AHRI* CAPACITY RATINGS
Model Numbers
Cooling
High Heating
47° F (8.33° C)
Low Heating
17° F ( --- 8.33° C)
Outdoor Unit
Indoor Unit
Capacity
(Btuh)
EER
SEER
Capacity (Btuh)
HSPF
Capacity (Btuh)
38GVM218 --- --- ---3
2 x 40GVM009 --- --- ---3
18,000
10.2
16.0
19,000
8.2
9,600
40GVM009 --- --- ---3
+ 40GVM012 --- --- ---3
18,000
10.2
16.0
19,000
8.2
9,600
38GVM224 --- --- ---3
2 x 40GVM009 --- --- ---3
+ 40GVM012 --- --- ---3
26,000
8.2
16.0
29,000
8.2
17,000
3 x 40GVM009 --- --- ---3
26,000
8.2
16.0
29,000
8.2
17,000
40GVM009 --- --- ---3 +
2 x 40GVM012 --- --- ---3
26,000
8.2
16.0
29,000
8.2
17,000
38GVM430 --- --- ---3
4 x 40GVM009 --- --- ---3
29,000
7.3
16.0
30,400
8.2
16,500
40GVM009 --- --- ---3 +
2 x 40GVM012 --- --- ---3
+ 40GVM018 --- --- ---3
29,000
7.3
16.0
30,400
8.2
16,500
38GVM436 --- --- ---3
Non ---Ducted FCU’s
34,400
8.0
16.0
37,200
8.2
22,000
38GVM542 --- --- ---3
Non ---Ducted FCU’s
40,000
9.3
16.0
43,000
8.0
24,800
*Air Conditioning, Heating & Refrigeration Institute
--- --- = N/A
Legend
EER
--- Energy Efficiency Ratio
HSPF
--- Heating Seasonal Performance Factor
SEER
--- Seasonal Energy Efficiency Ratio
NOTES
:
1.
Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80
_
F (26.67
_
C) db, 67
_
F (19.44
_
C) wb air entering indoor unit and 95
_
F
(35
_
C) db air entering outdoor unit. High Temperature Heating Standard: 70
_
F (21.11
_
C) db air entering indoor unit and 47
_
F (8.33
_
C) db, 43
_
F (6.11
_
C) wb air entering outdoor
unit.
2.
Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3.
All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for air flows at all available fan speeds.
AIR THROW DATA
Model Number
Approximate Air Throw ft. (m)
Low
Medium
High
Turbo
40GVM009 --- --- ---3
18 (5.5)
21 (6.4)
24 (7.3)
27 (8.2)
40GVM012 --- --- ---3
19 (5.8)
21 (6.4)
24 (7.3)
27 (8.2)
40GVM018 --- --- ---3
25 (7.6)
29 (8.8)
32 (9.8)
35 (10.7)
SOUND RATINGS
Outdoor Units
Model Number
Sound Power dBA
Sound Pressure dBA
38GVM218 --- --- ---3 (cool/heat)
66/66
56/56
38GVM324 --- --- ---3 (cool/heat)
66/66
56/56
38GVM430 --- --- ---3 (cool/heat)
66/66
56/56
38GVM436 --- --- ---3 (cool/heat)
69/69
59/59
38GVM542 --- --- ---3 (cool/heat)
68/68
58/58
Indoor Units
Model Number
Low
Medium
High
Turbo
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
40GVM009 --- --- ---3
36.0
26.0
45.0
35.0
47.0
37.0
51.0
41.0
40GVM012 --- --- ---3
38.0
28.0
46.0
36.0
48.0
38.0
52.0
42.0
40GVM018 --- --- ---3
45.0
35.0
50.0
40.0
54.0
44.0
56.0
46.0
NOTES
:
1.
Sound power ratings are per AHRI 270 and AHRI 350
2.
Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
Содержание 38GVM Series
Страница 14: ...14 WIRING DIAGRAMS A13093 Fig 12 38GVM 18k Wiring Diagram...
Страница 15: ...15 WIRING DIAGRAMS CONTINUED A13094 Fig 13 38GVM 24k Wiring Diagram...
Страница 16: ...16 WIRING DIAGRAMS CONTINUED A13095 Fig 14 38GVM 30k Wiring Diagram...
Страница 17: ...17 WIRING DIAGRAMS CONTINUED A13096 Fig 15 38GVM 36k Wiring Diagram...
Страница 18: ...18 WIRING DIAGRAMS CONTINUED A13097 Fig 16 38GVM 42k Wiring Diagram...