heck if the height difference between indoor unit & outdoor unit and the total length of refrigerant pipe meet 

system requirement.

R

efrigerant piping work follows the indoor unit and outdoor unit installation, connect the pipe at the indoor side 

first, then the outdoor side.

A

lways keep ends of tubing sealed by placing a cap or covering with tape during installation and do NOT 

remove them until you are ready to connect the piping.

B

e sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may 

cause condensation or burns if touched.

When the outdoor unit is the top position and the difference of level is over 10m, it is recommended that set

a oil return bend every 5~8m in the gas pipe. The radius of oil reture bend should be over than 10cm.

CAUTION

4.1 FLARING 

NOTE

  Tools required for flaring are pipe cutter, reamer, 

flaring tool and pipe holder.

   For R32 refrigerant models, the pipe connection 

points must be placed outside of room.

90

Oblique                  Rough                   Burr

R0.4~0.8

45 °

±2

90 °     

± 4

A

In case of needing brazing, work with Nitrogen gas blowing.

Improper torque will cause flare damage or gas leaks. 

CAUTION

Use separate thermal insulation pipes for gas & 

liquid pipes.

The thickness above is a standard of the indoor 

temperature  of  27°C and humidity of 80%. If install

-

ing in an unfavorable conditions such as near bath-

rooms, kitchens, and other similar locations, 

reinforce the insulation.

Insulation’s heat-resistance temperature should 

be more than 120°C.

Use the adhesives on the connection part of insula-

tion to prevent moisture from entering. 

Repair and cover any possible cracks in the insula-

tion, specially check the bent part or hanger of 

pipe.

4.1.1 Using a pipe cutter to cut the pipe to the 

         requested length. Ensure that the cut edge 

         remains at 90° with the side of the pipe. 

4.1.2 Use a reamer to remove burrs with the cut 

        surface downward so that the chips do not 

        enter the pipe.

4.1.3 Carry out flaring work using flaring tools as 

         below.

4.1.4 Check if the flaring is properly made. See 

         incorrectly flared pipes sample below.

4.2 PIPING WORK

4.2.1 Align the center to tighten the flare nut and finish

         connection using two wrenches.

Flare nut

Wrench

Torque wrench

4.2.2 Select the appropriate insulation material for 

refrigerant pipe.(Min. 10mm, thermal insulating foam C)

Inclined         Damaged Surface          Cracked          Uneven Thickness

Torque

Tubing size

18 ~ 20 N.m 

25 ~ 26 N.m 

35 ~ 36 N.m 

45 ~ 47 N.m 

65 ~ 67 N.m 

Φ6.35mm

Φ9.52mm

Φ12.7mm

Φ15.88mm

Φ19.05mm

Outside diameter

A(mm)

Max

8.7

Φ6.35mm

Φ9.52mm

Φ12.7mm

Φ15.88mm

Φ19.05mm

12.4

15.8

19.0

23.3

8.3

12.0

15.4

18.6

22.9

Min

After the piping work is finished, make sure to check the connection part of each refrigerant pipe and confirm 

that there is no gas leak by applying soapy water to them or by using a leak detector specific for HFC refrigerants. 

Refer below picture for illustration.

            A: Low pressure stop valve            B: High pressure stop valve
            C& D: Indoor unit flare nuts

Check-point of indoor unit

Check-point of outdoor unit

A

B

C

D

4.3 REFRIGERANT PIPE

NOTE

    Extended pipe length will affect the capacity and energy efficiency of the unit.

    The nominal efficiency is tested based on the pipe length of 5 meter.     

    When the pipe length is over 5m, the additional refrigerant should be added according to the pipe length.

    The max. pipe length is recommended as below.

4.4 AIR EVACUATION

Connect the charge hose from the manifold gauge to the service port of the gas side packed valve.

Connect the charge hose to the port of the vacuum pump.

Fully open the handle Lo of manifold gauge.

Operate the vacuum pump to evacuate air from the system until -76cmHg.

Close the handle Lo of manifold gauge.

Fully open the valve stem of the packed valves.

Remove the charging hose form the service port.

Securely tighten caps of packed valve.

-76 cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Packed valve

Manifold valve

Compound gauge

Pressure meter

4.5 LEAKAGE TEST

* Please use tools for R32 system.

