4. If voltage is present, the wiring harness is bad; if not, the Easy

Select Board is bad.

VERIFY MOTOR WINDING SECTION:

Before proceeding with module replacement, check the following
to ensure motor winding section is functional. With control module
removed and unplugged from winding section:

1. The resistance between any 2 motor leads should be similar.

2. The resistance between any motor lead and the unpainted

motor end plate should be greater than 100K ohms.

If motor winding section fails one of these tests, it is defective and
must be replaced.

START-UP PROCEDURES

Refer to outdoor unit Installation Instructions for system start-up
instructions and refrigerant charging method details.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible
equipment failure, it is essential that periodic maintenance be
performed on this equipment. The only required maintenance that
may be performed by the consumer is filter maintenance.

Disconnect all power to unit before servicing field wires or
removing control package. The disconnect (when used) on
access panel does not disconnect power to the line side of
disconnect, but does allow safe service to all other parts of
unit. If unit does not have a disconnect, disregard the
foregoing. Instead, make sure that a disconnecting means is
within sight from, and is readily accessible from, the unit.
Disconnect all electrical power to unit before performing any
maintenance or service on it. A failure to follow this warning
can cause electrical shock, fire, personal injury, or death.

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect and clean or replace air filter each month or as

required.

2. Inspect cooling coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean as necessary. An inspec-
tion port is provided on all A-coil delta plates. Remove plastic
plug to inspect.

3. Inspect blower motor and wheel for cleanliness each heating

and cooling season. Clean as necessary.

4. Inspect electrical connections for tightness and controls for

proper operation each heating and cooling season. Service as
necessary.

Consult Fan Coil Service Manual available from equipment
distributor for maintenance procedures.

As with any mechanical equipment, personal injury can result
from sharp metal edges, etc, therefore, care should be taken
when removing parts.

Using the Owner’s/User Manual furnished in outdoor unit, the
installing technician should explain system operation to the con-
sumer with particular emphasis on indoor fan coil operation
sounds and filter maintenance.

Fig. 19—40FKA Printed CIrcuit Board with Comfort Heat Pump Set-up Guide

A98290

EASY SELECT

D

H

R

W

1

W

2

Y

1

Y/Y

2

G

O

C

HEATER/MOTOR

CEBD430226-01B   CESS430226-01B

AUX HEAT KW/CFM

0-30

1075

SEC1

SEC2

J1

J2

AC/HP SIZE

036

030

024

018

AC

HP-COMFORT

HP-EFF

NOM

HI

ENH

LO

SYSTEM TYPE

AC/HP CFM ADJUST

ON/OFF DELAY

CONTINUOUS FAN

MED

HI

YEL

LO

AUX1

HUM1

AUX2

24VAC

GRY

HUM2

YEL

WHT

BLK

ORN

BLU

VIO

0-20

875

0-10

725

0

90

30
90

0
0

0-5

625

TM

LOW VOLTAGE TERMINAL BLOCK

MOLEX 12-PIN CONNECTOR

A

B

C

D

E

F

QUICK REFERENCE GUIDE

COMFORT HEAT PUMP SET-UP INSTRUCTIONS

     A.  AUX HEAT - Set for heater size (Ex: 0-10 for 10 kw)
     B.  AC/HP SIZE - Set for size of outdoor unit
     C.  SYSTEM TYPE - Select "HP COMFORT"
     D.  AC/HP CFM ADJUST - Select "LO"
     E.  ON/OFF DELAY - Select "ENH"
     F.  CONTINUOUS FAN - Leave on "LO"
2.  Install heater with Intelligent Heat Staging, and remove

     Jumper J2, except when using 5-, 8-, or 10-kw heater.
3.  Remove Jumper J1 to activate all dehumidify modes.
4.  Complete wiring and install outdoor temperature sensor according 

     to Installation Instructions.

1.  Configuration Taps 

     (See Installation Instructions, for detailed description.)

     •  Option 5 (Variable Speed Motors) - set to ON
     •  Option 7 (Super Dehumidify) - set to ON
     •  Option 9 (Intelligent Heat) - set to ON if installing with
         a single speed heat pump 
     •  Option 12 (Heaters during Defrost) - setting "2" is
         suggested for all heaters
     •  Option 16 (Super Comfort Heat) - set to ON for R-22
         systems.  For Puron applications, set to OFF.

2.  Thermidistat Control Configurations

     (See Thermidistat™ Control Installation Instructions for

     detailed description.)

1.  Set "DIP Switches" - Set the dip switches appropriate for

     the specific system being installed.

EASY SELECT BOARD

THERMIDISTAT™ CONTROL SETTINGS

Copyright 2002 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231

40fk7si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

3d 2e

PC 101

Catalog No. 534–017

Printed in U.S.A.

Form 40FK-7SI

Pg 16

3-02

Replaces: 40FK-5SI

Содержание 40FKA

Страница 1: ...sult local building codes and National Electrical Code NEC for special require ments Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most seriou...

Страница 2: ...on of a secondary drain pan under entire unit to avoid damage to ceiling is recommended 40FKA Fan Coils can be installed for upflow and horizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications See Fig 5 Units may be converted for downflow applications using factory authorized accessory kit NOTE To ensure pro...

