Hydro Unit(Indoor Unit) 

30AWH-025QI

Outdoor Unit

30AWH-025QO

|  Inverter Hybrid Boiler  |

(Original instruction)

Installation 

Manual

Please read carefully before installation to ensure that

installation is performed correctly.

This manual can be downloaded from the website.

http://www.carrier.co.kr/support/aircon_manual.asp

Installation 

Manual

Содержание 30AWH-025QI

Страница 1: ...5QO Inverter Hybrid Boiler Original instruction Installation Manual Please read carefully before installation to ensure that installation is performed correctly This manual can be downloaded from the...

Страница 2: ...compressors in outdoor unit and a hydro unit are self controlled inaccordance with ambient temperature and flow temperature Intelligent energy saving operation In case of malfunction the self diagnosi...

Страница 3: ...ance of brazed plate heat exchanger Control of water quality Other precautions and disposal of waste electronics 2 12 14 15 16 18 23 24 25 29 32 34 35 37 41 42 45 46 48 49 Operating Method ThingsYou M...

Страница 4: ...hing that must be paid attention to is specified in the symbol using a picture or phrase Caution Failure to observe this notice may cause injury or damage to property Caution Failure to observe this n...

Страница 5: ...to25 istheoptimalplaceforinstallation Installation Electrical work should be performed by a qualified technician in accordance with the instructions specified in this installation guide In addition a...

Страница 6: ...ion an outdoor unit that has fallen down may not be repairable Do not install the product in a place that is exposed to direct sunlight or moisture Do not install the product near any fire sources or...

Страница 7: ...evel when installing it Imbalance may cause vibration and leakage Mandatory Leveling off Leveling off Install the product in a place that can withstand the load of the product may cause vibration and...

Страница 8: ...h the air outlet of the indoor outdoor unit faces the wind Do not install the outdoor units too close each other in parallel Warning Installation Prohibited Prohibited Partial insulation of the piping...

Страница 9: ...Mandatory Warning Installation Caution Use a dedicated power supply Mandatory Mandatory Power supply to the product should be a dedicated circuit at a correct voltage Supplying power to the outdoor u...

Страница 10: ...n the other hand the product may adversely affect medical equipment or broadcasting equipment as it generates disturbance noises Mandatory Take appropriate action to prevent children from touching the...

Страница 11: ...bolts for transportation as materials for piping connection Clean the pipes before starting the plumbing work Make sure the sizes of the hot water suppy and return piping are identical If the room to...

Страница 12: ...put anticorrosive agent to prevent the corrosion of domestic hot water tank and pipes Make sure the domestic hot water tank is grounded Use a professional service provider when disposing of the boile...

Страница 13: ...pecified in the Article 41 of the Industrial Safety and Health Act After installing the boiler shake and fill the anticorrosive agent into the boiler before filling water Rinse the anticorrosive agent...

Страница 14: ...ir inlet Electrical part casing cover Air outlet Refrigerant pipe connection gas pipe 15 8 liquid pipe 9 5 Communication cable Power cable Water outlet pipe 25A Refrigerant pipe connection gas pipe 15...

Страница 15: ...when installing an expansion tank and insulation should be provided to prevent freezing and bursting Freeze and burst protection When the flow temperature goes below 6 the circulation pump heating pu...

Страница 16: ...ure is very low We recommend that you use an auxiliary heating source if the room temperature is insufficient in the winter season Defrost operation If the heat exchanger of outdoor unit becomes frost...

Страница 17: ...s restored Has an Er sign on the room temperature display or sign on the domestic hot water tank display been displayed for more than 1 hour Contact the authorized service center Is the voltage too lo...

Страница 18: ...10m 1 liquid pipe 2 Refrigerant connection pipe OD 15 8mm X 10m 1 gas pipe 3 Insulator for refrigerant pipes ID 14 X T7 X 5m 2 4 Insulator for refrigerant pipes ID 14 X T7 X 5m 2 5 Indoor outdoor unit...

Страница 19: ...nk Local sourcing 1 14 Expansion tank Local sourcing 1 15 Ball top Procured in the market 1 16 Ball valve Use pressure 10Kg diameter 25A material bronze 6 17 Ball valve for cleaning a brazed plate hea...

Страница 20: ...ources A location in which it is easy to connect to the pipe of outdoor unit and perform water piping and electrical work Electric wiring should be carried out by a qualified experienced service techn...

Страница 21: ...is exposed to hot air or direct sunlight Do not install it in a location with a saline atmosphere or where it will be exposed to sulphate gas Do not place any obstacle in front of the inlet or outlet...

Страница 22: ...When the outdoor temperature is below 0 drainage may be unavailable if the drain hose freezes 3 4 Recommended places An area with no head wind An area with no direct sunlight An area in which the win...

Страница 23: ...oninwhichwaterworksareavailable Installthedomestichotwatertankinalocationinwhichitiseasytoperformrepairandmaintenanceactivities Installthedomestichotwatertankinaplacewithnomoistureandthatisequippedwit...

Страница 24: ...ated place A place that is not directly exposed to hot wind from a heating device X Poorly ventilated place X A place near a window or door subject to the influence of drafts from the gap X A place su...