Note:The refrigerant should be charged from the service port on the outdoor unit’s low pressure valve.

Liquid side:

φ

9.52mm       

R32*

Chargeless length 

5m

Additional charge per meter

Liquid side:

φ

6.35mm       

12g

24g

Minimum length 

to reduce abnormal 

vibration & noise 

3m

4. REFRIGERANT PIPING WORK

4. REFRIGERANT PIPING WORK

* Please use tools for R32 system.

Max. height difference(m)

Models

25

R32  Inverter

Max. pipe length(m)     

10

9K/12K

GB

Содержание 38QHP009E8S

Страница 1: ...96300 IMROPTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models F GA...

Страница 2: ...vented to the atmosphere during installation service or disposal When any leakage of the contained fluorinated gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualifi...

Страница 3: ...uld cause severe injury or death Disconnect from power source before attempting any electrical work Connect the connective cable correctly Wrongly connecting may result in electric parts damaged Use t...

Страница 4: ...sed to strong winds it is recommended that a wind baffle be used A location which can bear the weight of outdoor unit and where the outdoor unit can be mounted in a level position A location which pro...

Страница 5: ...a rise Step 7 Wrap Pipe and Cable Step 8 Hang the Indoor Unit 1 Run refrigerant lines through hole in the wall 2 Hang indoor unit on upper hook of mounting plate then push lower part of indoor unit u...

Страница 6: ...le of outdoor unit and rotate 90 degree to securely assemble them 3 5 INSTALL THE DRAIN PIPE FOR OUTDOOR UNIT unit cm unit cm Base pan hole of outdoor unit Drain hose Field supply Gasket Drain Outlet...

Страница 7: ...ign the center to tighten the flare nut and finish connection using two wrenches Flare nut Wrench Torque wrench 4 2 2 Select the appropriate insulation material for refrigerant pipe Min 10mm thermal i...

Страница 8: ...0mA is advisable This appliance incorporates an earth connection for functional purposes only CAUTION NOTICE 1 All power wires must be sized in according with national state and local electrical wirin...

Страница 9: ...n under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed 7 3 GENERAL WORK AREA All mintenance staff and others working in...

Страница 10: ...hat can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Other parts...

Страница 11: ...t stating the equipment contains flammable refrigerant 20 19 7 19 RECOVERY CAUTION When removing refrigerant from a system either for service or decommissioning it is recommended good practice that al...

Страница 12: ...WEEE 2012 19 E 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 42QHP009E8S 3...

Страница 13: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13m2 9000Bth h 12000Btu h 17m2 12000Btu h 18000Btu h 26m2 18000Btu h 24000Btu h 35m2 04 BG...

Страница 14: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm 1 2 3 1 1 2 1 1 1 B 2 5 1 A 5 N 1 3 2 3 m BG...

Страница 15: ...07 2 2 1 65 65 mm 5 mm 2 2 A 65 mm 90 mm 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 16 mm 5 8 in 90 mm 3 54 in BG...

Страница 16: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm H D A B 3 100 mm x 150 mm 10 100 mm x 150 mm 10 W BG...

Страница 17: ...2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15 88 mm 45 47 N m 19 05 mm 65 67 N m 4 2 2 10 mm C 27 C 80 120 C 11 4 10 m 5 8 m 10 cm 12 76 cmHg Lo Hi 4 1 R32 4 1 1 90 4 1 2 4 1 3 A mm...

Страница 18: ...QHP009 QHP012 13 5 1 5 3 mm 30mA E 1 2 H07RN F 3 4 T20A 250VAC adpot R32 GND 14 A A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 GND 5 Y G 4 cm 4 cm BG...

Страница 19: ...15 7 7 1 7 2 7 3 7 4 7 5 7 6 7 7 7 8 16 6 1 6 2 24 C COOLING 30 OFF 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED 6 3 BG...

Страница 20: ...17 7 7 12 7 13 7 14 25 7 15 18 7 7 9 7 10 10 1 10 2 7 11 BG...

Страница 21: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 7 17 80 7 18 BG...

Страница 22: ...i ni i elektronski otpad WEEE prema direktivi 2012 19 EZ ne smije mije ati s obi nim ku nim otpadom Ovaj ure aj ne smije se odlagati u ku ni otpad Postoji nekoliko mogu nosti za odlaganje 1 Op ina je...

