34
AIR SOURCE BUS AND ELEMENT NUMBER — The Air
Source Bus and Element Number configurations define the
address of the air source providing conditioned air to the zones
controlled by the linkage coordinator. If the address is left at
zero, the linkage coordinator will look for a primary air sensor
to determine the equipment mode. If no primary air sensor is
installed, or the sensor fails, the Linkage Coordinator will
default the air source mode to Cooling.
Air Source
Bus Number:
Range
0 to 239
Default Value
0
Air Source
Element Number: Range
0 to 239
Default Value
0
Table 7 — Damper Service Configuration Table
Table 8 — Holiday Configuration Table
→
Table 9 — Linkage Configuration Table
DESCRIPTION
VALUE
UNITS
NAME
Cool Minimum Pos
0
%
CMINPOS
Cool Maximum Pos
100
%
CMAXPOS
Reheat Minimum Pos
0
%
REMINPOS
Heat Minimum Pos
0
%
HMINPOS
Heat Maximum Pos
100
%
HMAXPOS
Ventilation Pos
30
%
VENTPOS
DESCRIPTION
VALUE
UNITS
NAME
Start Month
1
MONTH
Start Day
1
DAY
Duration
0
DURATION
DESCRIPTION
VALUE
UNITS
NAME
Zone Linkage
Linkage Master Zone
No
MZENA
Number of Zones
1
NSYSTZ
Air Source Bus #
0
ASBUSN
Air Source Element #
0
ASELEMN
System Bypass Exists
Yes
SYS_BP
AST Mode Verification
No
AST_CHCK
AST Sensor Location
0
AST_LOC
0 = Airsource
1 = Local PAT
2 = Bypass
CCN-LINKAGE DATA
CCN Variable Name
CCNVAR
CCN Func Config
0
CCNFUNC
0 = None
1 = Average
2 = Low
3 = High
Data Transfer Rate
10
min
DATARATE
CCN Output Point
CCNOUTP
Destination Bus #
0
DESTBUSN
Destination Element #
0
DESTELEN
TEMP SENSOR GROUPING
Sensor Mode
1
BRD_RECV
1 = Local Sensor
2 = Broadcast
3 = Listen
Listen Sensor Config
1
SENSCFG
1 = SPT
2 = SPT & Offset
Broadcasting Element #
1
BRDDEVID
1104