45
Table 18 — Time Schedule Maintenance Table
UNOCCUPIED START TIME — This variable displays the
time that the current occupied mode will end (the beginning of
the next unoccupied mode).
Unoccupied Start
Time:
Display Range
00:00 to 24:00
Network Access None
NEXT OCCUPIED DAY — This variable displays the day
when the next occupied period is scheduled to begin. This
point is read in conjunction with the next occupied time to
allow the user to know the next time and day when the next
occupied period will occur.
NOTE: If the current mode is occupied, this point makes refer-
ence to the next occupied period and, in most cases, may not
be the same as the current occupied start time.
Next Occupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
NEXT OCCUPIED TIME — This variable displays the time
of day when the next occupied period will occur. This point is
read in conjunction with the next occupied day to allow the
user to know the next time and day when the zone will become
occupied.
NOTE: If the current mode is occupied, this point makes
reference to the next occupied period and, in most cases,
may not be the same as the current occupied start time.
Next Occupied
Time:
Display Range
00:00 to 24:00
Network Access None
NEXT UNOCCUPIED DAY — This variable displays the
day when the next unoccupied period is scheduled to begin.
This point is read in conjunction with the next unoccupied time
to allow the user to know the next time and day when the zone
will become unoccupied.
NOTE: If the current mode is unoccupied, this point makes
reference to the next unoccupied period and, in most cases,
may not be the same as the current unoccupied start time.
Next Unoccupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
NEXT UNOCCUPIED TIME — This variable displays the
time of day when the next unoccupied period is scheduled
to begin. This point is read in conjunction with the next
unoccupied day to allow the user to know the next time and
day when the zone will become unoccupied.
NOTE: If the current mode is unoccupied, this point makes
reference to the next unoccupied period and, in most cases,
may not be the same as the current unoccupied start time.
Next Unoccupied
Time:
Display Range
00:00 to 24:00
Network Access None
LAST UNOCCUPIED DAY — This variable displays the
last day when the zone changed from occupied to unoccupied
mode. This point is read in conjunction with the last unoccu-
pied time to allow the user to know the last time and day
when the zone became unoccupied.
Last Unoccupied
Day:
Display Range
MON, TUE, WED,
THU, FRI, SAT, SUN
Network Access None
LAST UNOCCUPIED TIME — This variable displays the
last time of day when the zone changed from occupied to unoc-
cupied mode. This point is read in conjunction with the last
unoccupied day to allow the user to know the last time and day
when a zone became unoccupied.
Last Unoccupied
Time:
Display Range
00:00 to 24:00
Network Access None
System Commissioning Maintenance Table —
The System Commissioning Maintenance Table (SYSTCOMM)
displays and permits the setting of all dampers in the linked sys-
tem from the Linkage Coordinator zone controller. The bypass
controller damper position, system pressure and pressure set
point are also displayed and the pressure set point may be altered
directly from this table. See Table 19.
COMMISSIONING MODE — This variable is used to put
the master zone controller into the commissioning mode. Force
this point to enable. The Linkage Coordinator zone controller
will be ready to accept a command to perform the tests and
functions on this screen. The Linkage Coordinator zone con-
troller will go into ZONE_BAL mode.
NOTE: If this zone controller is not the Linkage Coordinator,
enabling this variable will have no effect.
Commissioning
Mode:
Display Range
Disable/Enable
Default Value
Disable
Network Access Read /Write
DESCRIPTION
VALUE
UNITS
NAME
Mode
1
MODE
Current Occupied Period
2
PERIOD
Override in Progress
No
OVERLAST
Override Duration
0
min
OVERDURA
Occupied Start Time
08:00
OCCSTART
Unoccupied Start Time
18:00
UNSTART
Next Occupied Day
Thu
NXTOCCD
Next Occupied Time
00:00
NXTOCCT
Next Unoccupied Day
Wed
NXTUNOD
Next Unoccupied Time
18:00
NXTUNOT
Last Unoccupied Day
PRVUNOD
Last Unoccupied Time
00:00
PRVUNOT