Страница 23: ...cu uklanjanjem bilo koje sigurnosne za tite ili zaobila enjem sigurnosnih prekida a Elektri arski radovi moraju se izvesti u skladu s priru nikom za instalaciju dr avnim i lokalnim propisima za elektr...

Страница 24: ...i upravlja 1 Instalacijska plo a 1 Vijak B 2 Dibl 5 Mali filter 1 Vijak A 5 Magnetni prsten neke jedinice N U skladu sa stvarnom koli inom 1 3 IZBOR MJESTA INSTALACIJE Unutra nja jedinica mjesto koje...

Страница 25: ...iti cijelom du inom potpuno prohodan mora biti nagnut prema dole i izoliran cijelom du inom do vanjskog zida Ispravno Nemojte oblikovati uspon Nemojte stavljati kraj odvoda u vodu Korak 5 Priklju ite...

Страница 26: ...imenzije vanjske jedinice mm Dimenzije monta e mm Vanjska jedinica V D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 POTREBAN PROSTOR ZA VANJSKU JEDINICU 09 3 INSTALACIJA VANJSKE JEDINICE Instal...

Страница 27: ...ili dr sli ne lokacije poja ajte izolaciju Temperatura otpornosti izolacije na toplotu treba biti vi a od 120 C Nanesite ljepilo na spojni dio izolacije da biste sprije ili ulazak vlage Popravite i p...

Страница 28: ...emljenje koje ovaj ure aj sadr i ima isklju ivo funkcionalnu svrhu NAPOMENA 1 Dimenzije svih elektri nih ica moraju biti u skladu s dr avnim i lokalnim propisima za elektroinstalacije Posebne zahtjeve...

Страница 29: ...iti i po mogu nosti izbaciti u atmosferu 7 8 PROVJERE RASHLADNE OPREME Sve zamjenske elektri ne komponente moraju odgovarati namjeni i specifikacijama U svakom trenutku treba slijediti proizvo a eve s...

Страница 30: ...lemljenje cijevi Uvjerite se da ispust vakuumske pumpe nije blizu izvora zapaljenja i da je omogu ena ventilacija 18 7 INFORMACIJE O SERVISIRANJU Veli ina punjenja je u skladu s veli inom prostorije u...

Страница 31: ...edstva za hla enje uslijed mehani kog o te enja opreme u ambala i Dozvoljeni maksimalni broj dijelova opreme koji se smiju pohraniti zajedno odre uju lokalni propisi 7 INFORMACIJE O SERVISIRANJU 7 16...

Страница 32: ...n OEEZ podle sm rnice 2012 19 ES nesm b t sm ch na s b n m komun ln m odpadem Likvidace tohoto za zen spole n s b n m komun ln m odpadem je zak z na Pro likvidaci existuje n kolik mo nost 1 Obec m zav...

Страница 33: ...avujte tuto jednotku t m e odstran te jakoukoliv bezpe nostn ochranu nebo p emost te jak koliv sp na bezpe nostn ho blokov n Elektroinstala n pr ce by m ly b t prov d ny v souladu s n vodem k instalac...

Страница 34: ...an V vod odtoku 1 Baterie 2 T sn n 1 Dr k d lkov ho ovlada e 1 Mont n deska 1 roub B 2 Kotva 5 Mal filtr 1 roub A 5 Magnetick krou ek n kter jednotky N v z vislosti od skute n ho mno stv 1 3 V B R M S...

Страница 35: ...n n m roub demontujte kabelovou svorku 3 Prot hn te p ipojovac vodi e ze zadn strany vnit n jednotky a p ipojte je ke svorkovnici vnit n jednotky Odtok Odtokov potrub nesm b t v dn m m st sv d lky zab...

Страница 36: ...r hlavy upev ovac ho roubu by m l b t v ce ne 12 mm Rozm ry venkovn jednotky mm Mont n rozm ry mm Venkovn jednotka W H D A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 PROSTOROV PO ADAVKY VENKOV...

Страница 37: ...hyn a podobn ch m st zesilte izolaci Teplota tepeln ho odporu izolace by m la b t vy ne 120 C Pou ijte lepidla na spojovac sou sti izolace abyste p ede li vniknut vlhkosti Opravte a zakryjte p padn pr...

