Dehumidify/Super

Comfort Heat capable indoor control) following its installation
instructions for Super Dehumidify and Super Comfort Heat
operation.

This configuration provides the following comfort enhancements:

a. A 30 second blower on delay with 150 seconds at 70

percent airflow to allow the indoor coil to warm up or cool
down before the blower is asked to deliver 100 percent
airflow reducing the cold blow sensation at start up in
heating and allowing the indoor coil to more quickly reach
wet coil operating conditions in cooling.

b. No blower off delay eliminates cold blow which may be

associated with running the blower after shut down of the
compressor and avoids re-evaporation of condensed mois-
ture after cooling/dehumidifying operation.

c. Lower airflow while the compressor is running to reduce

draft effects and increase heating air temperature and
improved humidity control during cooling operation.

d. Intelligent Staging of the electric heater elements to more

closely match heating load requirements and provide more
consistent heating air temperatures.

Step 9—Accessory Installation

ACCESSORY ELECTRIC HEATERS

Electric heaters may be installed with the 40FKA Fan Coil per
instructions supplied with electric heater package. See unit rating
plate for factory-approved electric heater kits.

NOTE:

Units installed without electric heat should have a field-

supplied sheet metal block-off plate covering the heater opening.
This reduces air leakage and formation of exterior condensation.

AUXILIARY TERMINALS

The AUX and HUM terminals on the Easy Select Board are tied
directly to the G terminal, and provide a 24-vac signal whenever
the G terminal is energized. (See Fig. 17 and 19.) During Perfect
Heat Plus/Super Comfort Heat and Superdehumidify modes, the G
signal is not present and the auxiliary terminals are not energized.
If the installation includes the use of one of these operating modes,
do not use these terminals to control accessories. See Electronic
Air Cleaner and Humidifier sections for further information.

ELECTRONIC AIR CLEANER CONNECTIONS

The AUX1 and AUX2 terminals are not always energized during
blower operation, as described above. When using an electronic air
cleaner with the 40FKA Fan Coil, use Airflow Sensor Part No.
KEAAC0101AAA. The airflow sensor turns on electronic air
cleaner when the fan coil blower is operating.

HUMIDIFIER CONNECTIONS

The HUM1 and HUM2 terminals are not always energized during
blower operation, as described under Auxiliary Terminals Section.

To ensure humidifier will operate properly during Super Comfort
Heat mode, use HUM output of Thermidistat Control or Comfort
Zone II to control humidifier operation. Alternatively, the 24-vac
signal can be sourced from the W and C terminal block connec-
tions when electric heaters are used as the primary heating source,
or if another humidistat is desired to control the humidifier. (See
Fig. 9, 10, 11, and 12.)

Step 10—40FKA Fan Coil Sequence Of Operation

The 40FKA will supply airflow in a range which is more than
twice the range of a standard fan coil. It is designed to provide
nominal cooling capacities at a 50°F evaporator temperature and
the required airflow which enables it to match with 4 air condi-
tioner or heat pump system sizes. Table 6 outlines the CFM range
for the different 40FKA Fan Coil sizes.

CONTINUOUS FAN

Thermostat closes circuit R to G.

The blower runs at continuous fan airflow.

COOLING MODE - SINGLE SPEED OR 2-SPEED HIGH

If indoor temperature is above temperature set point and
humidity is below humidity set point, thermostat closes circuits
R to G, R to Y/Y2 and R to O.
The fan coil delivers single speed cooling airflow.

Thermostat closes circuits R to G, R to Y1, R to Y2 and R to
O.
The fan coil delivers 2-speed high cooling airflow.

COOLING MODE - 2-SPEED LOW

Thermostat closes circuits R to G, R to Y1 and R to O.
The fan coil delivers 2?speed low cooling airflow.

COOLING MODE - DEHUMIDIFICATION

If indoor temperature is above temperature set point and
humidity is above humidity set point, thermostat or Thermidis-
tat™ closes circuits R to G, R to O, and R to Y/Y2, and
humidistat or Thermidistat opens R to DH.

The fan coil delivers airflow which is approximately 80 percent
of the nominal cooling airflow to increase the latent capacity of
the system.

COOLING MODE - SUPERDEHUMIDIFY OPERATION

NOTE:

The indoor control used, such as Thermidistat, must be

capable of providing Super Dehumidify operation mode and
control must be configured as outlined in its installation instruc-
tions. Consult indoor control literature to determine if control is
capable of providing Super Dehumidify inputs and for configura-
tion instructions.

If the indoor temperature is below the temperature set point and the
humidity is above the humidity set point, the Thermidistat closes
circuit R to O, opens circuits R to DH and R to G, and cycles
circuit R to Y/Y2 (for single speed system R to Y1, or R to Y1 and
Y/Y2 for 2-speed system).

The ICM2 motor reads the G signal to the fan coil while the heat
pump is operating, (circuit R to Y/Y2 for single speed system, R
to Y1 or R to Y1 and Y/Y2 for 2-speed system), closed (24 vac).
If circuit R to G is closed (24 vac), the motor will deliver airflow
at the full cooling or cooling plus dehumidify mode requested

Table 6—CFM Range for 40FKA Units

FAN COIL SIZE

SYSTEM SIZES

CFM RANGE

40FKANF002

018, 024, 030, 036

450-1275

40FKANF003

024, 030, 036, 042

525-1475

40FKANF005

030 ,036, 042, 048

550-1700

40FKANB006

036, 042, 048, 060

550-2150

13

Содержание 40FKA

Страница 1: ...sult local building codes and National Electrical Code NEC for special require ments Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most seriou...

