Installation Manual
17
Installation materials (local procurement)
No
Component name
Specificat ions
Quantity
(2 holes)
Remarks
1 Refrigerant connection pipe
OD 9.52mm
1
Liquid pipe
2 Refrigerant connection pipe
OD 15.8mm
1
Gas pipe
3 Insulator for refrigerant piping
ID 14 X T8
1
4 Insulator for refrigerant piping
ID 14 X T8
1
5 Indoor unit power cable
(3-phase power cable)
4.0
㎟
X 4C (excluding ground wire) or 5G
1
Cable length
<
20m
6.0
㎟
X 4C (excluding ground wire) or 5G
Cable length
≥
20m
6
Indoor/outdoor unit connec-
tion power cable
(3-phase power cable)
2.5
㎟
X 4C (excluding ground wire) or 5G
1
Cable length
<
20m
4.0
㎟
X 4C (excluding ground wire) or 5G
1
Cable length
≥
20m
7 Power cable (thermal storage
pump, heating pump)
1.0
㎟
X 2C
1
8 Communication cable
CVV-SB (shield cable) 1.5
㎟
X 2C
1
9 Domestic hot water tank
Local sourcing (output : less than 80W)
1
10 Heating Pump
Local sourcing (output : less than 80W)
1
11
Domestic hot water tank tem-
perature sensor connection
cable
Heat shrinkable tube + CVV-SB (shield cable)
1
12 Wired remote controller con-
nection cable
UTP(Cat.5e)
1
13 Domestic hot water tank
Local sourcing
1
14 Expansion tank
Local sourcing
1
15 Ball top
Procured in the market
1
16 Ball valve
Use pressure: 10Kg, diameter: 25A, material:bronze
6
17 Ball valve (for cleaning a
brazed plate heat exchanger) Use pressure: 10Kg, diameter: 15A, material:bronze
2
18 Check valves
Use pressure: 10Kg, diameter: 25A, 50 mesh or
higher, material:bronze
2
19 Filter (strainer)
Use pressure: 10Kg, diameter: 25A, material:bronze
1
20 Air vent
Use pressure: 10Kg, diameter: 15A, material:bronze
1
21 Water drainage
Copper or stainless steel pipe
1
25A
22 Pipe insulator
PE heat insulator (with a thickness of 20mm or higher)
1
Note) The specified wire should be used when extending the domestic hot water tank temperature sensor.
In addition, wire tubing should be used to protect wires.
After removing the wire clothing to extend the wire, the connection area should be covered with a heat
shrinkable tube.
Note) For power cable, use an IEC 60245-4 IEC57 or higher, or an H05RN-F wire or higher.
Note) The length of the main power cable refers to the length from the main panel board to the hydro unit,
and should be less than 50 meters in principle.
If the length of the main power cable exceed 50 meters, please contact a Carrier dealer.
Note) The grounding wire should be of at least the same thickness as the power cable.