Страница 38: ...A Tento spot ebi zahrnuje zemnic p pojku pouze pro el funk nosti UPOZORN N 1 V echny nap jec vodi e mus b t dimenzov ny v souladu s n rodn mi st tn mi a m stn mi elektroinstala n mi p edpisy V p pad z...

Страница 39: ...prov d n m jak koliv innosti za p tomnosti vysok teploty dostate n odv tr v na Nep etr it odv tr v n mus b t zaji t no po celou dobu prov d n pr ce Odv tr v n mus bezpe n rozptylovat ve ker uvoln n ch...

Страница 40: ...adice v v vy nenach z v bl zkosti dn ch zdroj vzn cen a e je zaji t no odv tr v n 18 7 INFORMACE PRO PROV D N SERVISN CH Z SAH plnic objem odpov d velikosti m stnosti ve kter jsou um st ny sou sti obs...

Страница 41: ...ho po kozen za zen uvnit balen Maxim ln po et kus za zen kter je dovoleno skladovat spole n bude stanoveno m stn mi p edpisy 7 INFORMACE PRO PROV D N SERVISN CH Z SAH 7 16 POSTUPY PLN N Krom konven n...

Страница 42: ...30 2012 19 1 2 3 4 1 3 1 1 3 1 2 5 1 3 6 2 7 2 1 7 2 2 8 3 9 3 1 9 3 2 9 3 3 10 3 4 10 3 5 10 4 11 4 1 11 4 2 11 4 3 12 4 4 12 4 5 12 5 13 6 14 6 1 14 6 2 14 6 3 14 7 15 R32 R290 02 Hz 42QHP009E8S 38Q...

Страница 43: ...1 1 1 03 R410A 1 R32 4 m2 4 m2 R290 9000 Btu h 13 m2 9000 Bth h 12000 Btu h 17m2 12000 Btu h 18000 Btu h 26m2 18000 Btu h 24000 Btu h 35m2 04 EL...

Страница 44: ...1 05 1 06 15cm 30cm 2 3m 200cm 60cm 30cm 60cm 12cm 12cm A 1 2 3 1 Mode Timer TurboI ON LED ON OFF Fan Follow me Self clean 1 2 1 1 1 2 5 1 5 N 1 3 2 3 m EL...

Страница 45: ...895 435 435 5 217 460 242 5 45 150 258 65 232 5 45 45 65 298 16 mm 5 8 90 mm 3 54 A 65 mm 90 mm 07 2 2 1 5 mm 2 2 1 2 3 4 8 1 2 3 5 6 7 1 2 3 08 2 EL...

Страница 46: ...3 3 3 4 M10 3 5 90 3 1 12mm mm mm A B 38QHP009E8S 38QHP012E8S 800 554 333 515 340 3 2 09 3 cm cm A B 3 100mm x 150mm M10 100mm x 150mm 10 EL...

Страница 47: ...19 05 mm 23 3 22 9 4 1 4 4 3 6 35 mm 9 52mm R32 3 m 5 m 12 g 24 g R32 5 5m R32 Inverter m m 9K 12K 25 10 R32 4 4 76cmHg 4 5 HFC A B 4 2 4 2 1 6 35 mm 18 20 N m 9 52 mm 25 26 N m 12 7 mm 35 36 N m 15...

Страница 48: ...QHP009 QHP012 13 5 1 5 3 mm RCD 30 mA 1 2 H07RN F 3 4 T20A 250 V AC R32 14 A 38QHP009E8S 10 0 16 3 1 5 mm2 5 1 5 mm2 38QHP012E8S 13 0 20 3 1 5 mm2 5 1 5 mm2 5 4 cm 4 cm EL...

Страница 49: ...15 7 7 1 7 2 7 3 7 4 7 5 CO2 7 6 7 7 7 8 16 6 1 6 2 24 C 30 6 3 COOLING ON OFF MODE TEMPERATURE FAN SPEED E E 6 3 EL...

Страница 50: ...17 7 7 12 7 13 7 14 LFL 25 OFN 7 15 OFN OFN OFN 18 7 7 9 7 10 10 1 10 2 7 11 EL...

Страница 51: ...19 7 20 7 19 7 20 1 2 3 4 5 7 7 16 OFN 7 17 80 7 18 EL...

Отзывы: