Table 2 — LID Display Data (cont)
EXAMPLE 4 — STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS04.
4. Press SELECT .
DESCRIPTION
RANGE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
Main Gear Oil Pump
OFF/ON
MAINPMP1
Auxiliary Gear Oil Pump
OFF/ON
AUXPMP2
Gear Oil Pressure
−6.7 to 420 (−46 to 2896)
psi (kPa)
GEAROILP
Gear Oil Temperature
−40 to 245 (−40 to 118)
DEG F (DEG C)
GEAROILT
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SETPOINT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Base Demand Limit
40-100
%
DLM
100
LCW Setpoint
20-120 (–6.7-48.9)
DEG F (DEG C)
lcw
sp
50.0 (10.0)
ECW Setpoint
20-120 (–6.7-48.9)
DEG F (DEG C)
ecw
sp
60.0 (15.6)
ICE BUILD Setpoint
20- 60 (–6.7-15.6)
DEG F (DEG C)
ice
sp
40.0 ( 4.4)