Страница 3: ...support rail on left side of unit and reinstall on coil support rail on right side of unit 6 Convert air seal assembly for horizontal right a Remove air seal assembly from coil by removing 4 screws See Fig 6 b Remove air splitter B from coil seal assembly by remov ing 3 screws See Fig 6 factory shipped inset c Remove filler plate A and install air splitter B in place of filler plate d Install fill...

Страница 4: ... panels 3 Recommended method of securing for typical applications a If fan coil is away from wall attach pipe strap to top of fan coil using No 10 self tapping screws Angle strap down Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRAPS LOW VOLT ENTRY OPTIONS POWER ENTRY OPTIONS SECONDARY DRAIN 002 005 21 IN 006 24 IN FRONT SERVICE CLEARANCE FULL ...

Страница 5: ...nconditioned space must be insulated and covered with vapor barrier DUCTWORK ACOUSTICAL TREATMENT Metal duct systems that do not have a 90 elbow and 10 ft of main duct to first branch takeoff may require internal acoustical insula tion lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous ...

Страница 6: ...rating plate Be sure that electrical service provided by the utility is sufficient to handle the additional load imposed by this equipment See unit wiring label for proper field high and low voltage wiring Make all electrical connections in accordance with NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field su...

Страница 7: ...HEAT STAGE 1 COOL STAGE 1 FAN 24 VAC HOT 24 VAC COMM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 40FKA Fan Coil Wiring with 2 Speed Air Conditioner A98233 O W2 W W1 Y1 W2 G R W2 W1 INDOOR CONTROL 40FKA FAN COIL 2 SPEED AIR CONDITIONER Y1 G C Y2 R Y1 C DHUM HUM B S1 S2 Y Y2 R O...

Страница 8: ...o prevent damage to thermostatic expansion valve remove sensor bulb from vapor tube while brazing vapor connections Units have sweat suction and liquid tube connections Make suction tube connection first Units have sweat suction and liquid tube connections Make suction tube connection first 1 Cut tubing to correct length 2 Insert tube into sweat connection on unit until it bottoms 3 Braze with Sil...

Страница 9: ...of heaters for which airflow also marked is approved For increased comfort select the narrowest kw range matching the heater size for example 0 10 for 10 kw heater This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation See Table 4 and 5 for airflow delivery and minimum CFM Note that airflow marked is the ai...

Страница 10: ...peed factory setting 50 percent cooling mode airflow 2 MED speed move connector to MED 65 percent cooling mode airflow 3 HI speed move connector of HI 100 percent cooling mode airflow See Fig 19 F as indicated LOW VOLTAGE CIRCUIT FUSING AND REFERENCE The low voltage circuit is fused by a board mounted 5 amp automotive fuse placed in series with the transformer SEC2 and the R circuit The C circuit ...

Страница 11: ...00 1470 880 1175 680 910 545 725 440 570 875 525 680 1050 610 795 1225 700 910 1400 006 036 042 048 060 1050 1225 1400 1750 840 980 1120 1400 1100 1470 1835 880 1175 1470 745 995 1240 595 795 995 525 745 1050 610 870 1225 700 995 1400 875 1240 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI ...

Страница 12: ...HEATER KW RANGE 0 10 0 15 0 20 0 30 LO NOM HI LO NOM HI LO NOM HI LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 1500 1500 1500 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1665 1500 1500 1665 006 36 000 1100 1100 1250 1350 1350 1350 42 000 1140 1270 1460 1350 1350 1460 1525 1525 1525 48 000 ...

Страница 13: ...e fan coil blower is operating HUMIDIFIER CONNECTIONS The HUM1 and HUM2 terminals are not always energized during blower operation as described under Auxiliary Terminals Section To ensure humidifier will operate properly during Super Comfort Heat mode use HUM output of Thermidistat Control or Comfort Zone II to control humidifier operation Alternatively the 24 vac signal can be sourced from the W ...

Страница 14: ... is defective if it will not start Go through the steps described below before replacing control module Easy Select Board or entire motor The control module is available as a replacement part IF MOTOR TURNS SLOWLY 1 Replace panel Motor may appear to run slowly if access panel is removed 2 It is normal operation to run noticeably slower if G terminal is not energized in cooling or heat pump modes I...

Страница 15: ... 20 875 0 10 725 0 90 30 90 0 0 0 5 625 TM J2 JUMPER PULL FOR HEAT STAGING 12 PIN CONNECTOR PL 1 PIN 1 PIN 12 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 16 PIN PLUG DEHUMIDIFICATION INPUT 24 VAC HOT AUXILARY HEAT STAGE 1 AUXILIARY HEAT STAGE 2 LOW SPEED COMPRESSOR SINGLE OR HI SPEED COMPRESSOR FAN REVERSING VALVE COMMON J1 JUMPER PULL FOR DEHUMIDIFICATION CONTROL LOW VOLTAGE SCREW TERMINALS Table 7 Wi...

Страница 16: ... for maintenance procedures As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User Manual furnished in outdoor unit the installing technician should explain system operation to the con sumer with particular emphasis on indoor fan coil operation sounds and filter maintenance Fig 19 40FKA Printe...

Отзывы: