12
ELECTRICAL DATA
Outdoor Units
Unit Size
System Voltage
Operating Voltage*
Compressor
Outdoor Fan
MCA
MAX
FUSE/CB
Amp
(MOCP)
VOLT--- PH --- HZ
MAX/MIN
RLA
LRA
FLA
HP
W
18 K
208/230 ---1 ---60
253/187
9.6
27
0.54
1/12
60
13
20
24 K
14.7
45
0.59
20
30
30 K
19.6
45
26
45
36 K
21.0
45
0.67
1/8
120
28
45
42 K
21.5
67
1.10
1/6
140
29
50
Indoor Units
Unit Size
System Voltage
Operating Voltage
Indoor Fan
{
VOLT--- PH --- HZ
MAX/MIN
FLA
W
9 K
208/230 ---1 ---60
253/187
0.20
20
12 K
18 K
0.32
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
Indoor fan powered from outdoor unit.
LEGEND
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
MOCP
--- Maximum Over Current Protection
WIRING
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3)
wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64--inch thick insulation must be used.
Control Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64--inch thick insulation, must be used as the
communication wire from from the outdoor unit to the indoor unit.
To minimize voltage drop of the control wire, use the following wire size and maximum lengths shown in the chart below.
Wire Size
Length
ft (m)
18 AWG
50 ft. (15 m)
16 AWG
50 ft (15) to 100 ft. (30 m)
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
S
Wires should be sized based on NEC and local codes.
S
Use copper conductors only with a minimum 300 volt .
rating and 2/64 inch thick insulation.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
S
Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S
Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, be sure all
wiring is tightly connected.
S
No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S
Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
S
Connecting cable with conduit shall be routed through
hole in the conduit panel.
Содержание 38GVM Series
Страница 14: ...14 WIRING DIAGRAMS A13093 Fig 12 38GVM 18k Wiring Diagram...
Страница 15: ...15 WIRING DIAGRAMS CONTINUED A13094 Fig 13 38GVM 24k Wiring Diagram...
Страница 16: ...16 WIRING DIAGRAMS CONTINUED A13095 Fig 14 38GVM 30k Wiring Diagram...
Страница 17: ...17 WIRING DIAGRAMS CONTINUED A13096 Fig 15 38GVM 36k Wiring Diagram...
Страница 18: ...18 WIRING DIAGRAMS CONTINUED A13097 Fig 16 38GVM 42k Wiring Diagram...