Table 2 — LID Display Data (cont)
EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT .
LEAD/LAG CONFIGURATION SCREEN
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
0-3
leadlag
0
Load Balance Option
DISABLE/ENABLE
loadbal
DISABLE
Common Sensor Option
DISABLE/ENABLE
commsens
DISABLE
LAG Percent Capacity
25-75
%
lag
per
50
LAG Address
1-236
lag
add
92
LAG START Timer
2-60
MIN
lagstart
10
LAG STOP Timer
2-60
MIN
lagstop
10
PRESTART FAULT Timer
0-30
MIN
preflt
5
STANDBY Chiller Option
DISABLE/ENABLE
stndopt
DISABLE
STANDBY Percent Capacity
25-75
%
stnd
per
50
STANDBY Address
1-236
stnd
add
93
27