8.1 Refrigerant charge check
8.2 Cleaning the coil
This check becomes necessary after any refrigerant leak or after
replacement of the compressor.
The best method to correctly charge refrigerant is to completely empty
the refrigerant circuit using refrigerant recovery equipment.
Then charge the exact quantity of refrigerant according to the data
shown on the unit nameplate.
R-410A systems must be charged with liquid refrigerant.
Use the special recharging equipment (normally on the market) to
control the refrigerant correctly.
When it is necessary to recharge refrigerant, charge the specified
amount of new refrigerant according to the following steps:
1. Recover the refrigerant, and check no refrigerant remains in the
equipment.
2. Connect the charge hose to packed valve service port (see the
Check joint in the figure illustrated in chapter 3.4 Refrigerant
schematics).
3. Connect the charge hose of the vacuum pump adapter.
4. Place the handle of the gauge manifold Low in the fully opened
position, and turn on the vacuum pump’s power switch. Then,
evacuating the refrigerant in the cycle.
5. When the compound gauge’s pointer has indicated -0.1 MPa
( - 76 cmHg ), place the handle Low in the fully closed position, and
UVSOPòUIFWBDVVNQVNQTQPXFSTXJUDI
6. Keep the status set as it is for 1 to 2 minutes, and ensure that the
compound gauge’s pointer does not return.
7. Set the refrigerant cylinder to the electronic balance, connect the
connecting hose to the cylinder and the connecting port of the
electronic balance, and charge liquid refrigerant.
If necessary, proceed as follows for more careful cleaning of the coil:
- Switch the mains supply OFF.
- Remove unit top cover by losening the fixing screws and lifting
thecover. Carefully clean the coil with a vacuum cleaner from inside to
outside.
IMPORTANT:
All maintenance operations must be performed by qualified personnel.
IMPORTANT:
- Never charge refrigerant exceeding the specified amount.
- If the specified amount of refrigerant cannot be charged, charge
refrigerant bit by bit in COOL mode.
- Do not carry out additional charging. When additional charging is
carried out if refrigerant leaks, the refrigerant composition changes
in the refrigeration cycle, that is characteristics of the heat pump
changes, refrigerant exceeding the specified amount is charged, and
working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
- A cylinder with siphon enables liquid to be charged without the
cylinder turned upside down.(see the figure below)
With the same vacuum cleaner, remove the dust from inside the fan
compartment and the fan blades. Avoid any damage to the blades
which may cause future vibrations and noise.
Replace the unit cover and tighten the screws.
SM_30AW.indd 102
14-03-2011 14:46:27
Содержание 30AWH004HB
Страница 30: ...30 30AW GMC control size 004HB Electrical connections 4 SM_30AW indd 30 14 03 2011 14 42 18...
Страница 31: ...31 30AW Electrical connections 4 Inverter control size 004XB SM_30AW indd 31 14 03 2011 14 42 21...
Страница 32: ...32 30AW GMC control size 004XB Electrical connections 4 SM_30AW indd 32 14 03 2011 14 42 24...
Страница 33: ...33 30AW Inverter control size 006HB Electrical connections 4 SM_30AW indd 33 14 03 2011 14 42 27...
Страница 34: ...34 30AW GMC control size 006HB Electrical connections 4 SM_30AW indd 34 14 03 2011 14 42 29...
Страница 35: ...35 30AW Inverter control size 006XB Electrical connections 4 SM_30AW indd 35 14 03 2011 14 42 32...
Страница 36: ...36 30AW GMC control size 006XB Electrical connections 4 SM_30AW indd 36 14 03 2011 14 42 35...
Страница 37: ...37 30AW Inverter control size 006NX Electrical connections 4 SM_30AW indd 37 14 03 2011 14 42 38...
Страница 38: ...38 30AW GMC control size 006NX Electrical connections 4 SM_30AW indd 38 14 03 2011 14 42 40...
Страница 39: ...39 30AW Inverter control size 008HB Electrical connections 4 SM_30AW indd 39 14 03 2011 14 42 42...
Страница 40: ...40 30AW GMC control size 008HB Electrical connections 4 SM_30AW indd 40 14 03 2011 14 42 45...
Страница 41: ...41 30AW Inverter control size 008XB Electrical connections 4 SM_30AW indd 41 14 03 2011 14 42 48...
Страница 42: ...42 30AW GMC control size 008XB Electrical connections 4 SM_30AW indd 42 14 03 2011 14 42 50...
Страница 43: ...43 30AW Inverter control size 008NX Electrical connections 4 SM_30AW indd 43 14 03 2011 14 42 53...
Страница 44: ...44 30AW GMC control size 008NX Electrical connections 4 SM_30AW indd 44 14 03 2011 14 42 56...
Страница 45: ...45 30AW Inverter control size 012HB Electrical connections 4 SM_30AW indd 45 14 03 2011 14 42 58...
Страница 46: ...46 30AW GMC control size 012HB Electrical connections 4 SM_30AW indd 46 14 03 2011 14 43 01...
Страница 47: ...47 30AW Inverter control size 012XB Electrical connections 4 SM_30AW indd 47 14 03 2011 14 43 04...
Страница 48: ...48 30AW GMC control size 012XB Electrical connections 4 SM_30AW indd 48 14 03 2011 14 43 07...
Страница 49: ...49 30AW Inverter control size 012NX Electrical connections 4 SM_30AW indd 49 14 03 2011 14 43 10...
Страница 50: ...50 30AW GMC control size 012NX Electrical connections 4 SM_30AW indd 50 14 03 2011 14 43 13...
Страница 51: ...51 30AW Inverter control size 015HB SM_30AW indd 51 14 03 2011 14 43 16...
Страница 52: ...52 30AW GMC control size 015HB SM_30AW indd 52 14 03 2011 14 43 19...
Страница 53: ...53 30AW Inverter control size 015XB SM_30AW indd 53 14 03 2011 14 44 58...
Страница 54: ...54 30AW GMC control size 015XB SM_30AW indd 54 14 03 2011 14 45 01...
Страница 100: ...100 30AW Carrier interfaces 7 SM_30AW indd 100 14 03 2011 14 46 25...
Страница 120: ...120 30AW Spare Parts 9 For the spare parts refer to specific document SM_30AW indd 120 14 03 2011 14 47 00...
Страница 136: ...136 30AW Additional Informations 11 11 1 Additional information SM_30AW indd 136 14 03 2011 14 47 24...
Страница 137: ...137 30AW Additional Informations 11 11 1 Additional information SM_30AW indd 137 14 03 2011 14 47 25...