Страница 2: ...on of a secondary drain pan under entire unit to avoid damage to ceiling is recommended 40FKA Fan Coils can be installed for upflow and horizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications See Fig 5 Units may be converted for downflow applications using factory authorized accessory kit NOTE To ensure pro...

Страница 3: ...support rail on left side of unit and reinstall on coil support rail on right side of unit 6 Convert air seal assembly for horizontal right a Remove air seal assembly from coil by removing 4 screws See Fig 6 b Remove air splitter B from coil seal assembly by remov ing 3 screws See Fig 6 factory shipped inset c Remove filler plate A and install air splitter B in place of filler plate d Install fill...

Страница 4: ... panels 3 Recommended method of securing for typical applications a If fan coil is away from wall attach pipe strap to top of fan coil using No 10 self tapping screws Angle strap down Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRAPS LOW VOLT ENTRY OPTIONS POWER ENTRY OPTIONS SECONDARY DRAIN 002 005 21 IN 006 24 IN FRONT SERVICE CLEARANCE FULL ...

Страница 5: ...nconditioned space must be insulated and covered with vapor barrier DUCTWORK ACOUSTICAL TREATMENT Metal duct systems that do not have a 90 elbow and 10 ft of main duct to first branch takeoff may require internal acoustical insula tion lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous ...

Страница 6: ...rating plate Be sure that electrical service provided by the utility is sufficient to handle the additional load imposed by this equipment See unit wiring label for proper field high and low voltage wiring Make all electrical connections in accordance with NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field su...

Страница 7: ...HEAT STAGE 1 COOL STAGE 1 FAN 24 VAC HOT 24 VAC COMM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 40FKA Fan Coil Wiring with 2 Speed Air Conditioner A98233 O W2 W W1 Y1 W2 G R W2 W1 INDOOR CONTROL 40FKA FAN COIL 2 SPEED AIR CONDITIONER Y1 G C Y2 R Y1 C DHUM HUM B S1 S2 Y Y2 R O...

Страница 8: ...o prevent damage to thermostatic expansion valve remove sensor bulb from vapor tube while brazing vapor connections Units have sweat suction and liquid tube connections Make suction tube connection first Units have sweat suction and liquid tube connections Make suction tube connection first 1 Cut tubing to correct length 2 Insert tube into sweat connection on unit until it bottoms 3 Braze with Sil...

Страница 9: ...of heaters for which airflow also marked is approved For increased comfort select the narrowest kw range matching the heater size for example 0 10 for 10 kw heater This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation See Table 4 and 5 for airflow delivery and minimum CFM Note that airflow marked is the ai...

Страница 10: ...peed factory setting 50 percent cooling mode airflow 2 MED speed move connector to MED 65 percent cooling mode airflow 3 HI speed move connector of HI 100 percent cooling mode airflow See Fig 19 F as indicated LOW VOLTAGE CIRCUIT FUSING AND REFERENCE The low voltage circuit is fused by a board mounted 5 amp automotive fuse placed in series with the transformer SEC2 and the R circuit The C circuit ...

Страница 11: ...00 1470 880 1175 680 910 545 725 440 570 875 525 680 1050 610 795 1225 700 910 1400 006 036 042 048 060 1050 1225 1400 1750 840 980 1120 1400 1100 1470 1835 880 1175 1470 745 995 1240 595 795 995 525 745 1050 610 870 1225 700 995 1400 875 1240 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI ...

Страница 12: ...HEATER KW RANGE 0 10 0 15 0 20 0 30 LO NOM HI LO NOM HI LO NOM HI LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 1500 1500 1500 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1665 1500 1500 1665 006 36 000 1100 1100 1250 1350 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 ...

Страница 13: ...e fan coil blower is operating HUMIDIFIER CONNECTIONS The HUM1 and HUM2 terminals are not always energized during blower operation as described under Auxiliary Terminals Section To ensure humidifier will operate properly during Super Comfort Heat mode use HUM output of Thermidistat Control or Comfort Zone II to control humidifier operation Alternatively the 24 vac signal can be sourced from the W ...

Страница 14: ... is defective if it will not start Go through the steps described below before replacing control module Easy Select Board or entire motor The control module is available as a replacement part IF MOTOR TURNS SLOWLY 1 Replace panel Motor may appear to run slowly if access panel is removed 2 It is normal operation to run noticeably slower if G terminal is not energized in cooling or heat pump modes I...

Страница 15: ... 20 875 0 10 725 0 90 30 90 0 0 0 5 625 TM J2 JUMPER PULL FOR HEAT STAGING 12 PIN CONNECTOR PL 1 PIN 1 PIN 12 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 16 PIN PLUG DEHUMIDIFICATION INPUT 24 VAC HOT AUXILARY HEAT STAGE 1 AUXILIARY HEAT STAGE 2 LOW SPEED COMPRESSOR SINGLE OR HI SPEED COMPRESSOR FAN REVERSING VALVE COMMON J1 JUMPER PULL FOR DEHUMIDIFICATION CONTROL LOW VOLTAGE SCREW TERMINALS Table 7 Wi...

Страница 16: ... for maintenance procedures As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User Manual furnished in outdoor unit the installing technician should explain system operation to the con sumer with particular emphasis on indoor fan coil operation sounds and filter maintenance Fig 19 40FKA Printe...

Отзывы: