1. AUX HEAT KW/CFM - Select the heater range for the size
electric heater installed.
2. AC/HP SIZE - Select system size installed.
3. SYSTEM TYPE - Select system type HP-EFF.
4. AC/HP CFM ADJUST - Select NOM.
5. ON/OFF DELAY - Select 0/90 profile.
6. CONTINUOUS FAN - Select desired fan speed when ther-
mostat is set to continuous fan.
COMFORT OPTIONS -SUPER COMFORT HEAT AND SUPER
DEHUMIDIFY MODES
Super Comfort Heat and Super Dehumidify options are possible
when the 40FKA Fan Coil is installed with an outdoor temperature
sensor and the factory supplied Thermidistat™ Control (Super
Comfort Heat only; Super Dehumidify does not require an outdoor
temperature sensor). The following fan coil configuration is
recommended for maximum heating and cooling/dehumidifying
comfort.
NOTE:
The 40FKA Fan Coil provides better than average hu-
midity control and heated air temperature. This configuration will
improve the comfort provided by the heat pump system if more
Table 2—40FKA Fan Coil Airflow Delivery (CFM) in Cooling Mode
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
OPERATING MODE
FAN ONLY
LO/MED/HI
Single-Speed
Application
Two-Speed
Application
High Speed
Low Speed
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
Nominal
A/C
Cooling
A/C
Cooling
Dehumidity
002
018
024
030
036
525
700
875
1050
420
560
700
840
—
—
—
1100
—
—
—
880
—
—
—
680
—
—
—
545
350/350/525
350/455/700
440/570/875
525/680/1050
003
024
030
036
042
700
875
1050
1225
560
700
840
980
—
—
1100
—
—
—
880
—
—
—
680
—
—
—
545
—
415/455/700
440/570/875
525/680/1050
610/795/1225
005
030
036
042
048
875
1050
1225
1400
700
840
980
1120
—
1100
—
1470
—
880
—
1175
—
680
—
910
—
545
—
725
440/570/875
525/680/1050
610/795/1225
700/910/1400
006
036
042
048
060
1050
1225
1400
1750
840
980
1120
1400
1100
—
1470
1835
880
—
1175
1470
745
—
995
1240
595
—
795
995
525/745/1050
610/870/1225
700/995/1400
875/1240/1750
NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be ad15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.
Table 3—40FKA Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode
UNIT
SIZE
OUTDOOR
UNIT
CAPACITY
OPERATING MODE
FAN ONLY
LO/MED/HI
Single-Speed
Application
Two-Speed
Application
High Speed
Low Speed
Heat Pump
Comfort
Heat Pump
Efficiency
Heat Pump
Comfort
Heat Pump
Efficiency
Heat Pump
Comfort
Heat Pump
Efficiency
002
018
024
030
036
470
630
785
945
525
700
875
1050
—
—
—
990
—
—
—
1100
—
—
—
615
—
—
—
680
350/350/470
350/410/630
440/510/785
525/615/945
003
024
030
036
042
630
785
945
1100
700
875
1050
1225
—
—
990
—
—
—
1100
—
—
—
615
—
—
—
680
—
415/415/630
440/510/785
525/615/945
610/715/1100
005
030
036
042
048
785
945
1100
1260
875
1050
1225
1400
—
990
—
1320
—
1100
—
1470
—
615
—
820
—
680
—
910
440/510/785
525/615/945
610/715/1100
700/820/1260
006
036
042
048
060
945
1100
1260
1575
1050
1225
1400
1750
990
—
1325
1655
1100
—
1470
1835
670
—
895
1120
745
—
995
1240
525/670/945
610/780/1100
700/895/1260
875/1120/1575
NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be ad15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.