![Carrier 39T Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/carrier/39t/39t_installation-start-up-and-service-instructions-manual_2562109054.webp)
Table 20 — Direct Expansion Coil Circuiting Data (cont)
LARGE FACE AREA COILS (cont)
39T UNIT SIZE
61
74
92
CIRCUITING TYPE
Half
Full
Double
Half
Full
Double
Half
Full
Double
Airflow (cfm) at 550 fpm
33,446
40,567
50,401
Total Face Area (sq ft)
60.8
73.8
91.6
Tubes in Face (Upper/Lower)
30/32
32/34
40/42
Tube Length (in.)
113
128
3
⁄
4
128
3
⁄
4
No. of Circuits — Total
31
62
124
33
66
132
41
82
164
COIL SECTIONS
U
L
U
L
U
L
U
L
U
L
U
L
U
L
U
L
U
L
4-Row Coil
Circuit Equivalent Length (in.)
85.8
85.8
48.2 48.2
—
96.3
96.3
53.4 53.4
—
96.3
96.3
53.4
53.4
—
Face-Split Coils
No. of TXVs
2
2
2
2
—
2
2
2
2
—
2
2
4
4
—
No. of Circuits/Distributor*
7,8
8
15
16
8
8,9
16
17
—
10
10,11
10
10,11
—
Suction Connections (in. OD)
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
20
20
20
20
—
26
26
19
19
—
21
21
19
19
—
Distributor Nozzle Size†
12
12
17
17
—
20
20
20
20
—
25
25
12
12
—
Row-Split Coils
No. of TXVs
2
2
2
2
—
2
2
2
2
—
4
4
4
4
—
No. of Circuits/Distributor*
7,8
8
15
16
—
8
8,9
16
17
—
5
5,6
10
10,11
—
Suction Connections (in. OD)
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
1
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
3
⁄
8
1
3
⁄
8
—
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
Distributor Tube Length (in.)
26
26
28
28
—
26
26
28
28
—
16
16
19
19
—
Distributor Nozzle Size†
12
12
17
17
—
20
20
20
20
—
12
12
12
12
—
6-Row Coil
Circuit Equivalent Length
129.5 129.5
64
64
—
145.2 145.2 71.9 71.9
—
145.2 145.2 71.9
71.9
—
Face-Split Coils
No. of TXVs
2
2
2
2
—
2
2
2
2
—
2
2
4
4
—
No. of Circuits/Distributor*
7,8
8
15
16
—
8
8,9
16
17
—
10
10,11
10
10,11
—
Suction Connections (in. OD)
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
20
20
20
20
—
26
26
19
19
—
21
21
19
19
—
Distributor Nozzle Size†
12
12
17
17
—
20
20
20
20
—
25
25
12
12
—
Row-Split Coils
No. of TXVs
2
2
2
2
—
2
2
2
2
—
4
4
4
4
—
No. of Circuits/Distributor*
7,8
8
15
16
—
8
8,9
16
17
—
5
5,6
10
10,11
—
Suction Connections (in. OD)
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
1
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
3
⁄
8
1
3
⁄
8
—
7
⁄
8
7
⁄
8
1
3
⁄
8
1
3
⁄
8
—
Distributor Tube Length (in.)
26
26
28
28
—
26
26
28
28
—
16
16
19
19
—
Distributor Nozzle Size†
12
12
17
17
—
20
20
20
20
—
12
12
12
12
—
8-Row Coil
Circuit Equivalent Length
—
85.8 85.8 42.2 42.2
—
96.3 96.3 47.4 47.4
—
96.3
96.3
47.4
47.4
Face-Split Coils
No. of TXVs
—
2
2
4
4
—
2
2
4
4
—
4
4
8
8
No. of Circuits/Distributor*
—
15
16
15
16
—
16
17
16
17
—
10
10,11
10
10,11
Suction Connections (in. OD)
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
Distributor Connections (in. OD)
—
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Distributor Tube Length (in.)
—
20
20
20
20
—
19
19
19
19
—
19
19
13
13
Distributor Nozzle Size†
—
17
17
8
8
—
20
20
10
10
—
12
12
6
6
Row-Split Coils
No. of TXVs
—
2
2
4
4
—
2
2
4
4
—
4
4
8
8
No. of Circuits/Distributor*
—
15
16
15
16
—
16
17
16
17
—
10
10,11
10
10,11
Suction Connections (in. OD)
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
1
5
⁄
8
Distributor Connections (in. OD)
—
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
—
1
3
⁄
8
1
3
⁄
8
1
1
⁄
8
1
1
⁄
8
Distributor Tube Length (in.)
—
28
28
20
20
—
28
28
19
19
—
19
19
13
13
Distributor Nozzle Size†
—
17
17
8
8
—
20
20
10
10
—
12
12
6
6
LEGEND
L
— Lower
TXV — Thermostatic Expansion Valve (Field-Supplied)
U
— Upper
*Where each distributor has the same number of circuits, that number is shown once. When a coil has an uneven
number of circuits per distributor, both values are shown. For example, the upper coil of a half-circuit size 32 large
face area coil has 5 circuits on one distributor and 6 circuits on the other distributor; the lower coil has 6 circuits on
each distributor.
†Factory-supplied distributors have factory-selected nozzle sizes shown. If necessary, replace factory-supplied nozzles
with field-supplied and installed nozzles. Consult Electronic Catalog
AHU Builder™ program for correct nozzle
selection.
54
Содержание 39T
Страница 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Страница 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Страница 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Страница 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Страница 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Страница 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Страница 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Страница 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Страница 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Страница 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Страница 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Страница 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Страница 102: ......
Страница 103: ......