Страница 25: ...damages to the product Warning Transport the product with care A product with a weight of over 20kg should be carried by at least 2 people The plastic packing bag should be torn into pieces when disp...

Страница 26: ...cessing of pipe 1 2 Install the oil trap and liquid loop at the correct position depending on the installation location of the indoor outdoor unit The maximum allowable length of piping is 30m Bend a...

Страница 27: ...LPM and the recommended flow ranges from 35 to 40LPM The maximum allowable pressure is less than 0 98 bar Install a ball valve at each side of a pump to facilitate the cleaning and repair of the pump...

Страница 28: ...r Service ballvalve 15A Strainer Ball valve 25A Domestic hot water pump output less than 80W Air vent Check valve 25A Drain valve Expansiontank Water supply valve DHW tank temperature sensor Remote co...

Страница 29: ...e water pipe should be at least the same size as the connection pipe of the product When connecting a water pipe with a socket apply fastening torque as specified in the table below Applying more torq...

Страница 30: ...ture sensor into the cap hole of the sensor holder Lock the sensor holder cap Connect the sensor cable to the terminal of domestic hot water tank temperature sensor in the indoor unit Domestic Hot Wat...

Страница 31: ...th the ground s surface Be sure the end of the pipe is pointed downward toward the floor when you remove the burrs after machining a pipe Pay extra attention when performing piping work on a rainy day...

Страница 32: ...about the installation and characteristics of R410A product please see the service guide of Carrier inverter air conditioning system Attention There should be no moisture or dust 1 There should be no...

Страница 33: ...orr you should replace the oil if oil is mixed with dust or moisture coming from outside during the vacuum operation it takes longer or may be impossible to achieve the desired vacuum state 9 1 1 2 2...

Страница 34: ...t to expose the inside of the copper pipe to the atmosphere for a period exceeding the specified time Gradient Wrinkle Crack Uneven thickness There should be no burr at the end part of the flare and t...

Страница 35: ...according to the specified lengths of connection pipes First fasten the fitting by hand and then fasten it further using a wrench at a specified torque Fastening of connections Insufficient fastening...

Страница 36: ...ot provided Caution Remove the cap from the 3 way valve Generate a vacuum using the vacuum pump connected to the shut off valve gas on the suction side Maintain the shutdown state until the vacuum pre...

Страница 37: ...f refrigerant per 1m of extra pipe length Example 5m No additional refrigerant charging is required 25m 25m 5m x 40g 800g of additional refrigerant charging is required If the amount of refrigerant is...

Страница 38: ...ng power supply cable perform wiring work between the hydro unit and the outdoor unit Connect the electric wire firmly to the terminal in accordance with the wiring diagram When connecting to the powe...

Страница 39: ...cable together using a cable tie or other fixing devices As the power of the outdoor unit is supplied from the indoor unit connect to R S T N of the terminal block No 1 in the indoor unit Combining t...

Страница 40: ...ring will cause malfunctions of the controller however polarity does not matter when connecting each load When connecting the wired remote controller connect to the A1 B1 and terminals correctly Incor...

Страница 41: ...e power supply refer to the wiring diagram between outdoor unit and indoor unit on page 36 Caution Perform grounding work first before connecting wires Specifications of main power cable of Indoor uni...

Страница 42: ...ram between the outdoor unit and indoor unit on the page 36 Caution Perform grounding work first before connecting wires Cable specifications between Outdoor Unit and Indoor Unit Note 1 Use power cabl...

Страница 43: ...rence to the table below DIP S W Specifications SW1 1 2 3 4 ON New market Automatic control on Heater control on Not used OFF Replacement market Automatic control off Heater control off Not used Detai...

Страница 44: ...ts Check the temperature of supply water Installationofwater pipingsystem Verificationof abnormalitiesinthe waterpipingsystem Carryoutdesignofthesystemincludingheatingload waterflowandinstallationloca...

Страница 45: ...ating mode of the boiler to the user turning the product on and off functions of the remote controller Verify and check whether air has completely vented whether supply water flows seamlessly whether...

Страница 46: ...on The system automatically enters stop mode after 3 hours of test operation Automatically selects and performs the heating operation according to the outdoor temperature Operation other than Tact swi...

Страница 47: ...of Hydro Unit for more than 30 seconds in stop status of the system and then the outdoor unit will start the recovery operation right after releasing from TACT switch Recovery operation can be termin...

Страница 48: ...osed properly when performing cleaning Connect a pipe to service valve for cleaning and fill cleaning agent with a temperature of 50 to 60 into the brazed plate heat exchanger and circulate it for 4 t...

Страница 49: ...Insufficient water flow may cause freezing and bursting in the brazed plate heat exchanger Make sure that the strainer is not clogged or filled with air and determine whether the water flow is suffic...

Страница 50: ...n Scale Basic item pH 25 7 0 8 0 7 0 8 0 O O Electrical conductivity 25 mS m 30 30 O O Chloride ion mg Cl 50 50 O Sulfate ion mg S O 50 50 O Acid consumption pH 4 8 mg CaCO 50 50 O Total hardness mg C...

Страница 51: ...to any unrepairable used product Failures caused by nonconformance to the precautions for installation is not covered by the warranty and will incur service fees Grounding of the product is mandatory...