ELECTRONIC EXPANSION VALVE (EEV)
The opening of the EEV is based on compressor discharge temperature (T5). If T5 increases, EEV operates the opening to target value
directly. Otherwise, it regulates itself to step-by-step operation.
A210263
Fig. 29 —Cooling Operation
A210264
Fig. 30 —Heating Operation
If the superheat is too high, the software revises T5 so that EEV can quickly adjust to a larger opening. Discharge Superheat Correction
adjusts every two minutes.
T5 (new) = T5 (old) + 18°F
A210265
Fig. 31 —Discharge Superheat Correction