![Carrier 39T Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/carrier/39t/39t_installation-start-up-and-service-instructions-manual_2562109019.webp)
Table 6 — Steam Coil Connection Sizes
FACE
AREA
CONNECTION
39T UNIT SIZE
07
09
11
13
17
21
26
32
39
49
61
74
92
Nozzle Size (in. MPT)
LARGE
Inlet
3
3
3
3
3
3
3
—
—
—
—
—
—
Outlet
2
2
2
2
2
2
2
—
—
—
—
—
—
MEDIUM
Inlet
—
—
—
—
—
—
—
3
3
3
3
3
3
Outlet
—
—
—
—
—
—
—
2
2
2
2
2
2
SMALL
Inlet
2
1
⁄
2
2
1
⁄
2
2
1
⁄
2
2
1
⁄
2
2
1
⁄
2
3
3
3
3
3
3
3
3
Outlet
1
1
⁄
2
1
1
⁄
2
1
1
⁄
2
1
1
⁄
2
1
1
⁄
2
2
2
2
2
2
2
2
2
BYPASS
Inlet
2
1
⁄
2
3
3
3
3
3
3
3
3
3
3
3
3
Outlet
1
1
⁄
2
2
2
2
2
2
2
2
2
2
2
2
2
NOTE: The following sizes have two coils: medium face area — sizes 61-92; bypass face area — size 92.
Table 7 — Operating Charge (Approximate) — Direct Expansion coil
NUMBER
OF
ROWS
FACE
AREA
39T UNIT SIZE
07
09
11
13
17
21
26
32
39
49
61
74
92
Refrigerant R-22 (lb)
4
Large
4
5
5
6
8
11
13
14
19
21
30
38
45
Medium
3
4
5
5
7
9
10
11
12
19
21
30
38
6
Large
5
7
7
9
12
15
19
25
31
39
47
53
66
Medium
4
6
7
8
10
13
15
19
24
31
39
47
53
8
Large
7
8
10
12
15
20
24
35
40
48
60
70
87
Medium
5
7
9
10
13
16
21
30
32
40
48
60
70
Table 8 — Coil Moisture Blowoff Limits (fpm)
FINS
ALUMINUM
COPPER
PER INCH
FINS
FINS
8
550
500
11
550
425
14
550
375
NOTES:
1. See
AHU Builder™
program for specific limitations. Data shown is for
general use in high latent conditions.
2. Coils with phenolic coated fins exhibit the same limitations as copper
fins.
3. Units apply to clean, properly maintained coils.
19
Содержание 39T
Страница 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Страница 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Страница 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Страница 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Страница 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Страница 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Страница 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Страница 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Страница 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Страница 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Страница 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Страница 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Страница 102: ......
Страница 103: ......