45
Installation Manual
Refrigerant Recovery Operation
Refrigerant Recovery Operation
In order to relocate the products, it is necessary to recover the R-410A refrigerant of outdoor
unit.
1
2
3
How to start refrigerant recovery operation
How to stop refrigerant recovery operation
Caution
Please press and hold continuously the TACT switch in the main board of Hydro
Unit for more than 30 seconds in stop status of the system and then the outdoor
unit will start the recovery operation right after releasing from TACT switch.
Recovery operation can be terminated by pressing TACT switch for more than 2
seconds during recovery operation.
Also recovery operation will be automatically stopped in case of operating for
more than 10 minutes.
Please close the service valve at low pressure side within 30 seconds after
closing service valve at high pressure side. If it exceed 30 seconds, the
compressor will be damaged.