LEGEND
CB
— Circuit Breaker
COMM — Communications
N.O.
— Normally Open
N.C.
— Normally Closed
O.L.
— Overload
PR
— Pilot Relay
RLA
— Rated Load Amps
SMM
— Starter Management Module
TB
— Terminal Block
Starter Vendor Supplied Wiring
Field Wiring
Carrier Factory Wiring
NOTE: Voltage to terminals LL1 and LL2 comes from a control trans-
former in a starter built to Carrier specifications. Do not connect an
outside source of control power to the compressor motor starter (ter-
minals LL1 and LL2). An outside power source will produce danger-
ous voltage at the line side of the starter, because supplying voltage
at the transformer secondary terminals produces input level voltage
at the transformer primary terminals.
Fig. 59 — Elementary Wiring Diagram for Starter Management Module (SMM) and Control Interface Between
Starter and Chiller Power Panel (For Low and Medium Voltage Free-Standing Starters)
110