This code displays the Outdoor Air Temperature. The valid OAT
value is used with this priority:
1. OAT from GMC thermistor (if it is installed)
2. OAT from inverter, read by TO sensor.
-30°C
90°C
-
12
(
)
GMC OUTDOOR AIR
TEMPERATURE
This code displays the Outdoor Air Temperature read by GMC
thermistor.
-
-
-
13
TEMPERATURE ROOM
SENSOR ADJUSTMENT
This code is use to adjust the temperature read by the sensor in
order to recover bad positioning of the user interface.
-5°C
+5°C
0°C
14
DAY PERIOD
This code is use to select how many period per day will be availa-
ble for the scheduling:
2
4
6
2
6
4
15
HOME HEAT TEMPE-
RATURE
With this code the User can select the HOME Temperature set-
point in Heating Mode
12°C
38°C
20°C
16
HOME COOL TEMPE-
RATURE
With this code the User can select the HOME Temperature set-
point in Cooling Mode
12°C
38°C
24°C
17
SLEEP HEAT
TEMPERATURE
With this code the User can select the SLEEP Temperature set-
point in Heating mode
12°C
38°C
18°C
18
SLEEP COOL
TEMPERATURE
With this code the User can select the SLEEP Temperature set-
point in Cooling Mode
12°C
38°C
26°C
19
AWAY HEAT
TEMPERATURE
With this code the User can select the AWAY Temperature set-
point in Heating mode
12°C
38°C
15°C
20
AWAY COOL
TEMPERATURE
With this code the User can select the AWAY Temperature set-
point in Cooling Mode
12°C
38°C
28°C
21
(
)
USER ROOM
SET-POINT
This code displays the room set-point that the user, pressing the
temporary/hold button, is selecting as temporary or hold.
12°C
38°C
20°C
22
(
)
FAULT CODE
This code displays the last fault code occurred.
-
-
-
23
(
)
FAULT HISTORY
This code displays the recent 4 fault codes stored.
-
-
-
100
SYSTEM TYPE
This code is use to set the System type:
1. A2W Monobloc fixed Water Temperature Value (dry contacts)
2. A2W Monobloc Climatic Curve setup (dry contacts)
3. A2W Monobloc Comfort with NUI
4. A2W Monobloc Comfort with NUI as Thermostat
5. N.A.
6. A2W Monobloc RS485
7. N.A.
1
7
1. A2W
101
USER INTERFACE TYPE
This code is use to define if NUI User Interface is used and how it
is used:
0. Not Used (Input Relay active/SUI)
1. NUI Installed
2. NUI used as programmer
0
2
0. Not used
102
(
)
NUI SOFTWARE
RELEASE
This code displays the NUI Software Release
-
-
-
103
(
)
NUI SOFTWARE
VERSION
This code displays the NUI Software Version
-
-
-
104
OUTPUT TEST
This code is use to force Output ON to test (max 10 minutes):
0
9
0. No test
0. No test
1. Water pump
2. Alarm / Ambient temperature reached
3. External Heat Source / Defrost
4. Alarm + Defrost / Humidity
5. Trace Heater / Additional Water Pump
6. 3 Way valve
7. SUI Alarm
8. Blank
105
RESET PUMP
RUN-TIME
This code is use to reset the water pump timer to zero.
no
yes
no
106
EXTERNAL HEAT
SOURCE / DEFROST
This code is use to select the output connected at PIN 4 on
terminal strip:
1. External Heat Source
2. Defrost Output
1
2
1
107
HUMIDITY LIMIT
This code is use to define the humidity threshold limit to enable
the output for the external de-humidifier system.
20
100
Code Nr.
Name
DESCRIPTION
VALUE RANGE
STANDARD
Min
Max
SM_30AW.indd 96
14-03-2011 14:46:19
Содержание 30AWH004HB
Страница 30: ...30 30AW GMC control size 004HB Electrical connections 4 SM_30AW indd 30 14 03 2011 14 42 18...
