31
→
Table 6 — Terminal Service Configuration Table
DESCRIPTION
VALUE
UNITS
NAME
COOLING
Terminal Type
1
TERMTYPE
1 = Single Duct
2 = Parallel Fan
3 = Series Fan
Primary Inlet Size
Inlet Diameter (Inches)
6.0
RNDSZ
Inlet Area (Sq. In.)
0.0
SQA
Damper PID
Proportional Gain
10.0
KP
Integral Gain
2.5
KI
Derivative Gain
4.0
KD
Starting Value
40.0
%
STARTVAL
CW Rotation
Close
DMPDIR
HEATING
Heat Type
0
HEATTYPE
0 = None
2 = Two Position
3 = Staged Electric
4 = Modulating/CV
5 = Combination
Heating PID
Proportional
10.0
KP
Integral Gain
0.5
KI
Derivative Gain
0.0
KD
Starting Value
80.0
dF
STARTVAL
Ducted Heat
Yes
DUCTHEAT
Maximum Temperature
110
dF
MAXTEMP
# Electric Heat Stages
3
STAGES
Heat On Delay
2
min
HONDEL
Fan Off Delay
2
min
FNOFFD
2-Pos Heat Logic
Normal
HEATYPE
System Call for Heat?
Yes
HEATCALL
Supp. Heat Lockout Temp.
140.0
dF
SHL_TEMP
System Pilot Averaging
0
SENS_AVG
0 = System Pilot only
1 = with one T55
2 = with four T55s
3 = with nine T55s
SPT Sensor Trim
0.0
^F
SPTTRIM
SAT Sensor Trim
0.0
^F
SATTRIM
Local SAT Installed
Yes
LOC_SAT
Remote Contact Config
Close
RMTCFG
1104
Содержание 3V VVT 33ZCVVTZC-01