Table 19 — System Commissioning Maintenance Table
AUTO DISABLE TIMER — This variable displays the num-
ber of minutes remaining before the system commissioning
mode will be automatically disabled. System commissioning
mode is automatically disabled after one hour of no activity in
this table. The Auto Disable Timer is reset each time a value is
changed in this table.
Auto Disable
Timer:
Display Range
0 to 60 min
Network Access None
ALL ZONE DAMPERS TO MAX — This variable displays
whether the Linkage Coordinator zone controller has been
directed to set all of its linked zone controllers to their config-
ured Cool Maximum Positions (Damper Service Configuration
Table). If this decision is forced to
Enable
, the Linkage Coordi-
nator zone controller will set all system zone dampers to their
configured Cool Maximum Positions and display the values in
Zone (1-32) Damper Position variables. At this time if any of
the Zone (1-32) Damper Position variables are forced, the new
position will be written to the zone’s Cool Maximum Position
and Heat Maximum Position configuration values and the zone
will be repositioned to this new maximum position.
NOTE: If this zone controller is not the Linkage Coordinator,
enabling this variable will have no effect.
All Zone
Dampers to Max: Display Range
Enable/Disable
Network Access Read/Write
ALL ZONE DAMPERS TO MIN — This variable displays
whether the Linkage Coordinator zone controller has been
directed to set all of its linked zone controllers to their config-
ured Cool Minimum Positions (Damper Service Configuration
Table). If this decision is forced to
Enable
, the Linkage Coordi-
nator zone controller will set all system zone dampers to their
configured Cool Minimum Positions and display the values in
Zone (1-32) Damper Position variables. At this time if any of
the Zone (1-32) Damper Position variables are forced, the new
position will be written to the zone’s Cool Minimum Position
and Heat Minimum Position configuration values and the zone
will be repositioned to this new minimum position.
NOTE: If this zone controller is not the Linkage Coordinator,
enabling this variable will have no effect.
All Zone
Dampers to Min: Display Range
Enable/Disable
Network Access Read/Write
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Commissioning Mode
Disable
Enable/Disable
SCMOD
Auto-Disable Timer
0.0
Min
SCTIME
All Zone Dampers to Max
Disable
Enable/Disable
ZD_MAX
All Zone Dampers to Min
Disable
Enable/Disable
ZD_MIN
Position Single Zone
Disable
Enable/Disable
ZD_SING
Zone 1 Damper Position
0
%OPEN
ZD_POS01
Zone 2 Damper Position
0
%OPEN
ZD_POS02
Zone 3 Damper Position
0
%OPEN
ZD_POS03
Zone 4 Damper Position
0
%OPEN
ZD_POS04
Zone 5 Damper Position
0
%OPEN
ZD_POS05
Zone 6 Damper Position
0
%OPEN
ZD_POS06
Zone 7 Damper Position
0
%OPEN
ZD_POS07
Zone 8 Damper Position
0
%OPEN
ZD_POS08
Zone 9 Damper Position
0
%OPEN
ZD_POS09
Zone 10 Damper Position
0
%OPEN
ZD_POS10
Zone 11 Damper Position
0
%OPEN
ZD_POS11
Zone 12 Damper Position
0
%OPEN
ZD_POS12
Zone 13 Damper Position
0
%OPEN
ZD_POS13
Zone 14 Damper Position
0
%OPEN
ZD_POS14
Zone 15 Damper Position
0
%OPEN
ZD_POS15
Zone 16 Damper Position
0
%OPEN
ZD_POS16
Zone 17 Damper Position
0
%OPEN
ZD_POS17
Zone 18 Damper Position
0
%OPEN
ZD_POS18
Zone 19 Damper Position
0
%OPEN
ZD_POS19
Zone 20 Damper Position
0
%OPEN
ZD_POS20
Zone 21 Damper Position
0
%OPEN
ZD_POS21
Zone 22 Damper Position
0
%OPEN
ZD_POS22
Zone 23 Damper Position
0
%OPEN
ZD_POS23
Zone 24 Damper Position
0
%OPEN
ZD_POS24
Zone 25 Damper Position
0
%OPEN
ZD_POS25
Zone 26 Damper Position
0
%OPEN
ZD_POS26
Zone 27 Damper Position
0
%OPEN
ZD_POS27
Zone 28 Damper Position
0
%OPEN
ZD_POS28
Zone 29 Damper Position
0
%OPEN
ZD_POS29
Zone 30 Damper Position
0
%OPEN
ZD_POS30
Zone 31 Damper Position
0
%OPEN
ZD_POS31
Zone 32 Damper Position
0
%OPEN
ZD_POS32
Bypass Damper Position
0
%OPEN
BDP
Bypass Pressure Sensor
0.00
in H2O
BPSENS
Bypass Pressure Setpoint
0.00
in H2O
BPSETP