Страница 31: ...31 30AW Electrical connections 4 Inverter control size 004XB SM_30AW indd 31 14 03 2011 14 42 21...
Страница 32: ...32 30AW GMC control size 004XB Electrical connections 4 SM_30AW indd 32 14 03 2011 14 42 24...
Страница 33: ...33 30AW Inverter control size 006HB Electrical connections 4 SM_30AW indd 33 14 03 2011 14 42 27...
Страница 34: ...34 30AW GMC control size 006HB Electrical connections 4 SM_30AW indd 34 14 03 2011 14 42 29...
Страница 35: ...35 30AW Inverter control size 006XB Electrical connections 4 SM_30AW indd 35 14 03 2011 14 42 32...
Страница 36: ...36 30AW GMC control size 006XB Electrical connections 4 SM_30AW indd 36 14 03 2011 14 42 35...
Страница 37: ...37 30AW Inverter control size 006NX Electrical connections 4 SM_30AW indd 37 14 03 2011 14 42 38...
Страница 38: ...38 30AW GMC control size 006NX Electrical connections 4 SM_30AW indd 38 14 03 2011 14 42 40...
Страница 39: ...39 30AW Inverter control size 008HB Electrical connections 4 SM_30AW indd 39 14 03 2011 14 42 42...
Страница 40: ...40 30AW GMC control size 008HB Electrical connections 4 SM_30AW indd 40 14 03 2011 14 42 45...
Страница 41: ...41 30AW Inverter control size 008XB Electrical connections 4 SM_30AW indd 41 14 03 2011 14 42 48...
Страница 42: ...42 30AW GMC control size 008XB Electrical connections 4 SM_30AW indd 42 14 03 2011 14 42 50...
Страница 43: ...43 30AW Inverter control size 008NX Electrical connections 4 SM_30AW indd 43 14 03 2011 14 42 53...
Страница 44: ...44 30AW GMC control size 008NX Electrical connections 4 SM_30AW indd 44 14 03 2011 14 42 56...
Страница 45: ...45 30AW Inverter control size 012HB Electrical connections 4 SM_30AW indd 45 14 03 2011 14 42 58...
Страница 46: ...46 30AW GMC control size 012HB Electrical connections 4 SM_30AW indd 46 14 03 2011 14 43 01...
Страница 47: ...47 30AW Inverter control size 012XB Electrical connections 4 SM_30AW indd 47 14 03 2011 14 43 04...
Страница 48: ...48 30AW GMC control size 012XB Electrical connections 4 SM_30AW indd 48 14 03 2011 14 43 07...
Страница 49: ...49 30AW Inverter control size 012NX Electrical connections 4 SM_30AW indd 49 14 03 2011 14 43 10...
Страница 50: ...50 30AW GMC control size 012NX Electrical connections 4 SM_30AW indd 50 14 03 2011 14 43 13...
Страница 51: ...51 30AW Inverter control size 015HB SM_30AW indd 51 14 03 2011 14 43 16...
Страница 52: ...52 30AW GMC control size 015HB SM_30AW indd 52 14 03 2011 14 43 19...
Страница 53: ...53 30AW Inverter control size 015XB SM_30AW indd 53 14 03 2011 14 44 58...
Страница 54: ...54 30AW GMC control size 015XB SM_30AW indd 54 14 03 2011 14 45 01...
Страница 100: ...100 30AW Carrier interfaces 7 SM_30AW indd 100 14 03 2011 14 46 25...
Страница 120: ...120 30AW Spare Parts 9 For the spare parts refer to specific document SM_30AW indd 120 14 03 2011 14 47 00...
Страница 136: ...136 30AW Additional Informations 11 11 1 Additional information SM_30AW indd 136 14 03 2011 14 47 24...
Страница 137: ...137 30AW Additional Informations 11 11 1 Additional information SM_30AW indd 137 14 03 2011 14 47 25...